If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual HONEYWELL NXS0003V35A5H1. We hope that this HONEYWELL NXS0003V35A5H1 user guide will be useful to you.
Lastmanuals help download the user guide HONEYWELL NXS0003V35A5H1.
Manual abstract: user guide HONEYWELL NXS0003V35A5H1DATASHEET
Detailed instructions for use are in the User's Guide.
[. . . ] switching load: 5 V / 10 mA Open collector output, 50 mA / 48 V RTRIP = 4. 7 k (PTC), electrically isolated
Altitude
100% load capacity (no derating) up to 1000 m -1% derating for each 100 m above 1000 m; max. 3000 m 0. . . 95% RH, non-condensing, non-corrosive, no dripping water 5. . . 150 Hz Displacement amplitude 1 mm (peak) at 5. . . 15. 8 Hz Max acceleration amplitude 1 G at 15. 8. . . 150 Hz UPS Drop Test (for applicable UPS weights) Storage and shipping: max 15 G, 11 ms (in package) Digital output Motor thermistor Input
Relative humidity
Vibration: EN50178/EN60068-2-6
Shock: EN50178, IEC 68-2-27
EN0B-0620GE51 R1107
2
NXS VARIABLE FREQUENCY DRIVES
Protection
Overvoltage protection Undervoltage protection Earth-fault protection 911 Vdc 333 Vdc In case of earth fault in motor or motor cable, only the frequency converter is protected YES Trip limit 4. 0*IH instantaneously
Unit overtemp. protection YES Motor overload protection YES
Motor stall protection
Motor underload prot. [. . . ] clearance for fan change
7
EN0B-0620GE51 R1107
NXS VARIABLE FREQUENCY DRIVES
REQUIRED COOLING AIR
Type
FR4: NXS0003--NXS0012 FR5: NXS0016--NXS0031 FR6: NXS0038--NXS0061 FR7: NXS0072--NXS0105 FR8: NXS0140--NXS0205 FR9: NXS0260--NXS0310
Cooling air required [m3/h)
70 190 425 425 650 1300
CABLING
B- B+ RL1 L2 L3
U/T1 V/T2 W/T3
nxlk58. fh8
Fig. NXS power connections FR4-FR6 in FR7-FR9 connectors B-, B+ and R- do not exist as standard. Use cables with heat resistance of at least +70°C. The cables and the fuses must be dimensioned according to the tables below. The fuses function also as cable overload protection. These instructions apply only to cases with one motor and one cable connection from the frequency converter to the motor. In any other case, ask the technical support for more information. Connection Mains cable Cable type Power cable intended for fixed installation and the specific mains voltage. (NKCABLES/MCMK or similar recommended) Power cable equipped with compact low-impedance shield and intended for the specific mains voltage. (NKCABLES /MCCMK, SAB/ÖZCUY-J or similar recommended). Possibility to copy parameters from unit to unit with standard keypad Keypad can be used as a backup for parameter settings
Application adapting Start-Up Wizard
Real text-based wizard which guides the user through setup of all applications easily Start-up wizard adapts to the application selected and guides the operator to make the settings which are relevant for just the application in question
Application adapting Quick Menu
Quick menu called "Basic Parameters- group" adapts to the application selected Includes always the relevant parameters for just the application in
question in to the group
"Keypad Remote" Operation
Single button operation to change the control to manual (keypad) and back Useful function when commissioning and testing HVAC applications. Consistency: all Honeywell VFDs behave in similar way
Press LEFT ARROW for 3 s to change control place
·
Compact and Robust design
EN0B-0620GE51 R1107
10
NXS VARIABLE FREQUENCY DRIVES
Features
Enclosure Class
Functions
· NXS available with both IP21 and IP54 · Smallest and lightest inverter available in the market (especially IP54) · Separated cooling channel (no electronics in air flow) · Power electronics fully enclosed in metal · Easily replaceable cooling fans · Protection against input voltage surges · Lower total harmonic distortion THD · Fulfills all EMC requirements in buildings
Benefits
· Consumes less space · Easy to install · Increased reliability · Easy maintenance · Compact · No additional costs
Modular design
Built in input AC choke and RFI filter
·
Uninterruptible operation and energy saving functions Features Functions Benefits
· Uninterruptible operation · Uninterruptible operation
Automatically adjusts switching frequency to adapt to unusual increase in ambient temperature Automatically lowers motor speed to adapt to Power ride through sudden voltage drop such as power loss Ensures tripless operation when an output switch (e. g. safety switch) is operated between Tripless output switching the motor and the VFD. Truly intelligent and highly reliable function to ensure better functionality than with any other VFD Auto restart function can be configured to Auto restart function make VFD restart automatically once fault is addressed Energy Saving Function Flux Optimization automatically minimizes "Flux Optimization" energy consumption. Overtemperature ride through
· Uninterruptible operation
· Uninterruptible operation · Even 5% increase in energy savings.
