Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual HONEYWELL F. We hope that this HONEYWELL F user guide will be useful to you.
Lastmanuals help download the user guide HONEYWELL F.
You may also download the following manuals related to this product:
HONEYWELL F WITH ED3 (209 ko)
HONEYWELL F INSTALLATION (654 ko)
Manual abstract: user guide HONEYWELL FDATASHEET
Detailed instructions for use are in the User's Guide.
[. . . ] 1 W 010 V, 210 V (± 1 mA), 020 mA, 420 mA (3-conductor system) All outputs are invertible. Rising pressure produces a rising output signal (default setting). Voltage and current output can also be picked up and used simultaneously. Terminals 58 are reserved for later expansions and must not be connected as this would destroy the device. [. . . ] 1 W for each additional module plugged in. Long-term drift Repetition accuracy Accuracy class Temperature drift Influence of static pressure Mounting position Ambient temperature Max. medium temperature
Connection schemes Terminal connection
Storage temperature
Plug connection
!Important: When connecting to control systems with a common AC supply, the ground conductor must be looped through. That is to say, on all devices in the system, the same reference potential must be present at the corresponding ground terminal (terminal 2). In the case of a DC supply, ensure correct polarity.
ED 3 output signal 010 V
Pressure transmitters
71
Ty p e s e r i e s F
Adjustment and operation Operating ranges and output signals are adjustable over a wide range.
An outstanding characteristic of the pressure transmitters is the variability of the characteristic curve, which means that the pressure range and output signal can be adapted to any subsequent control system. P0 = starting pressure of nominal range PN = nominal pressure (end point of nominal range) PA = starting pressure of set range PE = end pressure of set range Operator interface ED 1 1 = Setting spindle for setting the final value PE 2 = Setting potentiometer for setting the initial value PA 3 = Slide switch for selecting the output signal 020 mA (010 V) or 420 mA (210 V) 4 = Slide switch for inverting the output signal 5 = Slide switch for changing the steepness of the characteristic in a ratio of 8:5. Normal position: 8 For smaller operating ranges (< approx. 70% of the nominal range), select position 5 6 = Plug connector for further evaluation modules
Output signals for module ED 1
Basic setting The factory default setting covers the nominal range P0 (usually 0 bar) to PN.
Altering the range The range can easily be altered by shifting the end point and adjusting the steepness of the characteristic curve.
Inversion The output signal can be inverted by means of a slideswitch.
Operator interface ED 3 1 = Setting spindle for setting the final value PE 2 = Setting potentiometer for setting the initial value PA 4 = Slide switch for inverting the output signal 6 = Plug connector for further evaluation modules
Output signals for module ED 3
Range alteration and inversion as above. The current signal can be reduced below 4 mA (down to approx. If the installation has a fault alarm system, the response threshold should be set below 2. 5 mA.
72
Pressure transmitters
Ty p e s e r i e s F
Setting and testing Altering the operating range
To check functioning or change the settings from outside the system, a test set-up is required which meets the following requirements: 1. It must be possible to apply pressure to the pressure transmitter up to the desired final value. The pressure must be displayed by a sufficiently accurate pressure gauge. To display the output signal a voltmeter with a measuring range of 010 V (preferably 015 V) or an ammeter with a measuring range of 020 mA (preferably 025 or 030 mA) are required. To supply power to the transmitter, a 24 V AC or 24 V DC voltage source is needed. Setting operations must be carried out in the correct sequence 1. Set the slide switches (3) and (4) to the correct position (switch 3 is only present on ED 1) Switch (3): Output signal 010 V / 020 mA or 420 mA / 210 V (only on ED 1) Switch (4): Direction of action Switch up rising pressure = rising output signal Switch down (INV): rising pressure = falling output signal 3. Loosen the locking screw above the cover glass (approx. [. . . ] A differential pressure must not be active, i. e. Remove the plastic cover and check slide switches 3 + 4. The FHBN is supplied with the correct voltage and the output voltage is displayed. Loosen the spindle locking screw above the inspection window. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL F
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual HONEYWELL F will begin.