If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual SAUNIER DUVAL SD 30E. We hope that this SAUNIER DUVAL SD 30E user guide will be useful to you.
Lastmanuals help download the user guide SAUNIER DUVAL SD 30E.
Detailed instructions for use are in the User's Guide.
[. . . ] 221873B. 07. 01
Instructions for Use Installation and Servicing
To b e l e f t w i t h t h e u s e r
7086
SD 30e
G. C. 47-920-16
Fanned Flue Combination Boiler
This is a Cat I2H Appliance
The instructions consist of three parts, User, Installation and Servicing Instructions, which include the Guarantee Registration Card. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.
Guarantee Registration
Thank you for installing a new Saunier Duval appliance in your home. Saunier Duval appliances' are manufactured to the very highest standard so we are pleased to offer our customers' a Comprehensive First Year Guarantee. [. . . ] The burner pressure is factory preset and no adjustment should be required. Check the burner pressure is within +/-0. 2mbar. If this is incorrect, the burner pressure may be adjusted to the correct setting by turning the hot water gas pressure adjuster (potentiometer), located on the control board. To gain access remove the two screws securing the controls facia, see diagram 9. 1. Using the burner adjusting tool supplied. (clockwise to increase), see diagram 10. 2. Turn the adjuster slowly, always making adjustment by reducing below the required pressure then increasing up to the required setting. Close the hot water draw off.
GAS CONTROL VALVE CONNECTION
BURNER PRESSURE TEST POINT Diagram 10. 1 CHASSIS EARTH LEAD
6989
SECURING SCREW (2) Slacken do not remove
CABLE ENTRY COVER
CLOCK-TIMER COVER
SENSING LEAD IGNITION LEAD (2)
IGNITION RATE SETTING POTTENTIOMETER
PLASTIC PLUGS
DOMESTIC HOT WATER BURNER PRESSURE POTENTIOMETER
SECURING SCREW (4)
CONTROL BOARD COVER
22
BURNER PRESSURE ADJUSTING TOOL
HEATING BURNER PRESSURE POTENTIOMETER Diagram 10. 2
221873B
7811
10 Commissioning
If the maximum pressure cannot be obtained, check that the gas supply of adequate size, refer to Section 1. 7.
10. 8 Ignition Rate
Set the mains electrical switch "B" to 0, located on the controls fascia, see diagram 3. Disconnect the sensing lead at the connection, see diagram 10. 2. Set the mains electrical switch "B" to 1. The electrode will continue to spark for (10 seconds approx. ) to enable the ignition to be set and checked before going to lockout. Check the ignition rate is set to 6. 0 mbar +/-1. 0 mbar, adjust if required by turning the ignition rate setting potentiometer using the adjustment tool supplied, If this is not achieved before the boiler goes to lockout the process can be repeated as required by pressing the rest button "G", see diagram 3. When set, switch the mains electrical switch "B" to 0. Set mains electrical switch "B" to 1, depress the rest button "G" if required. Isolate the boiler from the electrical supply. Replace plastic plugs, screw cap and adjusting tool. Disconnect the pressure gauge, tighten the burner pressure test point screw . Take care not to splash any of electrical components. Refit control fascia.
10. 5 Gas Rate Modulation
The burner pressures are factory preset and no adjustment should be required. When checked if they are not consistant with the information in table 1. Fully open a domestic hot water tap ensure there is no modulation. Turn the domestic burner pressure potentiometer to minimum by turnining anticlockwise with the tool supplied (do not force it), see diagram 10. 2. [. . . ] Replace heat exchanger making sure that it is correctly engaged on the retaining lugs at the back of the combustion chamber, carefully refit the pipe securing clips and front retaining clips.
SECURING CLIP
PUMP
Diagram 14. 23
BAFFLE
HEAT EXCHANGER
SIDE INSULATION (2)
FRONT RETAINING CLIP (2)
COMBUSTION CHAMBER MAIN PANEL BASE BAFFLE
SECURING SCREW (2) BEADING
SECURING SCREW (4) PIPE SECURING CLIP (2) 'O' RINGS Diagram 14. 24
39
221873B
9376
7494
14. 26 Heat Exchanger
14 Replacement of Parts
9379
REAR INSULATION SIDE INSULATION SIDE INSULATION FRONT INSULATION Diagram 14. 25 MICA WINDOW OPENING (BOILER INNER CASE FRONT) PEEL OFF BACKING PAPER Diagram 14. 26 SELF ADHESIVE ALUMINIUM FOIL GASKET AIR PRESSURE SWITCH SECURING SCREW (2) AIR PRESSURE SWITCH TUBE (2) RED ELECTRICAL CONNECTION (2) CLEAR Diagram 14. 27
40
COMBUSTION CHAMBER FRONT PANEL
Remove outer case front as section 11. 4. Remove the inner case front as Section 11. 5. Unhook the combustion chamber front, see diagram 8. 2. Remove the front insulation piece, see diagram 14. 25. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE SAUNIER DUVAL SD 30E
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.