If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual CITADEL XR2-ENGINEERING INFORMATION. We hope that this CITADEL XR2-ENGINEERING INFORMATION user guide will be useful to you.
Lastmanuals help download the user guide CITADEL XR2-ENGINEERING INFORMATION.
Manual abstract: user guide CITADEL XR2-ENGINEERING INFORMATION
Detailed instructions for use are in the User's Guide.
[. . . ] XR2/ XR2+
Features
Power
Intruder alarm system Engineering Information
RKP PART SET
8z
MEM
4
REMOTE
8
6
OUTPUT
5 09
SET
ÿ
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 Tamper Attack
8 zones, all programmable for Security, Fire, 24H Fire, PTS or keyswitch applications PA input Tamper input Outputs for Bell and Strobe 4 Access level Codes, User 1, User 2 and Engineer and Duress, all programmable 3 fully selectable part set programs Chime on any zone 8 event memory Programmable timers including bell cut off Walk Test facilities Quick set feature Remote keypad with on board PA and illuminated keys Option for connection of Lighting controllers Options to connect up to four remote keypads / Lighting controllers NVM for protection of engineer programme 6 digital outputs for a wire-in digital communicator, Red Care STU or dialler Service warning indicator, programmable between 100 and 800 set and unset events Battery capacity of up to : 2. 1Ah in XR2 enclosure 7Ah in XR2+ enclosure Features
0 5
Chime
1 6
Omit
2 7
Reset
3 8
Prog
4
PA
9
Set
Day
Power
8SP 403 XR2+ G3 panel with remote LED keypad
ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ ÿ
Power
ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 Tamper Attack
0 5
Chime
1 6
Omit
2 7
Reset
3 8
Prog
4
PA
9
Set
Day
Power
Accenta/!mini
8SP 404 XR2 G3 panel with remote LED keypad
The above intruder system is designed to comply with the installation requirements of BS 4737 1986/87. This manual provides information on Installation design, panel fixing, wiring, power up and programming of the intruder panel.
4188-694 issue 1_8/01
1
Downloaded from: http://www. guardianalarms. net
Engineering information
Contents
Features - - - - - - - - - - - - - Installation Design - - - - - - - - Fixing - - - - - - - - - - - - - - Wiring the system - - - - - - - - Tamper network - - - - - - - - - Connecting Remote Keypads / Lighting controllers - - - - - - - Fixing the Remote Keypad (RKP) Security zones - - - - - - - - - - Push to set zone - - - - - - - - - Remote keyswitch zone - - - - - Fire zone - - - - - - - - - - - - PA circuit - - - - - - - - - - - - Extension speaker - - - - - - - - Bell Output (External sounder) - - 13V Supply output - - - - - - - - Set - - - - - - - - - - - - - - - Remote signalling Input and Outputs 1 2 3 4 4 5 5 5 6 6 7 7 8 8 9 9 9 11 12 12 13 13 13 13 13 13 14 15 15 15 16 17 18 18 19 19 20 21 22 23 24 25 26 27 31 31 32
Citadel XR2/XR2+ G3 Intruder system
Installation Design
The purchase of this alarm system represents a major step forward in the protection of the property and its occupants. It is important to plan the installation before proceeding and then follow the procedures and advice contained in this manual. [. . . ] Where an intruder alarm is shortly followed by a restore at the ARC, this can be used to filter the alarm.
c.
10
4188-694 issue 1_8/01
Citadel XR2/XR2+ G3 Intruder system
Engineering information
Factory set condition
User code 1 - User code 2 - Duress Code - Engineer Code Bell Duration Bell Delay - - Program 1 Zone 1 - - Zone 2 - - Zones 3. . . 8 Exit time- Entry - - Exit mode Program 2 Zone1 - - Zone 2 - - Zone 3. . . 8 Exit time- Entry time Exit mode Program 3 Zone 1 - Zone 2 - Zone3. . . 8 Exit timeEntry time Exit mode 0123 Not programmed Not programmed 9999 20 minutes No delay Flag A Silent PA - - - - - - RKP PA Enable - - - Engineer Reset- - - - Anti Code Reset - - - Door bell on push to set Single key setting - - Strobe on setting - - - External bell on Fire - Flag B Communicator Output active high - - - - - Line Fail active high - - - - - User Reset PA - - - User Reset Fire - - - Program 1 to report - Program 2 to report - Program 3 to report - Rearm counter - - - Service counter - - - Site Code - - - - - - Light Controller Light Threshold Light Hold Time Light Channel 1 Light Channel 2 Light Channel 3 Light Channel 4 Light Channel 5 Light Channel 6 Light Channel 7 Light Channel 8 -
-
-
-
-
-
-
Timed Time Inhibited Immediate 30seconds 30seconds timed
-
-
No Yes No No No No No No
- - - - No (active low) No (active low) No No Yes Yes Yes 3 (re-arms) Off 00 Factory set condition
-
-
-
-
-
-
Timed Time inhibited Immediate 30seconds 30seconds Disabled
-
-
-
-
-
-
-
Timed Time Inhibited Immediate 30seconds 30seconds Disabled Zones 1. . . 8 None programmed None programmed None programmed None programmed None programmed None programmed 300mS ALL zones
Security Zones - - - Standard Fire zones 24 hour Fire zones - Push to set zones - - Keyswitch zones - - Double Knock zones Omit prevent zones- Zone debounce period
-
-
-
-
-
50% 30 seconds No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned No zones assigned
4188-694 issue 1_8/01
11
Engineering information
Citadel XR2/XR2+ G3 Intruder system Note: The panel is not supplied with wire links for unused zones. All unused zones must be programmed out by setting them to disabled using the Zone Type function see page 20.
