[. . . ] SMALL LINEAR VALVES PN16 FOR MODULATING AND ON/OFF-CONTROL
SPECIFICATION DATA
V5832A/5833A, C
FEATURES
· · · · · ·
V5832A V5833A
Small size allows installation where space is limited Long stroke results in a high quality characteristic Soft seat provides low leakage rate and high rangeability Reduced kVS values in the bypass to facilitate hydronic balancing Range of fittings available for different connections (soldered, threaded) Adjustment cap for manual operation Flat surfaces on body to fit installation tools Flat sealing connections in standard sizes Valve inserts changeable without draining by using insert replacement tool WV 108 40 mm distance between ports A/AB and the bypass (V5833C, only)
· · · ·
SPECIFICATIONS
V5833C
Models
Two-way V5832A Three-way V5833A Three-way with bypass V5833C Two-way stem up to open, port A to B; Three-way stem up to close, port A to AB PN16 see tables on page 2 and 3 0. 02% of kVS Brass DN15 (1/2"), DN20 (3/4") Stainless steel Brass Water, with max. 50% glycol 2. . . 120 °C
Operation
GENERAL
These small linear valves are used in combination with small electric linear valve actuators and thermoelectric actuators for the control of hot and/or chilled water for fan coil units and small reheaters/recoolers in electric/electronic temperature control systems.
Nominal pressure rating Capacity index (kVS) Leakage rate Valve body Material Size Trim Stem Plug Suitable medium Controlled water temperature
® U. S. [. . . ] This allows the stem to be set up for filling or initial heating/cooling during the building construction phase without the use of a controller or actuator. The small electric valve actuators as well as the thermoelectric actuators provide automatic control over the opening and closing movement of the valve stem.
Three-Way Valves
These valves are preferably used as mixing valves, this means: Port AB: Total flow outlet Port A: Controlled flow inlet Port B: Bypass inlet
inlet + -
inlet + -
AB
A B
AB B
A
TYPICAL OPERATION
All types of valves should be mounted in the return flow. If the p-values exceed 60 kPa, attention should be paid to the development of noise.
Fig. Three-way valve operation
Two-Way Valves
Direction of flow always from port A to port B Port B: Outlet
Three-Way Valves with Bypass
These valves simplify the installation, which is depending on the layout of the pipework, as the bypass pipe is part of the valve. The information for the normal three-way valves is also valid for this type.
+ -
inlet + outlet outlet
inlet
inlet + -
inlet + -
AB B
A
AB B
A
Fig. Three-way valve with bypass
3
EN0B-0308GE51 R1002
V5832A/V5833A, C SMALL LINEAR VALVES PN16
MOUNTING
When installing the valve care must be taken that the flow direction is correct (see section "Typical Operation"). The valve must not be mounted with the stem pointing downward. The adjustment cap must be removed from the valve only when the actuator is fitted. The valve should be installed as stress-free as possible with a tightening torque of 25 to 30 Nm. The valve is supplied complete with mounting instructions. The water quality must meet VDI 2035 requirements.
ACCESSORIES
Valves V5832A need two connection sets, valves V5833A three connection sets, and valves V5833C four connection sets. Connection Soldering Pipe Size 12 mm 15 mm R3/8" R1/2" DN 15 20 15 20 Order Number AC-15FS AC-20FS AC-15FT AC-20FT Connection Set Description Consisting of 1 union nut, 1 solder bush, and 1 gasket Consisting of 1 union nut, 1 tailpiece, and 1 gasket
External Thread
*Cannot be purchased from Honeywell
Dimensions of Connection Sets a G1/2" G3/4" c 12 mm 15 mm d
Order Number
AC-15FS AC-20FS
G1/2" G3/4"
R3/8" R1/2"
AC-15FT AC-20FT
EN0B-0308GE51 R1002
4
V5832A/V5833A, C SMALL LINEAR VALVES PN16
DIMENSIONS
Two-way valve
6. [. . . ] Order Number V5832A1004 V5832A1012 V5832A1020 V5832A1038 V5832A1046 V5832A1053 V5832A1061 V5832A1079 V5832A4008* V5832A4016*
*For on/off control
DN 15 15 15 15 15 15 20 20 15 20 DN 15 15 15 15 15 20 20 20 20 15 20
kVS 0. 16 0. 25 0. 40 0. 63 1. 00 1. 60 2. 50 4. 00 1. 60 4. 00 kVS 0. 25 0. 40 0. 63 1. 00 1. 60 2. 50 2. 50 4. 00 4. 00 1. 60 2. 50
Order Number Valve Insert 0902812 0902811 0902810 0902809 0902808 0902807 0902814 0902815 0902813 0902816 Order Number Valve Insert 0902821 0902822 0902823 0902824 0902825 0902826 0902818 0902827 0902819 0902817 0902820
Order Number V5833A1003 / V5833C1066 V5833A1011 / V5833C1009 V5833A1029 / V5833C1017 V5833A1037 / V5833C1025 V5833A1045 / V5833C1033 V5833A1052 / V5833C1041 V5833A3009 / V5833C1140 V5833A1060 / V5833C1058 V5833A3017 / V5833C1152 V5833A4007* / V5833C4003* V5833A4015* / V5833C4011*
*For on/off control
The following valve inserts are interchangeable · Two-way valves: kVS 0. 16, 0. 25, 0. 40, and 0. 63 kVS 1. 0 and 1. 6 kVS 2. 5 and 4. 0 kVS 0. 25, 0. 40, 0. 63, and 1. 0 kVS 2. 5 and 4. 0
·
Three-way valves:
Control Products Honeywell AG Hardhofweg D-74821 Mosbach Phone: (49) 6261 810 Fax: (49) 6261 81309 http://europe. hbc. honeywell. com Subject to change without notice. Printed in Germany EN0B-0308GE51 R1002 Manufacturing location certified to [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL V5833C
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.