11
EN0B-0620GE51 R1107
NXS VARIABLE FREQUENCY DRIVES
·
VFD and motor control features Features Functions
Ability to get an already spinning fan under speed control Boosts initial voltage to start high inertia fans Performs measurements to find out motor internal variables such as stator resistance. Honeywell NXS has higher switching frequency than the most of the competition as standard (= no derating required) Overriding the critical frequencies to avoid resonance Fan stops operating when not needed
Benefits
· Important in clean room production to ensure the standard conditions · Avoids tripping and enables smooth starts also to high inertia loads · Increases reliability · Less audible noise from the motor
·
Best in performance Flying start Automatic torque boost function Motor auto identification High Switching Frequency Prohibit frequency Temperature-controlled fans
Elimination of resonance
· Less audible noise from VFD itself · Increase of energy savings
·
HVAC control features Features Functions
· Normal and Inverse Regulation · Delta P regulation with 2 standard pressure transmitters · Volume flow control · Less wiring since sensor normally close to inverter Shutting down the motor, when no demand Keeps fan/pump running in case of fire Controls total pumping system with several parallel pumps by equally sharing the load
Benefits
· Cost savings · Faster response in process closed loop · · · · Saves energy Legal requirement Longer lifetime of the system Lower investment cost for pumping system
Inbuilt PID controllers
Sleep Mode Fire override mode PFC (Pump and Fan Cascade) -Controller
·
Special application software Features Functions
· The best available fully controlled pump cascade VFD system in the market · System with a VFD for each pump · Only 2 wires needed for the connection between inverters no additional hardware · Full control over the total pumping system · Equal usage of each pump · Fully redundant system
Benefits
· Longer lifetime of the system · Increased reliability · Increased energy savings with optimized usage of pumps · Fully independent pump control system can be created for pumping stations
Multimaster PFC
EN0B-0620GE51 R1107
12
NXS VARIABLE FREQUENCY DRIVES
·
"ALL-IN-ONE" MULTIPURPOSE software
Flexible "ALL-IN-ONE" multipurpose software offers predefined applications as described below for different kind of needs. This flexible package really makes it possible to answer any needs from the application with Honeywell NXS.
Basic application
The most typical choice for HVAC - covers most of the applications Everything needed for basic speed control Includes only one small group of parameters with default values to create simple selection Very simple commissioning The control signals of this application are fixed with default functions (not configurable) The Basic Application is set as the default when the drive leaves the factory.
Standard application
The 2nd most typical choice for HVAC - extended version of the basic application For more demanding cases where more functionality is required The Standard Application has the same I/O-configuration and control logic as the Basic application (i. e. All inputs and all outputs are freely configurable More functions, e. g. dynamic braking, DC braking, Prohibit Frequency for resonance elimination
Motor
Pump
or
Load
Fan
Speed Signal V signal to AI1 mA signal to AI2
Sensor
Variable Frequency Drive
Control System
Fig. [. . . ] More programmable digital inputs Best option with difficult applications all Honeywell NXS capabilities accessible through this application
PFC (Pump and Fan Cascade) Control Application
Used for controlling a group of pumps or fans. The internal PID regulator controls the speed of one motor and provides start/stop commands for 1 to 4 auxiliary motors (connected directly to mains) Provides redundancy and high efficiency. Four auxiliary pumps or fans can be connected Autochange (if activated) allows to set the starting and stopping order of the drives, controlled by the pump and fan automatics (including the main drive)
EXTERNAL CONTACTORS
Fig. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL NXS0003V35A5H1
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.