[. . . ] Any work done on the actuator may only be carried out by authorized and trained personnel. These products are according to the Machine Guidelines 98/37/EG (ancient 89/392/EWG), not regarded as machines; they are, however, built into installations which are regarded as machines. Note We distinctly emphasize that operation is prohibited until it has been confirmed that the machine (plant) into which the products have been built corresponds to the conditions of the EC Machine Guidelines 98/37/EG (ancient 89/392/EWG).
44
¬
2. Design of the actuator
The standard version of the electrical actuator EA 41 consists of the following elements: spurwheel gear, DC motor, power supply board for the DC motor, transformer as well as components for limit positioning. [. . . ] Limit switch positions Switch S1 opens at <open> position Switch S2 opens at <closed> position (see diagram in the margin) Procedure Both switching cams S1 and S2 are to be adjusted so that the actuating angle is less than 90°). Drive the actuator until one limit switch, either <closed> or <open>, is operated. The end positions can be adjusted by moving the switching cams, as the actuator follows them. ¼ For George Fischer ball valves an exact 90°) rotation should be set. ¼ For George Fischer butterfly valves the <closed> position should be adjusted according to the following directions.
S2 S1
¬
49
G/2 a
Setting the <closed> position in actuators At the <closed> position in butterfly valves, the disk is not exactly vertical to the pipe axis. Deviation values can be taken from the following table.
open
ab
b
DN mm 100 125 150 200
d mm 110 140 160 225
ab mm 5 5 6 6
50
¬
5. Specifications
Nominal voltage 1@5 / 230 V, 5060 Hz (selectable) 24 V=/24 V, 5060 Hz 48 V, 5060 Hz on request 72 W IP 65 according to DIN 40050 50% at 25°C/30% at 50°C, 20 min current-time dependent (self resetting) 1) unit plug 3 P + GND according DIN 43650 additional cable port PG 11 8 s/90° ) max. 270°, set at 90° 60 Nm 200 Nm 10 to +50°C 2) 098%, non-condensing UPGF external screws corrosion-free visual, integrated
1)
Rated performance Protection class Duty rating Overload protection Electrical connection Operating time Operating angle Nominal torque Peak torque Ambient temperature Allowable humidity Housing material Position indicator
The overload protection is designed to protect both motor and power supply board. If the overload protection device has triggered, it will reset automatically when the unit has cooled down sufficiently and the actuator will operate again. For temperatures below 10°C the heating element Nr. 199 190 142/. . 143 should be installed (see Item 6. 5).
2)
¬
51
5. 1 Block Diagram
input voltage selection 230 V 115 V
power supply overload protection
<open> L <closed>
1
S1
2 3
S2
M
N
230 V 115 V
reversing circuit
5. 2 Dimensions
38
60
150
@02
8
70
@02
M8 x 8 17
2@0
. . .
8 220
220
52
23
@49
¬
6. Assembly and Connection of Modular Components
The electrical actuator EA 41 is equipped with fastening points which allow for additional modular components to be mounted. The configuration of these points is described under Section 2. The modular components are connected electrically over the free terminal points (714). The external wiring is done via a multiple wire cable through a threaded cable joint. The respective kits are prepared for installation; the electric cables are ready to use. [. . . ] 5 / 230 V /5060 Hz Power supply unit 5 / 230 V /5060 Hz 24 V / 48 V Housing seal NBR Housing cover Electrical Actuator, complete 100240 V /5060 Hz 24 V / 48 V /50-60 Hz Code Number 198 000 147 198 802 700 198 321 003 198 321 002 198 198 198 198 198 150 150 150 802 802 456 457 458 379 703
5 6 7
198 150 470 198 150 471 198 150 469
3
2
5 1 4
Butterfly Valve Type 035
d mm 110 140 160 225 DN mm 100 125 150 200 Intermediate housing Intermediate housing with manual override without manual inch override 4 198 000 122 198 000 128 5 198 000 123 198 000 129 6 198 000 124 198 000 130 8 198 000 125 198 000 131
Ball Valve Type 108
d mm 110 160 DN mm 100 150 Intermediate housing with manual override inch 4 198 000 134 6 198 000 134 Warning: Beware of turning bolt in the intermediate housing with manual override
¬
60
¥
A AUS B/L CH CHINA D Georg Fischer Rohrleitungssysteme GmbH, Sandgasse 16, 3130 Herzogenburg Tel. +43(0)2782/8 56 43-0, Fax +43(0)2782/8 51 56, e-mail: office@georgfischer. at George Fischer Pty. Ltd. , 4 Jacks Road, South Oakleigh, Victoria 3¢67 Tel. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE GEORG FISCHER EA41
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.