REDISTART DIGITAL RSD6 SERIES INSTRUCTION MANUAL
Solid State Motor Control
Technology
Publication #: 890001-05-07
The Leader In
QUICK START GUIDE
Quick Start
General This quickstart guide provides the information necessary for the operator to set the starter for basic operation. This manual should be read in its entirety before the starter is put into service.
· Connect the incoming power connections to terminals L1, L2 and L3. · Connect the motor leads to T1, T2, and T3. · Connect the control wiring to TB1 on the control card, as shown in the following
diagram. [. . . ] If the motor stops rotating before the deceleration time has expired, increase this parameter value. NOTE: P9 is not used in any of the controller modes.
Parameter Values
The motor deceleration level 2 parameter values range from 0% through 100%. Parameter values are set in 1% increments. NOTE: The motor deceleration level 2 parameter's value must be less than the motor deceleration level 1 parameter's value. If the deceleration level 2 parameter is set higher than the deceleration level 1 parameter, the starter will swap the deceleration level 1 and deceleration level 2 settings when decel is commanded.
Parameter Default
The motor deceleration level 2 parameter's default value is 10%.
4. 11
Parameter Description
P10 - Deceleration Time
The motor deceleration time parameter sets the deceleration time from motor deceleration level 1 to motor deceleration level 2. Deceleration time is the amount of time during which the starter will gradually reduce the amount of line voltage being delivered to the motor (after a Stop command has been received). The motor deceleration time parameter is not functional when the motor deceleration control jumper JP1 on the control card is in the disabled position. When this parameter is set to any value other than OFF, the motor deceleration Level 1 and motor deceleration Level 2 parameters must be programmed. When the motor deceleration time parameter is set to OFF, the motor deceleration level 1 and motor deceleration level 2 parameters are disabled. If the motor is still rotating when the deceleration time expires, increase the deceleration time. If the motor stops rotating before the deceleration time expires, decrease the deceleration time. NOTE: If the motor deceleration time parameter is set to OFF, the motor's deceleration is not controlled by the starter. If the motor needs to be stopped faster than the time it takes to coast to a stop, the deceleration control will not help. NOTE: P10 is not used in any of the controller modes. NOTE: If deceleration jumper JP1 is in place and deceleration time is programmed, the deceleration will not operate. The deceleration timer will block a restart attempt until it has timed out. This can operate as a blocked restart timer for up to 1 minute. This is useful for reversing starters or dual starters.
Parameter Values
The motor deceleration time parameter values range from OFF to 60 seconds. Parameter values are set in 1 second increments. The motor deceleration time parameter's default value is OFF.
Parameter Default
24
4. OPERATING PARAMETERS
4. 12
Parameter Description
P11 - Overcurrent Trip Level
The overcurrent trip level parameter sets the high current level trip point as a percentage of motor full load amps parameter P1. The overcurrent trip level parameter takes effect after the motor is up to speed. [. . . ] This will reset all the parameters to the default settings listed above. The reset can also be performed to clear a passcode that has been forgotten. To automatically reset the operating parameter to the default settings: Single Phase While the power to the control card is off: · Hold the Parameter push button and the Down push button on the control card. While continuing to hold the Parameter and Down push buttons. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE BENSHAW RSD6
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.