Manual abstract: user guide HONEYWELL HMC 82PRODUCT DATA
Detailed instructions for use are in the User's Guide.
[. . . ] PRE-CONFIGURED KITS
PRODUCT DATA
HMC 80/82
GENERAL
The wireless Universal Mixing valve Controller is used for heating/cooling zoning control. [. . . ] 6A Pump relay Mixing valve relay : 3A, cos 0, 7, without potential free relay contact : 3A, cos 0, 7, without potential free relay contact
FEATURES
· Direct control of mixing valve actuators for individual room temperature control · The HM80 is communicating with the Chronotherm CM67RFMV, (CM67z) to keep the room temperature constant, time program, holiday function · Manual or automatic control · Reduce installation time and costs · Pump control, after running time adjustable 0. . 99 min. · External Flow Sensor connectable NTC 20K, 25°C not linear (type T7414C1012) · Maintenance run for pump and mixing valve · Boiler feedback heat on demand with CM67RFMV, CM67z · Heating / Cooling operation · RF communication check
RF Communication
Frequency Receiver class
: 868, 3 MHz Receiver :2
RF communication range : 30m in a residential building environment RF communication Technology : short, high rate transmission to minimize air time and avoid collisions
ENVIRONMENTAL and STANDARDS
Storage temperature : -20 . . . 90 % : Socket: PA-GF 25-FR Cover : PC-FR VO certificated IP class Options Compatible products Approval : IP54 : Flow sensor NTC 20K connectable : CM67RFMV, CM67z : CE Operating temperature Dimensions (HxWxD) Humidity Material
EN0H0503GE51 R0905
HMC 80/82
KIT CONFIGURATION
Kit
HMC80 HMC82
Components
1x Universal Mixing Valve Controller HM80 1x Chronotherm CM67RFMV 4x Eurofix (strain relief) 1x Universal Mixing Valve Controller HM80 1x Chronotherm CM67RFMV 1x Flow sensor T7414C1012 4x Eurofix (strain relief)
Pre-Configured
Yes Yes
APPLICATION EXAMPLES
Mixing Valve Application for UFH without boiler feedback
Flow temperature sensor T7414C1012 (optional)
CM67RFMV with parameter settings
Pump after running time 0. . . 99 min Actuator running time 0. . . 240 s Min flow temperature setpoint 0. . . 50°C Max flow temperature setpoint 0. . . 99°C
CM67RFMV
HM80 Pump M Mixing Valve
The HM80 controls the mixing valve depending on the room temperature setpoint and communicates with the CM67RFMV. In addition the controller has a relay output for pump control and connection for the flow sensor. Without using the flow sensor the mixing valve position is adjusted in accordance with the room setpoint temperature and the actual room temperature. If the flow sensor is used the mixing valve position is adjusted in accordance with the calculated flow temperature setpoint and the measured flow temperature. [. . . ] Printed in Germany EN0H0503GE51 R0905 Manufacturing location certified to [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL HMC 82
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.