Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual DANFOSS RX3. We hope that this DANFOSS RX3 user guide will be useful to you.
Lastmanuals help download the user guide DANFOSS RX3.
Detailed instructions for use are in the User's Guide.
[. . . ] Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only.
This guide is associated with ECL Card 087B4974 Installer: By: Date:
The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.
= Closes
If the system you are about to install differs from the shown diagram of a standard heating system, feel free to sketch an outline for comparison. Adaptation of systems, see section 10.
S2
S1
ECL Comfort 301
List of components:
Room temperature sensor
Circuit indicator
Circuit Shift selector button
Adjust- Controller ment mode
M2 M1 P3 P1 S6 S5 S4 S3
Motorized control valve, circuit II Motorized control valve, circuit I Circulation pump, DHW, circuit II Circulation pump, heating, circuit I DHW return temperature sensor, circuit II DHW flow temperature sensor, circuit II Return temperature sensor, circuit I Flow temperature sensor, circuit I Outdoor temperature sensor
Table of Contents
Sections in the Installer's Guide
The documentation for the ECL Comfort controller is composed of numbered sections. Only sections relevant to your ECL Comfort controller are included here. Before you start
Installation
10 11 12 14 15 Identifying the system type Mounting the ECL Comfort controller Electrical connections 230 V a. c. [. . . ] 50 25 141 Override input selection OFF / 1 . . . 6 °C OFF
15 °C
40 °C
°C
-15 °C
°C
60 °C
°C
-2. 0
0. 0
37 Time constant for return temperature limitation OFF / 1 . . . 50 25 43 Parallel operation of DHW and heating circuits OFF / 1 . . . 99 K OFF 52 Closed valve / normal operation ON / OFF 141 Override input selection OFF / 1 . . . 6 OFF OFF
K
32
Adjusting the service parameters
Service parameter(s) 10-11
10 Choice of room panel / remote control Circuit Setting range
32a
Factory setting
In addition to the settings in line 1 to 7 on the grey side of the ECL Card, there is an extended service menu from line 10 and onwards. Push repeatedly to reach the lines numbered 10 and onwards.
I 0 . . . 5 0 Decides the communication with the room panel or remote control. Please note that the room panel / remote control is only active if the system device bus is active. The bus is active when the outdoor temperature sensor is connected.
0
Line
Value
10
Range indicator
Now you can move to any line of your choice.
Choose between 0: Room temperature sensor (no room panel / remote control) 1: Room panel ECA 60 / 62 or remote control ECA 61 / 63 with address A 2: Room panel ECA 60 / 62 or remote control ECA 61 / 63 with address B 3 . . . You can select any of the two circuits no matter what line you are in. You will not necessarily enter the same line number. This is done by integrating the difference and adjusting the desired flow temperature. 1: 30: The desired temperature is adapted quickly. The desired temperature is adapted slowly.
The grey side of the ECL Card
The grey side of the ECL Card
32d
Circuit
Service parameter(s) 17-20
Service parameter(s) 21
21 Total stop Circuit Setting range
32e
Factory setting OFF
17 Influence on desired flow temperature (Tflow. ref(I)) Setting range Factory setting I OFF / 1 . . . 20 K OFF The desired flow temperature in heating circuit I can be influenced by an external reference.
I ON / OFF Decide whether you want a total stop during the setback temperature period.
OFF: The desired flow temperature in circuit I is not influenced by any other controller (slave or circuit II). 20: The desired flow temperature is increased by the set value (line 17), if the demand of a slave / circuit II is higher.
Temp. Setting line 17
ON:
The desired flow temperature is lowered to 10 °C. setting of the flow temperature (line 2, section 22) is overruled.
Desired flow temp. (°C)
Tflow. ref(I) 10 °C Tflow. ref(II) Time Time
OFF: No total stop
Desired flow temp. (°C)
Example: If a slave controller (or circuit II) demands a higher temperature than that of the master controller (Tflow. ref(I)), the temperature of the master will be increased accordingly (Tflow. ref(II)) + the setting (line 17).
The function of line 17 can compensate for heat losses between master and slave controlled systems.
10 °C
Extended service
Extended service
20 Optimization based on room / outdoor temperature Circuit Setting range Factory setting I ON / OFF OFF The optimized start and stop time can be based on either room or outdoor temperature.
Time
ON:
Optimization based on room temperature, if measured.
OFF: Optimization based on outdoor temperature. Use this setting if the room temperature is not measured.
The grey side of the ECL Card
The grey side of the ECL Card
32f
Circuit
Service parameter(s) 22-24
Service parameter(s) 30-34
30 Return temperature limitation
32g
Factory setting
22 Pump exercise Setting range Factory setting I ON / OFF ON Exercises the pump to avoid blocking in periods without heat demand.
Circuit
Setting range
II 10 . . . 110 °C 50 °C Set the return temperature you accept for the heating / DHW circuit.
ON:
The pump is switched ON for 1 minute every third day around noon.
Set the acceptable return temperature limit. [. . . ] In the DHW circuit, however, the DHW temperature is controlled according to the setback temperature.
The setting of the desired room temperature is important even if a room temperature sensor / room panel / remote control is not connected. Make sure that the radiator thermostat does not limit the room temperature. If you still cannot obtain the desired room temperature by adjusting the radiator thermostats, the flow temperature is too low. Increase the desired room temperature.
Circuit II: Setting the desired DHW temperature
55
Desired DHW temp. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE DANFOSS RX3
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual DANFOSS RX3 will begin.