First Power up
To power up for the first time: a. Check that the factory fitted links are connected to terminals PA, TAMP and T-A. Fit the battery wires to the BATT terminals on the PCB, Red to + and Black to -.
Panel
BATTERY
b.
Mains Connection
The mains power should be connected using a 3 core cable of not less than 0. 75mm sq. from a fused spur to the mains connector inside the control panel. The 2A fused spur must be located close to the control panel.
Dedicated mains supply from consumer unit.
F1
Board
J4 +BATT AC
1. 6A
(red) +
Black -
N E L 125mA Fuse
2A Fused Spur unit
Panel
BATTERY
F1
Board
J4 +BATT AC
First Power up
12V battery
Transformer
c.
On connecting the battery the system will now go into alarm condition and Tamper is indicated
Tamper
1. 6A
and there is an audible
(red) +
Black -
N E L 125mA Fuse Transformer
d.
Alarm. Fit the cover to hold down the tamper spring at the bottom centre of the PCB.
12V battery
e.
Enter the user code: 0 1 2 3 (factory set at 0123). The alarm condition will cease and the system will go to Day mode . Immediately enter the engineer code
Prog
Day
Note: The mains supply must be connected by a technically competent person and according to current IEE regulations. Caution: To avoid the risk of electrical shock you must always totally isolate the mains supply before opening the control panel cover(s).
Mains Input Fuse rating: 125mA, 250V type T (anti surge) and of a type approved to IEC 127 part 2 sheet III. On connecting the mains supply to the panel the power indicator is lit.
Power
f.
. The system is now in Engineer program mode and can be programmed. Note the
Tamper
9
9
9
9
ÿ
Tamper indicator is lit.
12
4188-694 issue 1_8/01
Citadel XR2/XR2+ G3 Intruder system
Engineering information
Testing the system
Complete the wiring of the system and then:
System indications
Day Power
ÿ ÿ ÿ ÿ
- Unset system indication
Fully test the system and ensure it is fault free. Fill in the installation log at the back of the manual and retain if for future reference. Finally explain the operation of the system to the end user. The Operating Instructions are attached to the centre of this manual. Detach them and leave them with the user.
Power
- Set system indication
To enter Engineer program mode
Note: The factory configured engineer's access code is 9999. If however this code is changed then enter the appropriate code.
Prog
ZONE 1 - 8 Momentarily On
Engineer program mode
The panel may be programmed to suit a wide variety of installations. Once the engineer program mode has been accessed, each configuration may be changed in any order. As each configuration is completed the system will automatically return to top level of engineer program mode. Before entering engineer program mode the system should be in the Day mode, with the Day and Power indicators lit. Keys
9
9
9
9
Acknowledge
Tamper
Day
To Exit Engineer program mode
Reset
Day
LED steady On indication LED flashing indication LED Off
o/p ARC Output to Alarm Receiving Centre
To reset panel to Factory set conditions
Caution: All configurations of the panel are restored to factory `default' conditions.
Within 5 seconds of powering up the panel
Reset Reset
Internal sound
Sound description
NOTE: In general a flat beep is an indication of an incorrect key press. [. . . ] The following points outline the most common installation and commissioning faults. As supplied the user code is 0123 and the engineer code is 9999. Both codes will revert back to these default settings on clearing the NVM. The Engineer Program is accessed directly from Day mode via the engineer code. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE CITADEL XR2-ENGINEERING INFORMATION
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.