If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual GRACO VARIABLE FREQUENCY DRIVE. We hope that this GRACO VARIABLE FREQUENCY DRIVE user guide will be useful to you.
Lastmanuals help download the user guide GRACO VARIABLE FREQUENCY DRIVE.
Manual abstract: user guide GRACO VARIABLE FREQUENCY DRIVE311596F
Detailed instructions for use are in the User's Guide.
[. . . ] Instructions
Variable Frequency Drive
Motor drive control for Graco E-Flo® Electric Circulation Pumps.
Important Safety Instructions
Read all warnings and instructions in this manual. Save these instructions.
311596F
See page 3 for approvals information.
Part No. 15J753, 200-240 Vac
UNIDRIVE SP Digital AC Drive 208/230VAC, 5HP, SP2201
Part No. 15J754, 380-480 Vac
UNIDRIVE SP Digital AC Drive 460VAC, 5HP, SP1405
UNIDRIVE Information
Unidrives are manufactured by Control Techniques Corporation. [. . . ] E-Flo system is a constant torque application, and therefore the motor's constant torque limits must not be violated. The system is available with two motors: the UL/CSA explosion-proof motor and the ATEX explosion-proof motor. To stay within the allowed torque, flow and pressure limits are installed.
Running the Pump
CAUTION The drive has been programmed by Graco. Do not attempt to recalibrate the Sequencer or Motor Control as it can interfere with the Graco Program.
Flow Limit
Speed command is limited to 5:1 operation for ATEX motors and 10:1 operation for UL/CSA motors. 5:1 dictates a frequency of 10 Hz minimum to 50 Hz maximum. 10:1 dictates a frequency of 6 Hz minimum to 60 Hz maximum. See TABLE 2 for flow limits (Pr 20. 05).
Secure Disable
According to Control Techniques Unidrive SP User Guide, "Secure Disable (SD) function provides a means for preventing the drive from generating torque in the motor, with very high level of integrity". This hardware function controls enable/disable state of the drive. Secure Disable/Drive enable hardware input (VFD terminal #31) is designed for positive logic input only. It should be connected to internal 24VDC power supply (VFD terminal #22). The SD is a fail-safe function; it enables the drive when 24VDC is connected to SD hardware input and disables (inhibits) the drive when SD hardware input is open. Pr 6. 29 and Pr 8. 09 can be used to monitor state of the Hardware enable input. Local I/O Box (see page 5) provides a normally closed Secure Disable switch, which has a red mushroom-type button (press to latch, pull to unlock). When latched, switch opens SD circuit, therefore disabling (inhibiting) the drive. When unlocked, switch closes SD circuit, enabling the drive.
Pressure Limits
Operating pressure limits are unique to the pump lower sizes. If the system pressure is greater than the maximum allowed for a given pump lower size for longer than 30 seconds, system Trip #44 will shut the system down. Table 3: System Pressure Limits Graco Motor (Pr 20. 37 = 0, 1, 3, or 4) psi 250 330 460 425 (if set to 3 or 4); 500 (if set to 0 or 1) bar 17. 2 22. 8 31. 7 29. 3 (if set to 3 or 4); 34. 5 (if set to 0 or 1) Non-Graco Motor (Pr 20. 37 = 2) psi 250 330 460 500 bar 17. 2 22. 8 31. 7 34. 5
Lower Size (cc) 2000 1500 1000 750
311596F
21
Running the Pump
Start/Stop Command
Local Control Mode
When Local mode is selected, Run command can only be initiated by means of Run/Stop hardware switch set Run/Stop switch to Run position. Stop command can be initiated by one of the following: 1. Run/Stop switch: Set Run/Stop switch to Stop position. Stop/Reset button: Press Stop/Reset (red) button on a VFD Keypad display. Note that if Stop command was initiated by pressing Stop/Reset button, one of the following two actions will restart the pump: a. Cycle the Run/Stop switch Set it to Stop position and then to `Run' position. [. . . ] With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco's written recommendations. This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE GRACO VARIABLE FREQUENCY DRIVE
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.