HONEYWELL EXCEL 5000 OPEN SYSTEM
INSTALLATION INSTRUCTIONS
GENERAL INFORMATION
Depending on your application's hardware requirements, you can choose between the following different Excel 12 models: Table 1. Overview of Excel 12 models
AI1 (NTC20k + V) AI5 (NTC20k + V) AI7 (NTC20k + V) wall module LED output AO1 (0. . . 10 Vdc) AO2 (0. . . 10 Vdc)
AI3 (fan speed / bypass)
AI2 (NTC20k)
W7704A1004*1 W7704B1002* W7704C1000* W7704D1008 W7704D1016 W7704F1003* *
1 12 1 1
X X X X X X X X
XXXXXXXXXXXXXX XXXXXXXXXXXXXXXX XXXX XXXXXX XXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX XXXXXXXXX
X X X X X
XX XX XX XX XX
X X X X X
XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX XXXX
* These hardware versions have been discontinued. 2 * The hardware variant W7704F1003 is cost-optimized for light control and does not support hardwired wall modules.
BEFORE INSTALLATION
Standards Weight
IMPORTANT It is recommended that the Excel 12 be kept at room temperature for at least 24 hours before applying power; this is to allow the evaporation of any condensation resulting from low shipping / storage temperatures.
CE-certified according to EN60730-1.
Short housing: Long housing:
400 g 860 g
CAUTION
To avoid electrical shock or equipment damage, you must turn off the power supply before attaching / removing connections to/from any terminals.
Mounting
The Excel 12 is available with either short (W x L x H = 126 x 76 x 110 mm) or long (W x L x H = 180 x 76 x 110 mm) housings (see Fig. The mounting procedures are similar for both sizes. [. . . ] Specifically: · If the wall module's LED is OFF, the Excel 12 is in the "unoccupied" mode. · If the wall module's LED is ON, the Excel 12 is in the "occupied" mode. · If the wall module's LED flashes once per second, the Excel 12 is in the "standby" mode. · If the wall module's LED flashes four times per second, the Excel 12 is responding to a network management "wink" command. When possible, use Honeywell AK3781, AK3782, AK3791, or AK3792 cable (US part nos. ). See Excel 50/5000 LonWorks Mechanisms, EN0B-0270GE51, for details, including max. The unit is connected to the LONWORKS network as shown in Fig. 9 via terminal pins 3 and 4 (black screw-type T terminal plug) underneath the terminal protection cover (if present) located on the low-voltage side. Terminal 24 and 25 are used to connect further devices to the LONWORKS network.
Connection of CO2-Sensor
A CO2-sensor (e. g. C7110D1009) may be connected to analog inputs 1, 5, or 7 for air-quality control.
W7704
TEMP. SENSOR BYPASS / FAN
COMMON
9
10
11 12 13 14 15 16
24V ~ 22 24V 0 23 LON 1 24 LON 2 25
LED OUT
24 VAC
CO2 IN
Excel 12
24V ~
24V 0 2
LON 1 3
LON 2 4
1
2
3
4 TEMP. SETPOINT
6
7
1
BYPASS / FAN
24V ~ 22
24V 0 23
LON 1 24
LON 2 25
COMMON
CO2 OUT
24 VAC
LED IN
Excel 12
24V ~ 1
24V 0 2
LON 1 3
LON 2 4
C7110D
Fig. Connection to LonWorks (fixed terminals) Depending upon the chosen network configuration, one or two terminations (see section "LONWORKS Termination" on page 7) may be required.
LonWorks Communications
The Excel 12 is equipped with a free-topology transceiver (FTT10A) for communicating on LONWORKS® networks. The LONWORKS network is insensitive to polarity, eliminating the possibility of installation errors due to miswiring. Different network configurations (daisy-chain, loop, and star configurations, or any combination thereof) are possible (see also Excel 50/500 LONWORKS Mechanisms Interface Description, EN0B-0270GE51). All Excel 12 controllers feature a LONWORKS service LED and service button (see section "Troubleshooting" on page 6).
General Information
Inputs/Outputs
Use a min. of 14 AWG (2. 5 mm2) for all input/output connections. length of all input/output cables is 1300 ft (400 m). Two wires with a total thickness of 14 AWG can be twisted together and connected using a wire nut (include a pigtail with this wire group and attach the pigtail to the individual terminal block). Deviations from this rule can result in improper electrical contact. Local wiring codes may take precedence over this recommendation. Wire to the terminal blocks as follows:
Wiring the Inputs/Outputs
5
EN1B-0201GE51 R0209E
EXCEL 12 MODULES
1. Insert it at the required terminal location, and tighten the screw to complete the termination. [. . . ] LED flashes at power-up, goes OFF, then comes ON solid. Afterwards, the service LED turns ON and remains ON, indicating completion of the blanking process. Afterwards, the service LED turns ON and remains ON. OFF duration is 1. . . 15 sec, depending on the application size and the system clock. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL W7704
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.