User manual HONEYWELL T7560A

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual HONEYWELL T7560A. We hope that this HONEYWELL T7560A user guide will be useful to you.

Lastmanuals help download the user guide HONEYWELL T7560A.


Mode d'emploi HONEYWELL T7560A
Download

You may also download the following manuals related to this product:

   HONEYWELL T7560A DATASHEET (724 ko)

Manual abstract: user guide HONEYWELL T7560A

Detailed instructions for use are in the User's Guide.

[. . . ] Disconnect the power supply before making connections DWM DISASSEMBLY The T7560A, B, C comes packed with a sub-base that mounts separately for ease of installation. The cover is fixed by a latch on the underside of the unit. Insert the tip of an awl or a similar narrow, pointed object into the small hole in the latch (T7560A, B) or simply depress the latch by hand (T7560C). Pry off the cover. to or removing connections from the DWM's terminals. Do not reconnect the power supply until you have com- pleted the installation. If the DWM is powered via terminal 8 and connected to earth ground, then the cable must be shielded. Observe precautions for handling electrostatic sensitive devices. Fig. [. . . ] 15 Vdc Imax 4 mA or LED output of any Excel 10 controller Terminal 8: 24 Vac from controller; I < 6 mA or 18 Vdc (I < 2. 4 mA) . . . 30 Vdc (I < 10 mA) Controllers with the following output ratings can be connected to terminal 5 (ratings are met by all Excel 10 controllers): · 5 V with 389 · 4. 3 V with 100 · 14. 3 V with 1. 5k Use up to 16 AWG (1. 5 mm2) with a minimum of 18 AWG (1. 0 mm2) wire for connecting 24 Vac power to terminal 8. Fig. Mounting cover of T7560A, B DWM CAUTION Low Voltage Equipment. The 24 Vac power source for the DWM must be a Class II Power Source. To conform to Class II restrictions, transformers must not be larger than 100 VA. A transformer that is CE certified and meets the Low Voltage Device (LVD) requirements must be used in Europe for all installations of this product. The DWM power usage is < 0. 2 VA at 24 Vac. The DWM does not require a dedicated transformer. The DWM can get power from any convenient location in the 24 Vac power circuit. The 24 Vac power can come from the 24 Vac power terminals on the nearest controller or directly from a 24 Vac transformer, whichever is closer. When all wiring is complete, attach the cover of the DWM as is shown in Fig. NOTE: Make sure that the latch on the underside of the DWM engages properly. Fig. DWM dimensions in inches (mm) 3 EN1B-0146GE51 R0309B T7560A, B, C DIGITAL WALL MODULES CONFIGURATION (T7560A, B) After installation, the T7560A, B DWM must be configured in order to perform as desired. This is done by using the buttons and the setpoint wheel (see Fig. 7). In the following, default settings are marked with an asterisk (*). P1 Setpoint Type Setting / Scale Type Setting · Fahrenheit relative · Fahrenheit absolute Celsius relative * Celsius absolute · P2 · * · Room Temperature Setting Do not display room temperature (setpoint, only) Display room temperature Display room temperature and humidity, alternating every 5 seconds (T7560B, only) Bargraph Use Setting No Fan Auto, Off, On Auto, Off, 2 Speeds Auto, Off, 3 Speeds Controller Type Setting New LCD signaling from controller (only for controllers and SW versions as listed in Table 2 or higher, in which case this setting must be selected; set Excel 10 controller to LCD_DISPLAY) LED override mode from controller, US signaling (100 ms pulses); with contr. W7750, W7751, W7753, W7761, and XL12 LED override mode from controller, European signaling (500 ms pulses); with contr. W7752, W7762, W7763, and XL12 (in the case of SW versions as listed in Table 2 or higher, select ). LED occupancy mode from controller, European signaling (500 ms pulses); with contr. W7752, W7762, W7763, and XL12 Same as Excel 500 signaling from controller (10 V, 8 V, 6 V) Pin 4 (Bypass/Fan) Grounding Pin 4 not shorted to GND if override is pressed (UV-controller, W7753) Pin 4 shorted to GND if override is pressed P3 Fig. Control elements of T7560A, B DWM Normal Operating Mode After the DWM is powered up by the controller, it will display the room temperature and will operate as configured by default; the respective default setting is marked with an asterisk in the following. After power-up, all display segments are switched on for approx. [. . . ] Default (if set to Celsius): Default (if set to Fahrenheit): Example (units set to Celsius): A setting of means that the set point offset is limited to -3 to +3 °C. Example (units set to Fahrenheit): A setting of means that the set point offset is limited to -8 to +8 °F. Limit for humidity low limit output value Limit the output value to 10 . . . This affects the output voltage on pin 7, only, and has no effect upon values appearing in the display. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL T7560A

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets...
In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.

Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual HONEYWELL T7560A will begin.

Search for a user manual

 

Copyright © 2015 - LastManuals - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.

flag