[. . . ] RediStart Micro II Computer Card Jumpers . 16 16 17 21 21 21 22
i
TABLE OF CONTENTS
4. 26 27 31 31 32 33 33 34 35 35 36 37 38 38 40
5. 42 43 44 44 45 45 45 45 46 46 46 47 47
5. 2 PROGRAMMING: Quick Start . [. . . ] Values The decel level #1 is adjustable from 10% to 100% in 1% increments. The decel level #1 setting must be greater than the decel level #2 setting. The default value for the decel level #1 parameter is 40%.
Default
V Level #2
Description The V Level #2 parameter sets the ending voltage for the voltage ramp profile. Decel level #2 can not be set greater than decel level #1. The deceleration profile uses an open loop voltage ramp profile. The decel level #2 parameter sets the ending point on the S curve. This means that decel level #2 is not set as a percentage of actual line voltage. If the motor stops rotating before the deceleration time has expired, increase this parameter value. If the motor is still rotating when the deceleration time has expired, decrease this parameter value. A typical decel level #2 setting is between 10% and 20%. Values The decel level #2 parameter is adjustable from 1% to 99% in 1% increments. The default value for the Sense Time parameter is 0. 05 seconds.
Values
Default
58
5. 10 PROGRAMMING: Starter Setup - TruTorque Ramp
Int Torque (initial torque)
Description The initial torque parameter sets the initial torque level that the motor will produce during starting. This parameter should be set to a level that allows the motor to begin acceleration with a few seconds of a start command being received. The initial torque is adjustable from 1% to 100% in 1% increments. The default value for initial torque is 20%.
Values Default
Max Torque (maximum torque)
Description The maximum torque parameter sets the final level of torque that is supplied to the motor during starting. For a loaded motor, the maximum torque parameter initially should be set to 100% or greater. If the maximum torque value is set too low, the motor may not produce enough torque to reach full speed (UTS). On a lightly loaded motor this parameter may be reduced below 100% to provide for smoother starts. The maximum torque is adjustable from 10% to 325% in 1% increments. The default value for the maximum torque parameter is 105%.
Values Default
Ramp Time
Description The ramp time parameter sets the time it takes for the commanded torque to go from the Initial Torque Setting to the Maximum Torque Setting. To make the motor accelerate faster, decrease the ramp time. To make the motor accelerate slower, increase the ramp time. [. . . ] ONLY)
1 2
TBP10 SCR GATE 5
1 JP1 COMPUTER CARD RIBBON CABLE 2
1
TBP11 SCR GATE 3
LEDP3 SCR STATUS (LOW VOLT. ONLY) 1 2 3 4 5 6 7 8
1 2 SW1 SW2 (RIGHT - ON)
TBP12 SCR GATE 6
TBP4 CURRENT TRANSFORMERS
1 2 3
TBP13 TACH. INPUT
112
7. 1 DRAWINGS
RediStart Micro II Four (4) Relay Card Layout
TB2 RELAY OUTPUTS
1 24
TB1 CARD POWER
1 2
J1 RIBBON CABLE CONNECTOR
RediStart Micro II Seven (7) Relay Card Layout
K1 Relay
1 2 3
K2 Relay
4 5 6
K3 Relay
7 8 9
K4 Relay
10 11 12
K5 Relay
13 14 15
K6 Relay
16 17 18
K7 Relay
19 20 21
K1
K2
K3
K4
K5
K6
K7
HOT 1 2 3 4 NEUTRAL
FU1 J1
TB3 120Vac Connector
J1 Ribbon Cable Connector
113
7. 1 DRAWINGS
RediStart Micro II RS-232 Communications Card Layout
RECEIVE LED TRANSMIT LED
RIBBON CABLE CONNECTOR TO COMPUTER CARD
LED1 RXD
LED2 TXD
RS-232 IC
RS232 CARD
J2
TB1
9-PIN SUB-D MALE DCE PINOUT RS-232 CONNECTORS
TXD C COM RXD
RediStart Micro II RS-485 Communications Card Layout
RECEIVE LED TRANSMIT LED
DRIVER ENABLE
RIBBON CABLE CONNECTOR TO COMPUTER CARD
LED1 RXD
LED3 DE
LED2 TXD
RS485 CARD
RS-485 IC
TB1
J3
B(+) COM A(-) RS-485 CONNECTORS
9-PIN SUB-D FEMALE
114
7. 1 DRAWINGS
RediStart Micro II RS-232/485 Communications Card Layout
RIBBON CABLE CONNECTOR TO COMPUTER CARD
TRANSMIT LED RECEIVE LED
120 OHM TERM SHIELD TO COM
RS-485 CONFIGURATION SWITCHES
RS-485 TERMINAL BLOCK RS-232 CONNECTOR 9 PIN, SUB-D, FEMALE DCE PINOUT
Modbus Master Card (for Remote RTD Module)
24VDC FROM POWER CARD
J3 Gnd+24V
24VDC POWER SUPPLY
Com +24V J8 DE TxD RxD
REMOTE RTD MODULE CONNECTOR
A B Com Shield J6
D4
D5
D6
J7
CPU J1
Display J2 U3
RECEIVE TRANSMIT DEVICE ENABLE
U6
CPU RIBBON CABLE CONNECTOR
J5 U5 U7
DISPLAY RIBBON CABLE CONNECTOR
810007 02-00
U1
U4
D3 LED1
D2 LED2
UJ1 UJ2
VALID SLAVE RESPONSE STATUS
115
7. 1 DRAWINGS
RediStart Micro II Display Cut-out
2 27/32"
MICRO DISPLAY CUT-OUT TEMPLATE (May not print to scale)
2 15/16"
CUT-OUT SIZE: 5-3/8" x 2-5/8" HOLE PATTERN: 5-11/16" x 2-15/16" HOLE SIZE: 3/16"
5 11/16"
116
8.
PARAMETER LIST
8. 1 Parameter List
RediStart Micro II Parameter List
General The following pages list the menu parameters for the RediStart Micro II. The list gives the page number where information on the parameter can be found. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE BENSHAW RS11
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.