If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual HONEYWELL Q7055B1047. We hope that this HONEYWELL Q7055B1047 user guide will be useful to you.
Lastmanuals help download the user guide HONEYWELL Q7055B1047.
Detailed instructions for use are in the User's Guide.
[. . . ] Advanced features like graphics, trends and reports give enhanced flexibility and total control when accessing the Building Management System from a remote location. Customers can now gain the advantages of high-performance network and services, including traffic management, to more locations throughout the network.
TCP/IP
OVN
OVN
SINGLE C-BUS (ONLY FOR XL5000 CONTROLLERS FAMILY)
SINGLE C-BUS (ONLY FOR XL5000 CONTROLLERS FAMILY)
M25198
Fig. The Q7055B1047 OVN Server is used in systems for signaling in energy management systems (UL 916). In addition, the following standards apply: requirements of Canadian province and local building codes; CEC 22. 1 Canadian Code.
95-7711
Q7055B1047 OPEN VIEW NET SERVER (OVN)
SPECIFICATIONS
Models: Q7055B1047 Open View Net Server (OVN). [. . . ] · Building Network Adapter driver software CD.
Tx
Test LAN
10 100 ACT
M25117
Fig. Single server operating position.
95-7711
2
Q7055B1047 OPEN VIEW NET SERVER (OVN)
Wall Mounting
It is also possible to mount the OVN server to a wall. The following sequence describes how the server should be prepared prior to mounting it on a wall (see Fig. 3).
Communications Panel Mounting
It is also possible to mount the OVN Server in the 14006090-555151 series EBI Communications Panel (Refer to Fig. 4).
Place the OVN server with the topside down on the desk.
Rx Tx LAN 10
100 100 100
100 100
ACT ACT ACT
ACT ACT
Remove the four feet from the bottom of the OVN by pushing horizontally away from the housing with a flat screwdriver.
Rx Tx LAN LAN
LAN LAN
10 10
10 10
Push the four inserts (included) fully and horizontally into the housing.
Rx Tx
Tx Tx
Adjust the four retaining clips (included) on top of the inserts. Fasten the retaining clips with the included four screws.
Rx
Use the housing with the clips to mark the positions of the four mounting holes on the wall surface. (4 mm) holes for the mounting screws (not included) and secure the OVN server.
Fig. OVN wall mount.
Rx
M25121
3
95-7711
Q7055B1047 OPEN VIEW NET SERVER (OVN)
WIRE PER NEC FOR FIRE ALARM
2
3
H
TRIPP-LITE
NG
6
4
6
G F D
OVN
G F D
1 4 5
2
OVN
NON-POWER LIMITED AREA 1 2 3 4 5 6
POWER LIMITED AREA
TYPICAL MOUNTING LOCATIONS FOR 14005680-089582/592 FIBER OPTIC INTERFACE. ALL WIRING MUST BE IN ACCORDANCE WITH NFPA 70, NATIONAL ELECTRICAL CODE AND ALL APPLICABLE LOCAL CODES. G = GROUNDING CONDUCTOR GROUND CONNECTION. GROUND CONNECTION FOR 14507678 SERIES PNET PROTECTOR AND OTHER LOW VOLTAGE EQUIPMENT. DRILLED MOUNTING HOLES FOR 14507719-001 8 PORT ETHERNET HUB (IF USED).
NOTE: SYSTEM WIRING IS CLASSIFIED AS EITHER POWER LIMITED OR NON-POWER LIMITED PER NEC ARTICLE 760. ALL POWER LIMITED WIRING MUST BE SEPARATED FROM ALL NON-POWER LIMITED WIRING BY A MINIMUM DISTANCE OF 1/4 IN. Typical mounting of Q7055B1047 OVN Assembly on 14006090-555151 series Communication Panel.
95-7711
4
Q7055B1047 OPEN VIEW NET SERVER (OVN)
CONNECTIONS
This section describes how to connect power and the field bus to the OVN server. A supply pack with installation material containing the required connectors for power and the field bus are shipped with the server.
CABLES AND CONNECTORS
DB9F Null-Modem Connector
See Fig. 5 for serial connectors.
Power Connection
The OVN server requires an external power supply with the following specifications: 24 Vac, 50 Hz to 60 Hz, or 24 Vdc. Typical power supplies include: DC Power Supply: 50017367-001, Jameco Model No. DDU240050, 120 Vac, 60 Hz input, 24 Vdc, 0. 500 A output, wall mounted power cube, Class 2. FW7224-D5F, 120/240 Vac, 50/60 Hz input, 24 Vdc, 3. 0 A output. AC Power Supply: 120 Vac/50 to 60 Hz input, 24 Vac output, 14507287 series, 14507350-002, listed. Power consumption of the OVN server is 8 VA. For the power connection, the 3-pole Phoenix connector is required (included). [. . . ] 6--AC/DC IN 24 V Power connector for 24 Vac (50 Hz to 60Hz) or 24 Vdc power supplies and chassis ground. Power consumption is 8 VA (connected via 10/100BaseT, cable). Excel 5000 Open View Net Server rear panel. Enterprise Buildings Integrator (EBI)TM and Excel 5000TM are trademarks of Honeywell International, Inc. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL Q7055B1047
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.