User manual BENSHAW RSM10

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual BENSHAW RSM10. We hope that this BENSHAW RSM10 user guide will be useful to you.

Lastmanuals help download the user guide BENSHAW RSM10.


Mode d'emploi BENSHAW RSM10
Download
Manual abstract: user guide BENSHAW RSM10

Detailed instructions for use are in the User's Guide.

[. . . ] BENSHAW REDISTART MICRO II INSTRUCTION MANUAL RSM10/10B/11/11B SERIES Solid State Motor Control Technology Publication #: 890015-03-08 The Leader In TABLE OF CONTENTS Table of Contents 1. Computer Card JC11 Header Assignments RediStart Micro II Power Card Jumpers . 8 8 8 8 8 9 9 9 9 10 11 12 13 14 15 15 15 3. RediStart Micro II Computer Card Jumpers . [. . . ] If the jog at set speed will be used on a regular basis, the motor temperature should be monitored using a thermostat. The thermostat can be connected between the power and input terminal 1 of the JC13 terminal block on the RediStart Micro II computer card so that the starter will trip when a fault occurs. Alternatively, temperature monitoring devices, such as thermistors or RTDs can be used. This will prevent the motor from being overheated and inadvertently damaged. Due to the way the jog at set speed operates, the starter may require the installation of a 5% line reactor to eliminate harmonic problems being introduced into the power system. This is dependent on the size of the motor in relation to the capacity of the power system. The jog at set speed has more of an effect on a weak power system. Values Default The jog current is adjustable from 25% to 250% in 1% increments. The default value for the jog current is 50%. Max. Time (maximum time) Description The maximum time parameter sets the time limit for continuous operation in the jog at set speed mode. This parameter should be set to a value that doesn't allow the motor to be operated in the jog at set speed mode for such a length of time that damage to the motor can occur. During initial set-up, monitor the motor temperature to determine it's maximum safe jogging time and then enter this time. This can help avoid damage to the motor by stopping the starter before the motor overheats. This parameter does not stop the operator from stopping and re-starting the motor during jog operation which could still lead to the operation time of the motor being exceeded. Use the timers in the Starts Lockouts submenu to protect against this. Values Default The maximum time is adjustable from 1 to 9000 seconds in 1 second intervals. The default value for the maximum time parameter is 200 seconds. 63 5. 9 PROGRAMMING: Starter Setup - Jog Cntrl Setup Kick Curr (kick current) Description The kick current parameter sets the level of the kick current that is applied to the motor when a start command is given and the starter is set for operation in the forward jog at set speed mode. This parameter should be set to a midrange value and then the kick time should be increased in 0. 1 second intervals until the kick is applied long enough to start the motor rotating when a start is given. If the motor does not start rotating with the set kick current value then increase the kick current and begin adjusting the kick time from 0. 1 seconds again. If the motor accelerates to a speed which is greater than the jog speed, then either the kick current or kick time should be decreased. Values Default The kick current parameter is adjustable from 50% to 400% in 1% increments. The default value for the kick current parameter is 300%. Kick Time Description The kick time parameter sets the length of time that the current level, as specified by the kick current, is applied to the motor. [. . . ] Default 100 600 15 300 Off User Setting _______________ _______________ _______________ _______________ _______________ Step Unit Default Curr Coas User Setting _______________ _______________ 132 8. 1 Parameter List Parameter Forward2 Profile Int. Kick Time Parameter Reverse1 Profile Int. Kick Time Parameter Reverse2 Profile Int. Kick Time Parameter Jog Cntrl Setup Jog Curr. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE BENSHAW RSM10

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets...
In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.

Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual BENSHAW RSM10 will begin.

Search for a user manual

 

Copyright © 2015 - LastManuals - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.

flag