[. . . ] THREE-WAY ROTARY VALVE PN10 AND HE25/32 EXTENSION
PRODUCT DATA
DRU/HE
FEATURES
· Chrome-plated plug for long life-span · Optimized characteristics for supply water temperature control · All around changeable rotary plug · Reliable and easy mounting of electrical actuators · Wide range of flow rates in two housing sizes · Compact design · Use for manifolds by accessory HE25/32 Extension · Thermal insulation package included
APPLICATION
The DRU25/32 Three-Way Rotary Valve provides water temperature control in heating and air-conditioning applications. These valves are designed for accurate mixing control of supply water temperature and return-flow temperature. [. . . ] The required flow water temperature is achieved by adding a proportion of return water to the boiler hot water. The DRU has special control characteristics for optimal control performance.
SUITABLE ACTUATORS
torque [Nm] 10 20 OS no. 0/2. . . 10V M7061E1012 M7061E1020 / VRM20
MOUNTING
Adjustments for Mixing Applications
0
9
9
0
9
0
0
9
EN0B-0608GE51 R0108
2
DRU/HE PRODUCT DATA
Mounting the Actuator
SPECIFICATION AND ORDER NUMBER PER DN
OS No. DRU25-2. 5 DRU25-4. 0 DRU25-6. 3 DRU25-10 DRU25-16 DRU32-10 DRU32-16 DRU32-25 HE25 HE32 DN 25 25 25 25 25 32 32 32 25 32 kvs [m³/h] 2. 5 4. 0 6. 3 10. 0 16. 0 10 16 25 heat flow [kW] 7-12 12-17 17-30 30-50 50-70 30-50 50-70 70-100 p [kPa] 100 100 100 100 100 100 100 100 nom. torque [Nm] 10 10 10 10 10 20 20 20 actuator floating modulating
M6061A1013, M6061A1021 / VMM20-24, M6061L1019, M6061L1027 / VMM20
M7061E1012, M7061E1020 / VRM20
-
-
ACCESSORIES
connection set description Welding sockets with gasket and cap nut DN 25 32 25 25 25 32 32 32 25 32 pipe size [mm] 25 32 18 22 28 22 28 35 25 32 weight [kg] 0. 3 0. 6 0. 21 0. 21 0. 21 0. 42 0. 42 0. 41 0. 21 0. 40 OS No. WTU25 WTU32 LSU25-18 LSU25-22 LSU25-28 LSU32-22 LSU32-28 LSU32-35 STU25 STU32
Soldering sockets with gasket and cap nut
Internal threaded sockets with gasket and cap nut
3
EN0B-0608GE51 R0108
DRU/HE PRODUCT DATA
DIMENSIONS
DRU
type DRU25-2. 5 DRU25-4. 0 DRU25-6. 3 DRU25-10 DRU25-16 DRU32-10 DRU32-16 DRU32-25 DN 25 25 25 25 25 32 32 32 a 55 55 55 55 55 70 70 70 b 32 32 32 32 32 44 44 44 c 110 110 110 110 110 140 140 140 d 89 89 89 89 89 99 99 99 e 55 55 55 55 55 70 70 70 g 51 51 51 51 51 59 59 59 h 182 182 182 182 182 200 200 200 R 1½ 1½ 1½ 1½ 1½ 2 2 2 weight [kg] 2. 2 2. 2 2. 2 2. 2 2. 2 4. 1 4. 1 4. 1
a
b
d
R
c e g g h
HE
type HE25 HE32
= g
DN 25 32
a 110 140
b 42 51
e 55 70
b
f 0-25 0-50
g 51 59
R 1½ 2
weight [kg] 1. 7 2. 7
f e
a
R
EN0B-0608GE51 R0108
4
DRU/HE PRODUCT DATA
HYDRAULIC FUNCTION
Characteristics
100% 80% 60% 40% 20% 0% V5434T 2 3 4 5 6 7 8 9
Spare Parts
· O-ring (part no. : 07169 9535)
5
EN0B-0608GE51 R0108
DRU/HE PRODUCT DATA
VALVE DIMENSIONING
Honeywell Rotary Valves are employed mainly in hydraulic systems corresponding to the examples shown on page 2. The rotary valve can be set quite easily. In order to obtain good control characteristics, the pressure drop in the rotary valve should be about the same as the pressure drop in the "volume-variable" part of the pipe system, i. e. The following dimensioning diagram is based on this interrelationship. 4.
& Find heat flow Q
in the diagram.
& Move vertically upwards to the intersection with the corresponding line. On the vertical axis, the volume flow V can be read off on the left in liters per hour. Move horizontally to the right from the intersection with the line into the shaded section (1. 5-4. 0 kPa). [. . . ] (Factor 1. 163 contains the water density 1000 kg/m and the specific heat capacity 4. 19 kJ/kgK. is the temperature difference between supply and return flow in Kelvin)
3
Unit Conversion
1 kW = 3600 kJ/h = 860 kcal/h 1000 kcal/h = 1. 163 kW
1 bar = 100 kPa = 10 m water column 1 mbar = 10 mm water column
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions Honeywell GmbH Böblinger Straße 17 D-71101 Schönaich Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc. emea. honeywell. com Subject to change without notice. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL DRU-HE
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual HONEYWELL DRU-HE will begin.