[. . . ] The end position is limited both electrically and mechanically. The electrical limitation can be adjusted by pressing and turning (with a screwdriver) the adjustment screws situated on the white and black cams. The end position is factory-set to -2° and +92°. As a rule, it is not necessary to alter this value.
declutch button
Fig. [. . . ] Feedback terminals NOTE: These change-over switches must be supplied with power from an independent (external) power source (maximum permissible load: 230 Vac, 16 A).
Adjusting the V5422L for Floating Control
A
2
1
B
7
·
ON
6 5 4 3 2 1
Fig. Default microswitch settings of the V5422L To adjust the V5422L for floating control, microswitches 5 and 6 (located on the main PCB; see Fig. 3) must both be set to position "B" (see Fig. Explosion view
Input Terminals
An external floating controller controls the actuator of the V5422L. This controller transmits the phase to input 31 (for closing the valve) or to input 32 (for opening the valve). 12.
NOTE: In the case of the V5422L, microswitches 1, 2, 3, and 4 have no function/effect.
Adjusting the Direction of Rotation of the V5422L
· · To adjust the direction of rotation so that the V5422L closes in the clockwise (right) direction, microswitch 7 must be set to position "A". To set the direction of rotation so that the V5422L closes in the counterclockwise (left) direction, microswitch 7 must be set to position "B".
Feedback Terminals
The V5422L is equipped with two change-over switches (see Fig. 7) located (together with a feedback potentiometer and the angle indicator) under the cover (see Fig. To access the main PCB, remove the cover.
Table 3. Adjusting the input signal range (V5422E) Input signal 0. . . 10 V 2. . . 10 V 4. . . 20 mA output signal 0. . . 10 V 2. . . 10 V 4. . . 20 mA 0. . . 20 mA 0. . . 20 mA 4. . . 20 mA 2. . . 10 V 0. . . 10 V microswitch positions 1 B B A A B B A A 2 B B A A B B A A 3 B B A A A A B B 4 B A A B B A A B 5 A A A A A A A A 6 A A A A A A A A 7* A/B A/B A/B A/B A/B A/B A/B A/B
3
1 2 18 17 16 17 18 4 9
Tr1
Tr2
15 12 14 11 10
0. . . 20 mA 0. . . 10 V 2. . . 10 V 4. . . 20 mA 0. . . 20 mA
3
feedback jacks
27 26 41 40 1 2
Tr1
microswitches
A
*Depends upon desired direction of rotation.
P1 P2 offset adjustment
R2
Dead Band
B
7 6 5 4 3 2 1
Terminals for Input/Output Signals
Ful
R1
L L N PE N PE
70 71 72 73 31 32 70 71 72 73 31 32 Cl Op Tq red/green analog /yellow LEDs input/output
An external modulating controller controls the actuator of the V5422E by means of an analog signal provided at terminal 70/71. An analog output signal for position indication is provided at terminal 71/72.
power supply
Adjusting the Input/Output Signal Offset
The offset of modulating actuators is adjusted at the factory and should not be changed. If you wish to change the offset (using offset potentiometer P2; see Fig. 7), note that an excessively small offset will result in oscillation of the actuator.
Fig. Main PCB of the V5422E
Adjusting the V5422E for Modulating Control
A
2
1
Reversing Direction of Rotation of the V5422E
In the case of the V5422E, it is possible to reverse the direction of rotation of the valve by adjusting the feedback signals. The feedback signals are adjusted by resetting the microswitches and replugging the feedback potentiometer's cables. Reset the microswitches as shown in Table 3, but with microswitch 7 in position B. Replug the feedback potentiometer's cables as shown in Fig. 9.
B
7
·
ON
6 5 4 3 2 1
Fig. Default microswitch settings of the V5422E To adjust the V5422E for modulating control, microswitches 5 and 6 (located on the main PCB; see Fig. 7) must both be set to position "A" (see Fig. [. . . ] Installing the valve
Step 3
70 71 72
Y = 0. . . 10 V (2. . . 10 V, 0/4. . . 20 mA) POS = 0. . . 10 V (2. . . 10 V, 0/4. . . 20 mA)
Bolting
Table 4 lists the number of bolts and nuts required for mounting. The number is dependent upon the size (DN). Bolts and nuts required for installation DN 250 300 350 400 PN10 bolts (M x length) M20x150 M20x160 M20x160 M24x200 number 12 12 16 16
Fig. Modulating Control (V5422E)
length
Fig. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL V5422L
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.