If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual BENSHAW MV ATL STARTER. We hope that this BENSHAW MV ATL STARTER user guide will be useful to you.
Lastmanuals help download the user guide BENSHAW MV ATL STARTER.
Manual abstract: user guide BENSHAW MV ATL STARTER
Detailed instructions for use are in the User's Guide.
[. . . ] BENSHAW
REDISTART MICRO II ATL STARTER MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MVRSM SERIES
Solid State Motor Control
Technology
Publication #: 890015-09-00
The Leader In
TABLE OF CONTENTS
Table of Contents 1. Computer Card JC11 Header Assignments RediStart Micro II Power Card Jumpers . RediStart Micro II Computer Card Jumpers . 34 35 36 36
i
TABLE OF CONTENTS
5. 2 PROGRAMMING: Quick Start . [. . . ] The default value for the starts per hour parameter is Off.
Values
Default
Time Start (time between starts)
Description The time between starts parameter sets the minimum allowed time between starts. Once a start command has been given, the next start cannot be performed until this time has expired. If the starter is stopped and the time between starts has yet to expire, the starter will display TBS in the top left of the display and the time, in minutes, until the next start is allowed in the bottom left of the display. The time between starts is adjustable from 1 to 600 minutes, in 1 minute intervals. The time between starts can also be set to Off by going below 1 minute. The default value for the time between starts parameter is Off.
Values
Default
BKS Timer (backspin timer)
Description The backspin timer parameter sets the minimum time between a stop and the next allowed start. If the starter is stopped and a time has been set, the starter will display BKS in the top left of the display and the time, in minutes, until the next allowed start in the bottom left. The backspin timer is adjustable from 1 to 200 minutes, in 1 minute intervals. The backspin timer can also be set to Off by going below 1 minute. The default value for the backspin timer parameter is Off.
Values
Default
48
5. 12 PROGRAMMING: Motor Protection - Active Timers
UTS Timer (up-to-speed timer)
Description The up-to-speed timer parameter sets the maximum acceleration time to full speed that the motor can take. A stalled motor condition will be detected if the motor does not get up-to-speed before the up-to-speed timer expires. This allows the programming of a maximum acceleration time for the motor. The motor is considered up-to-speed once the unit has achieved slip speed. Fault Code 74 - Up to Speed Fault will be displayed when a stalled motor condition is detected. Values The up-to-speed timer parameter can be set from 1 to 300 seconds. The up-to-speed timer can be set to Off by setting it below 1 second. The default value for the up-to-speed timer parameter is 30 seconds.
Default
Zero Speed
Description When using the zero speed stall protection, the starter will start monitoring the zero speed input (at JC13-8) as soon as a run command is given and will recognize a stalled motor if the zero speed time has elapsed before the zero speed signal is removed. The zero speed input requires a 120VAC signal to indicate the zero speed condition. Fault Code 69 - Zero Speed Timer will be displayed when a stalled motor condition is detected. NOTE: The zero speed timer is not available on synchronous starters. Values The zero speed parameter can be set from 0 to 30 seconds, The zero speed timer can be set to Off by setting it below 1 second. The default value for the zero speed parameter is Off.
Default
49
5. 13 PROGRAMMING: Motor Protection - Permissive Input
M Contactor
Description The starter has a 120VAC feedback input from the M contactor It uses this feedback to check that the contactor is energized when it should not be. [. . . ] ONLY) 1 2 3 4 5 6 7 8
1 2 SW1 SW2 (RIGHT - ON)
TBP12 SCR GATE 6
TBP4 CURRENT TRANSFORMERS
1 2 3
TBP13 TACH. INPUT
87
7. 1 DRAWINGS
RediStart Micro II Four (4) Relay Card Layout
TB2 RELAY OUTPUTS
1 24
TB1 CARD POWER
1 2
J1 RIBBON CABLE CONNECTOR
RediStart Micro II Seven (7) Relay Card Layout
K1 Relay
1 2 3
K2 Relay
4 5 6
K3 Relay
7 8 9
K4 Relay
10 11 12
K5 Relay
13 14 15
K6 Relay
16 17 18
K7 Relay
19 20 21
K1
K2
K3
K4
K5
K6
K7
HOT 1 2 3 4 NEUTRAL
FU1 J1
TB3 120Vac Connector
J1 Ribbon Cable Connector
88
7. 1 DRAWINGS
RediStart Micro II RS-232 Communications Card Layout
RECEIVE TRANSMIT
DEVICE ENABLE
RIBBON CABLE CONNECTOR
LED4 LED3 SP DE
LED2 TXD
LED1 RXD
RS-232 IC
RS232 CARD
BENSHAW INC.
PC-1362 REV 1 BIPCMCOMS
J2 TB1
TX/RXGND TX/RX+ RS-232 CONNECTORS
RediStart Micro II RS-485 Communications Card Layout
RECEIVE TRANSMIT
DEVICE ENABLE
RIBBON CABLE CONNECTOR
LED3 DE
LED2 TXD
LED1 RXD
RS485 CARD
RS-485 IC
BENSHAW INC.
PC-1362 REV 1 BIPCMCOMS
TB1 J3
TX/RX+ GND TX/RXRS-485 CONNECTORS
89
7. 1 DRAWINGS
RediStart Micro II Reversing Card Layout
TB3 SCR GATE 1A
1 2
TB4 SCR GATE 4A
1 2
TB5 SCR GATE 3A
1 2
TB6 SCR GATE 6A
1 2
TB2 GATE POWER
1 2
4 3 2 1
TB1 GATE SIGNALS
Modbus Master Card (for Remote RTD Module)
24VDC FROM POWER CARD
J3 Gnd+24V
24VDC POWER SUPPLY
Com +24V J8 DE TxD RxD
REMOTE RTD MODULE CONNECTOR
A B Com Shield J6
D4
D5
D6
J7
CPU J1
Display J2 U3
RECEIVE TRANSMIT DEVICE ENABLE
U6
CPU RIBBON CABLE CONNECTOR
J5 U5 U7
DISPLAY RIBBON CABLE CONNECTOR
810007 02-00
U1
U4
D3 LED1
D2 LED2
UJ1 UJ2
VALID SLAVE RESPONSE STATUS
90
7. 1 DRAWINGS
RediStart Micro II Display Cut-out
2 27/32"
MICRO DISPLAY CUT-OUT TEMPLATE (May not print to scale)
2 15/16"
CUT-OUT SIZE: 5-3/8" x 2-5/8" HOLE PATTERN: 5-11/16" x 2-15/16" HOLE SIZE: 3/16"
5 11/16"
91
8.
PARAMETER LIST
8. 1 Parameter List
RediStart Micro II Parameter List
General The following pages list the menu parameters for the RediStart Micro II. The list gives the page number where information on the parameter can be found. The list can also be used to record the values that are programmed into the RediStart Micro II for the installation. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE BENSHAW MV ATL STARTER
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.