[. . . ] Owner's Manual
Installation and Operation
Models: RH-36 Series RH-42 Series
Wood Burning Fireplace
NOTICE
DO NOT DISCARD THIS MANUAL
· Important operating · and maintenance instructions included. Read, understand and follow these instructions for safe installation and operation. · Leave this manual with party responsible for use and operation.
T O N RD OA D SC I
WARNING
If the information in these instructions is not followed exactly, a fire may result causing property damage, personal injury, or death. · Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. [. . . ] A small dip is acceptable for a cold air trap. The outside air kit must be installed on the left hand side of the fireplace. Locate the outside air hood in a clear area, preferably into prevailing wind during the heating season. Install as shown in Figures 7. 3, 7. 4 and 7. 5. The outside air hood must be at least 3 ft (. 91 m) below the top of the uppermost chimney section. DO NOT draw outside combustion air from wall, floor or ceiling cavity, or enclosed spaces such as an attic or garage. · DO NOT place outside air hood close to exhaust vents or chimneys. Fumes or odor could be drawn into the room through the fireplace. · Locate outside air inlet to prevent blockage from leaves, snow/ice, or other debris. Blockages could cause combustion air starvation.
Flexible Duct (not supplied)
· · ·
Outside Air Hood
2 Wire Ties
Outside Air Plate Assembly
Figure 7. 5
Outside Air Installation
22
Heat & Glo · RH-36/RH-42 · 4044-153 · Rev V · 08/08
8
Chimney Assembly
NOTICE: Chimney performance may vary. · Trees, buildings, roof lines and wind conditions affect performance. · Chimney height may need adjustment if smoking or overdraft occurs.
Chimney must extend beyond combustible roof structure Maintain minimum height of chimney above roof
Termination Cap Additional support for tall chimneys Storm Collar Maintain minimum clearances to combustibles as specified Support straps for returns must be secured to adequate framing Offsets and returns must be secured with the screws provided (outer pipe only)
Install roof flashing according to minimum requirements
Offsets/returns may not exceed 30° from vertical
Lock chimney sections together firmly to resist movement Ceiling firestops are required where chimney passes through ceiling or floor
Figure 8. 1 Typical Chimney System - Guidelines for Chimney System Installation
Heat & Glo · RH-36/RH-42 · 4044-153 · Rev V · 08/08
23
A. Chimney Requirements
Measure vertical distances from the base of the fireplace as shown in Figure 8. 2.
· Minimum overall straight height · Minimum height with offset/return · Maximum height · Maximum chimney length between an offset and return · Maximum distance between chimney stabilizers · Double offset/return minimum height · Maximum unsupported chimney length between the offset and return · Maximum unsupported chimney height above the fireplace · Maximum unsupported chimney above roof 13 14. 5 ft 90 ft 20 ft 35 ft 20 ft 6 ft 35 ft 6 ft (3. 96 m) (4. 42 m) (27. 43 m) (6. 1 m) (10. 67 m) (6. 1 m) (1. 83 m)
Determine the chimney components needed to complete your particular installation: · Measure the total vertical height of the fireplace installation from the base of the fireplace assembly to the approximate location of the bottom of the termination cap. Subtract the effective height of the fireplace assembly (see Figure 8. 2) from the total vertical height to determine the overall height of the chimney installation. Create a schematic for your application similar to Figure 8. 2 showing components required (referring to Table 8. 1). Figure 8. 1 identifies those components and where used. Install a ceiling firestop whenever the chimney penetrates a floor/ceiling. NOTICE: A maximum of two pairs of offsets and returns may be used. DO NOT connect this fireplace to a chimney flue servicing another appliance. DO NOT connect to any air distribution duct or system. These actions could cause overheating/fire in the chimney flue, or release of exhaust fumes into the living areas.
·
·
·
(10. 67 m) (1. 83 m)
WARNING!(51 mm) air space clearance to insulation and other combustible materials around the chimney system. [. . . ] (787 mm)
RF371 Roof Flashing
24-5/8 in. (625 mm)
26 in.
CT-3A
TR-TVK TR Top Vent Kit
Heat & Glo · RH-36/RH-42 · 4044-153 · Rev V · 08/08
47
20 in. (238 mm)
TR344 Round Termination Cap
15-3/4 in. (235 mm)
TCT375 Terra Cotta Cap
34-3/4 in. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HEAT AND GLO RH-36
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.