If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual BENSHAW RSI (S-SERIES) METASYS N2 CARD. We hope that this BENSHAW RSI (S-SERIES) METASYS N2 CARD user guide will be useful to you.
Lastmanuals help download the user guide BENSHAW RSI (S-SERIES) METASYS N2 CARD.
Manual abstract: user guide BENSHAW RSI (S-SERIES) METASYS N2 CARD
Detailed instructions for use are in the User's Guide.
[. . . ] The N2 protocol interface is RS-485 utilizing a differential pair of signaling wires plus a common or reference wire. The transmission format is 8 data bits, 1 stop bit and no parity. The baud rate is fixed at 9600 bits per second. The card provides a terminal block for the N2 interface. [. . . ] Input points provide information from the drive to the N2 network. The N2 network commands values to the drive through output points. The following tables describe all of the inputs and outputs defined by the drive's Metasys N2 card. The heading NPT stands for Network Point Type. The heading NPA stands for Network Point Address.
3. 1
Analog Outputs
Analog Output (AO) objects are used to configure the drive. Values of AO objects are changed by issuing override commands. AO objects will not report an override active status and issuing an override release command will not restore an AO object to its previous value. AO objects do not support Change of State (COS).
NPT NPA Units Description Range / Value Notes Can not be set higher than the Freq. Max parameter in the drive (FUN code 04). Max parameter must be set through the drive's keypad. 0. 00 400. 00 The drive only uses this value if the Frequency Set parameter (AO-4) is set to Remote. This value is not saved when power to the drive is lost. AO 2 Sec Accel Time 0. 0 6000. 0 The drive only uses this value if the Frequency Set parameter (AO-4) is set to Remote. This value is not saved when power to the drive is lost. AO 3 Sec Decel Time 0. 0 6000. 0 0 Key 1 Terminal 2 Remote 0 Key 1 Terminal-1 2 Terminal-2 3 Remote The drive only uses this value if the Frequency Set parameter (AO-4) is set to Remote. This value is not saved when power to the drive is lost. AO 4 Frequency Set
AO
1
Hz
Command Frequency
AO
5
-
Run/Stop Set
7
I/O POINT MAP
3. 2
Binary Outputs
Binary Output (BO) objects are used to control the drive. Values of BO objects are changed by issuing override commands. BO objects will not report an override active status and issuing an override release command will not restore a BO object to its previous value. BO objects do not support the Minimum On-time, Minimum Off-time or Maximum cycles per hour functions.
NPT BO BO BO BO BO NPA 1 2 3 4 5 Description Stop Run Forward Run Reverse Reset Fault Coast to Stop (BX function) Range / Value 1 Stop 1 Run Forward 1 Run Reverse 1 Reset 1 Coast The drive may be stopped by resetting this to 0 or by setting BO-1 to 1 or by setting BO-5 to 1. [. . . ] The ERR LED should never light.
4. 1
CPU LED
Indicates · The card is installed properly and working normally. · Card not installed properly · Drive not operating normally · Verify that the card is installed properly · Verify that the drive has power Corrective Measures
State Blinking Off
4. 2
RXD and TXD LEDs
Indicates · The card is functioning normally and receiving and sending messages · Incorrect N2 connection to the card Off · Master is not polling · Verify that the N- signal is connected to terminal N and the N+ signal is connected to terminal P · Verify that the master is polling the drive Corrective Measures
State Blinking
4. 3
ERR LED
Indicates · The card is functioning normally and receiving and sending messages · The card is receiving invalid requests · Trouble with the Metasys N2 card · Verify that the master is specifying valid register addresses and valid data · Contact Benshaw Corrective Measures
State Off Blinking On
10
BENSHAW SERVICES
5. Benshaw Services
Benshaw offers its customers the following services: · Start-up services · On-site training services · Technical support · Detailed documentation · Replacement parts Benshaw technical field support personnel are available to assist customers with the initial start-up of the RSi S-Series Inverter. Information about start-up services and fees are available by contacting Benshaw. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE BENSHAW RSI (S-SERIES) METASYS N2 CARD
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.