[. . . ] INSTALLATION AND OPERATING INSTRUCTIONS T7460H SETPOINT SELECTOR
DESCRIPTION
The T7460H setpoint selector is a temperature selector equipped with operating mode switch, room temperature sensor, and error indicator LED. [. . . ] Connect the cable coming from the controller.
Figure 4: Wiring diagram
Wiring of the terminals:
1 2 3 Setpoint + 10 V Gnd 4 5 6 not used Room sensor LED
4. Return cover to housing by placing top edge against backplate and snap lower part of cover onto housing (2).
Figure 5: Replacing of housing cover
EN1H-0154GE51 R0508
T7460H Installation and Operating Instructions
OPERATION AND FUNCTIONS
Figure 6: Operating devices and indicators
1 2 3 4
Operating mode switch LED (error indicator) Temperature selector with scale Temperature sensor (to the side)
T7460H in operation with systems MCR 35, 36, 40, 200, DHC 23 and EXCEL 500
Operating mode switch The operating mode switch allows for the selection of three different functions: Position Operating mode Auto Automatic Daytime Switch-off Function Heating is controlled by timer. In the event of danger of frost, the heating pump and the burner are automatically switched on.
Note The operating mode switch of the T7460H does not in any way influence the domestic hot water program. Temperature selector The desired value can be changed only if the operating mode switch is set to positions Auto or respectively. Range: 7. . . +7 °C Mid-point position: 0 °C (in relation to controller settings)
LED Function in operation with MCR 200: The LED is on if the controller has detected an error. The LED may also be used with other systems. The input voltage is 5 24 V AC or DC.
EN1H-0154GE51 R0508
T7460H Installation and Operating Instructions
T7460H in operation with Excel 500 System
If the T7460H is operated with the Excel 500 System, the temperature range and options of the operating mode switch can be chosen to suit your needs. In such an installation, the feedback control system of the Excel System provides information on the current configuration of the switch.
TECHNICAL DATA
Sensor device: Resistance: Temperature range: Dimensions (H×W×D): Installation: NTC thermistor 20 kOhm at 25 °C 6. . . 40 °C 103 × 98 × 28 mm Installation on wall or on standard 60 mm distribution box
Max. [. . . ] Printed in Germany
7157408
EN1H-0154GE51 R0508 [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL T7460H
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.