[. . . ] M7410G
LINEAR VALVE ACTUATOR WITH LON CAPABILITIES AND OPTIONAL PI-CONTROL
PRODUCT DATA
CONTENTS
APPLICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 FEATURES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 DEVICE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] Up to that point, the actuator will stay in the defined safety position [nciDefaultOutput].
Watchdog-timer in case of manual operation.
Is the actuator working in the manual operation mode (nviManActPos INVALID) the watchdog-timer is working in the background. This means, if the controller fails, the watchdog-timer expires and after switching manual operation [nviManActPos] to [INVALID] the actuator is running to the safety position according to the definition in [nciDefaultOutput].
0%
FACTORY SETTINGS
State of the Network and Configuration Parameters: nviActPos = 163. 835 (INVALID) nviManActPos = 163. 835 (INVALID) nviActPosFb = 163. 835 (INVALID) nvoDIswitch = [ 0. 0 -1 ] after initialization (3 sec. ) = [ 0. 0 0 ] (if there is no switch connected) nciDefaultOutput = 163. 835 (INVALID) nciDirRev = 1111111111111111 (for M7410G1008 / -16 / -24) nciDirRev = 100000000000000 (for M7410G1032 / -40 / -57) nciMaxRcvTime = 0. 0 sec nciDIconfig = ST_OFF nciRunTime = 6553. 5 (INVALID)
100 %
INTERRUPTION OF THE SYNCHRONIZATION
The interruption of the synchronization after Power-on / Reset (nciDefaultOutput = 0 or 100 %) is not possible. Later synchronizations can be interrupted every time.
11
EN0B-0235 GE51R0802
PRODUCT DATA
WHAT HAPPENS AT OFFLINE-ONLINE MODE CHANGES
If the actuator is taken offline by a network management tool the application program of the device stops, and the following actions will be done before the offline mode takes place:
Online-Offline change
· The motor stops, if it is running · The Status LED is taken off · The network variable nviActPosFb will be set to INVALID (163. 835), to show that the actuator is in a undefined situation · The state-value of the network variable nviDIswitch will be set to INVALID (255 = 0xFF = -1), to show that the actuator is in a undefined situation.
Offline-Online change
· Application restart. Same situation as Power-on or Reset.
EN0B-0235 GE51R0802
12
PRODUCT DATA
CONTROLLER OBJECT (ACTUATORS WITH PI-CONTROLLER ONLY)
The controller object supports the following network variables used for the communication and configuration
Controller Object
Controller Object, Object Type 5
nviActualTemp SNVT_temp_p nvoValvePosition SNVT_lev_percent
nv1
nv7
nv2
nviSetpoint SNVT_temp_p
nv3
nviSetPtOffset SNVT_temp_p
Network Variables
nv4
nviEnergyHoldOff SNVT_switch
nv5
nviOccupancy SNVT_occupancy
nv5
nviApplicMode SNVT_hvac_mode
Configuration Parameter nc 78 UCPT UCPT nciSetpoint nciPIGains[2] nciPIGains. pi_Xp nciPIGains. pi_Tn nciPIConfig (SNVT_temp_p) (SNVT_temp_p) (SNVT_time_sec) (Heat / Cool)
Optional Configuration Properties
Modify SCPT´s anytime (no reset of device)
Fig. 12 Controller Object
13
EN0B-0235 GE51R0802
PRODUCT DATA
DESCRIPTION OF USED SNVTS AND SCPTS
This table shows all used standard network variables and standard configuration parameters, their default values, a short description, the range and the send conditions and service of the outputs.
Standard Network Variable Type {Range} {factory settings} Network Variables nviActualTemp SNVT_temp_p {-163, 80 to 163, 80; 327, 67} {327, 67} = INVALID Definition nviActualTemp = 327, 67 [INVALID] after Power on or Reset. If nviActualTemp is INVALID than nvoValvePosition will be Invalid, too, cause no control loop is possible. not equal 327, 67 [INVALID] normal operation If nviActualTemp is not INVALID than normal operation is possible. Explanation nviActualTemp includes the actual temperature delivered by an separate LON temperature sensor. Received values below 163, 80°C are calculated like 163, 80°C and values above 163, 80°C will be calculated with 163, 80°C. The only exception is the value 327, 67 = [INVALID]. Is this value received, the output of the controller nvoValvePosition will be set to INVALID, too. Received values below 157, 80°C are calculated like 157, 80°C and values above 157, 80°C will be calculated with 157, 80°C. The only exception is the value 327, 67 = [INVALID]. Is this value received, the internally setpoint [nciSetpoint] will be taken as the actual one. If the SNVT nviSetPtOffset is not INVALID than the required temperature will be evaluated like this. Setpoint = nviSetpoint + nviSetPtOffset nviSetPtOffset works together with nviSetpoint or nciSetpoint and is part of the actual required temperature. Received values below 157, 80°C are calculated like 157, 80°C and values above 157, 80°C will be calculated with 157, 80°C. The only exception is the value 327, 67 = [INVALID]. Is this value received, it will be ignored. Can be used for binding of a physical digital input, e. g. nvoDIswitch from the internal actuator object. So the energy could be saved if an open window or a dewpoint sensor detects a situation to switch off the energy = close the valve totally. This means no more heating in HEATING applications or no more cooling in COOLING applications For binding of an occupancy sensor. [. . . ] Same situation as power-on / reset
Wiring Diagram
Diagram 2: Wiring Wiring Colors Power Supply + Digital Input Brown White Green LON (E-Bus) Black White Input Voltage: LON (E-Bus): Connection Cable:
24 Vac + 24 Vac DI (+)
LON LON Input Voltage for power supply 24 Vac ± 20 %, 50 / 60 Hz Connection of the LON Bus FTT-10A. The LON Bus is insensitive to polarity, eliminating wiring errors during installation. 1, 5 m
23
EN0B-0235 GE51R0802
PRODUCT DATA
PI-CONTROLLER OBJECT
The PI-Controller Descriptions of the Plug-In only apply to the actuator types which have the PI-Controller integrated.
MONITORING
Fig. 17 Monitoring Screen Priority Table
EN0B-0235 GE51R0802
24
PRODUCT DATA
Actual and Required Temperature
ACTUAL TEMPERATURE (nviActualTemp) Shows the actual temperature received from a LON temperature sensor. For INVALID state refer to the priority table above (priority 3). [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL M7410G
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.