User manual OMRON MX2 DEVICENET OPTION BOARD

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual OMRON MX2 DEVICENET OPTION BOARD. We hope that this OMRON MX2 DEVICENET OPTION BOARD user guide will be useful to you.

Lastmanuals help download the user guide OMRON MX2 DEVICENET OPTION BOARD.


Mode d'emploi OMRON MX2 DEVICENET OPTION BOARD
Download
Manual abstract: user guide OMRON MX2 DEVICENET OPTION BOARD

Detailed instructions for use are in the User's Guide.

[. . . ] I112E-EN-01 MX2 DeviceNet Option Board Born to drive machines Model: 3G3AX-MX2-DRT-E USER'S MANUAL Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property. OMRON Product References All OMRON products are capitalized in this manual. [. . . ] Not all assemblies support setting the external trip by using a bit in IO Data. Basically there are two options: · Select an assembly which support this trip set in the output data. · Using explicit message to set the Force Fault/Trip attribute in the Control Supervisor Object ( Class 29 Hex, Instance 01 Hex, Attribute 11 Hex). The two Extended Control IO assemblies (Output 101, Input 151) contains the FFL (Force Fault/Trip) bit and can be used for this feature. Step 1 Step 2 Follow the instructions sections 3-1 Installation of EDS files and 3-2 Configuring the Option Board to configure the assemblies. Set bit 8 (FFL) of the first word of the output data to trip the Inverter. The alternative is to use the explicit message mechanism to generate the external trip. Please refer to APPENDIX E DeviceNet Explicit Messages example 3 for a description how to do this. 4-5-2 Clearing a Trip When the inverter trips due to a fault condition first analyse the trip cause as explained in section 5-1 Troubleshooting Using the LED Indicators on page 33 or section 5-3 Maintenance and Inspection on page 38. Notice that the FLT bit is set (present in all output assemblies) when the Inverter trips. !WARNING In the event the Inverter is in a Trip state, be sure to investigate the cause of this Trip state thoroughly before clearing the Trip. Not checking the cause may result in unexpected operation. Please clear the FWD and REV bits in your PLC program when a rising edge is detected on FLT. Set the RST bit of the output assembly to clear the trip. Step 1 Step 2 25 Accessing Parameters !WARNING Section 4-6 Always clear the run bits FWD and REV in your PLC program on the rising edge of the FLT bit. Not doing so may result in the motor starting unexpectedly when the trip is cleared via DeviceNet or the , , Stop/reset" button on the Inverter 4-6 Accessing Parameters DeviceNet explicit messages sent from the Master Unit to the 3G3AX-MX2-DRT-E Unit can be used to access any parameter from the Unit or the MX2-A@ Inverter. Please refer to the APPENDIX E DeviceNet Explicit Messages on page 71 for details and examples. Refer to the DeviceNet Master Units Operation manual (Cat. W380) for details on how to send the explicit messages to the 3G3AX-MX2-DRT-E. Below are examples for usage of the OMRON CJ1W-DRM21 Master Unit with the FINS Explicit Message Send command (2801). 4-6-1 Accessing General (AC Drive Profile) Objects Reading the value of MX2-A@ inverter input terminal [4]. Command: 28 01 0E 00 08 00 04 03 Attribute ID Command Code Destination node address Response: Class ID Instance ID Service Code 28 01 00 00 03 8E 01 Data Service code Command Code End Code No. of bytes received Source node address The value of input terminal [4] is ON. 4-6-2 Accessing Inverter parameter using Function Code Object Writing the value of the acceleration time (F002) to 3. 00 seconds (012C Hex). The parameter F002 corresponds to address 5002 (138A Hex). Please note the swapping of the data following CIP data type encoding. Command: 28 01 10 00 65 00 13 8A 2C 01 00 00 Command Code Destination node address Response: Class ID Instance ID Service Code Data Attribute ID 28 01 00 00 02 90 Command Code End Code No. [. . . ] 51 Extended Speed and Acceleration Control Output - Assembly 110 Description. 51 Extended Speed and Acceleration Control Input - Assembly 111 Allocation . 52 Extended Speed and Acceleration Control Input - Assembly 111 Description . 52 Identity Object - Supported Service Codes . [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON MX2 DEVICENET OPTION BOARD

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets...
In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.

Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual OMRON MX2 DEVICENET OPTION BOARD will begin.

Search for a user manual

 

Copyright © 2015 - LastManuals - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.

flag