[. . . ] · TMVXX:Valve body and solder base with external pressure equalisation; for optimal evaporation effectiveness in all applications. Obligatory for multiple injection by liquid distributors. · Combi adsorber charge The same valve can be used for different refrigerants (see table on page 2) Controller charge is high sensitive and responsive thus lowest possible level of superheat can be achieved Charge is not sensitive to effects of temperature on the capillary tube and valve head Damping characteristic results in stable control behaviour · Suitable for systems with hot gas defrosting · Adjustable superheat setting · Solder connections · Solder base available in two-way construction and in angle construction · Extreme durable due to stainless steel head and stainless steel diaphragm welded using protective gas · Interchangeable orifice cartridges · Refrigerants: R134a, R401A, R12 R22, R407C, R407A, R422D R404A, R507A, R402A, R407B, R502 R124, R227, R410A Further refrigerants on request.
TMVXX-W
TMVXX-D
Application
Thermostatic expansion valves series TMVX are used in general refrigeration and for original equipment. [. . . ] · Combi adsorber charge The same valve can be used for different refrigerants (see table on page 2) Controller charge is high sensitive and responsive thus lowest possible level of superheat can be achieved Charge is not sensitive to effects of temperature on the capillary tube and valve head Damping characteristic results in stable control behaviour · Suitable for systems with hot gas defrosting · Adjustable superheat setting · Solder connections · Solder base available in two-way construction and in angle construction · Extreme durable due to stainless steel head and stainless steel diaphragm welded using protective gas · Interchangeable orifice cartridges · Refrigerants: R134a, R401A, R12 R22, R407C, R407A, R422D R404A, R507A, R402A, R407B, R502 R124, R227, R410A Further refrigerants on request.
TMVXX-W
TMVXX-D
Application
Thermostatic expansion valves series TMVX are used in general refrigeration and for original equipment. Plants with one or more refrigerant circuits such as refrigerated cabinets even with cramped mounting conditions, ice and cream machines, milk cooling systems, cold stores, air conditioning systems and heat pumps.
Materials
Body Thermal head Connection tubes brass stainless steel copper
Specification
Nominal capacity range 0. 52 to 22. 4 kW R22 (small orifice graduation for optimal control behaviour, interchangeable orifice cartridges) Evaporating temp. range see table on page 2 Maximum pressure PS see table on page 2 Maximum test pressure PF see table on page 2 Max. bulb temperature 140 °C Static superheat approx. 3 K Length of capillary tube 1. 5 m Bulb diameter 12 mm
EN0H-1902GE23 R0709
Copyright © 2009 Honeywell GmbH · Subject to change without notice
SERIES TMVX
Thermal Charges and Temperature Ranges
1. Adsorber charge Refrigerant R134a, R401A, R12 R22, R407C, R407A, R422D Evaporation temperature range +15 °C to -30 °C +15 °C to -45 °C PS
(bar(a))
2. Adsorber charge with pressure limiting performance MOP PF
(bar(a))
Refrigerant
34 36 36 36 29 29 36 40
37. 4 39. 6 39. 6 39. 6 31. 9 31. 9 39. 6 44
Evaporation temperature range
MOP
PS
(bar(a))
PF
(bar(a))
R134a, +5 °C to -30 °C R401A, -10 °C to -30 °C R12 R22, +5 °C to -45 °C R407C, -10 °C to -45 °C R407A, R422D -27 °C to -45 °C R404A, -10 °C to -50 °C R507A, -20 °C to -50 °C R402A, R407B, -27 °C to -50 °C R502
MOP A +15 °C
34
37. 4 31. 9 39. 6 31. 9 31. 9 39. 6 37. 4 37. 4
MOP A ±0 °C 29 MOP A +15 °C MOP A -18 °C MOP A -10 °C MOP A -18 °C 36 29 34 34
R404A, R507A, ±0 °C to -50 °C R402A, R407B, +15 °C to -30 °C R502 R124 R227 R407C R410A +20 °C to -30 °C +20 °C to -30 °C +15 °C to -30 °C +15 °C to -20 °C
MOP A ±0 °C 29 MOP A ±0 °C 36
Further refrigerants on request. · Do not bend or squeeze the bulb when tightening the bulb clamp · The screws fixing the valve body to the solder base must be tightened in diagonal sequence (torque 12 Nm). · Constructive modifications at the valve are not allowed. · Never quench the solder base with water after soldering, this may cause cracks and distort the sealing surfaces.
Superheat Adjustment
In general the Honeywell valves should be installed with the factory setting for the used refrigerant unaltered. At combi adsorber valves the label on the capillary tube indicates how to adjust the adjusting spindle (with arrow for direction), depending on the refrigerant used. This correction of the adjustment is essential to ensure that the control performance of the valve is correct. The refrigerant used must be marked on the label. This superheat adjustment is calibrated for lowest superheating and optimum evaporator utilisation. [. . . ] This correction of the adjustment is essential to ensure that the control performance of the valve is correct. The refrigerant used must be marked on the label. This superheat adjustment is calibrated for lowest superheating and optimum evaporator utilisation. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL TMVX Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service. Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual HONEYWELL TMVX will begin.