[. . . ] W7752D, E, F, G, J AND W7754K, L, M, N, P FAN COIL UNIT CONTROLLERS
SYSTEM ENGINEERING CONTENTS
Revision overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Description of Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Products Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] ON time fan run-up time
1 1 1 1
configuration options continuous during occupied mode; automatic, based on control algorithm 0 to 1200 seconds 0 to 1200 seconds (with fan interlock only) 0 to 600 seconds
fefault automatic 0 0 0 0
fan min. OFF time
fan overrun time (with fan interlock only) 0 to 600 seconds Notes: 1. Fan run time options apply to all fan speeds.
31
EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Switching Levels
See Configurations section above for more information about parameters. FCU Controller switching levels configuration options function cooling stage 1 switching level heating stage 1 switching level cooling stage 2 switching level heating stage 2 switching level cooling stage 3 switching level heating stage 3 switching level cooling hysteresis configuration options 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100% 0 to 100%, default 5% 5% 50% 50% 75% 75% 10%
heating hysteresis 0 to 100% 10% Notes: 1. Stage switching levels and hysteresis are used for fan control as well as multi-stage heating/cooling outputs control.
Zone Options
The Zone configuration options are listed in the following table. See Control Provided and Configurations sections above for more information on parameters. FCU Controller zone configuration options function cooling occupied setpoint heating occupied setpoint cooling standby setpoint heating standby setpoint cooling unoccupied setpoint configuration options 50 to 95°F (10 to 35°C) 50 to 95°F (10 to 35°C) 50 to 95°F (10 to 35°C) 50 to 95°F (10 to 35°C) 50 to 95°F (10 to 35°C) default 73. 4°F (23°C) 69. 8°F (21°C) 77°F (25°C) 66. 2°F (19°C) 82. 4°F (28°C)
heating unoccupied setpoint 50 to 95°F (10 to 35°C) 60. 8°F (16°C) Notes: 1. Ensure that unoccupied heating<occupied heating<occupied cooling<unoccupied cooling and standby heating<standby cooling.
Miscellaneous
The options available in the Miscellaneous tab in E-Vision are listed in the following table. See Configurations section above for more information about parameters. FCU Controller miscellaneous configuration options Function Bypass time Override priority Demand limit control bump Cool rec ramp (cooling optimum start gradient) Heat rec ramp (heating optimum start gradient) Configuration options 0 to 1080 minutes last wins - the last command from either the wall module or from the network has priority. network wins - a network command always has priority until canceled. 0 to 18 DDF (0 to 10 K) -36 DDF/hour to 0 (-20 K/hour to 0) 0 to 36 DDF/hour (0 to 20 K/hour) 3. 6 DDF (2 K) 0 0 Default 180 minutes last wins
EN0B-0377GE51 R0703
32
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
PID
The options for configuring PID parameters with defaults are shown in the following table. See Control Provided section above for more information about parameters. FCU Controller PID configuration options function cooling proportional gain
1
configuration options P control: 2. 25 to 180 DDF (1. 25 to 100 K) (0 = disable) PI control: 3. 6 to 180 DDF (2 to 100 K) (0 = disable)
1
default 36 DDF (20 K) 36 DDF (20 K) 250 s 250 s 0 0 1. 8 DDF (1 K)
heating proportional gain cooling reset time heating reset time cooling derivative time heating derivative time
P control: 2. 25 to 180 DDF (1. 25 to 100 K) (0 = disable) PI control: 3. 6 to 180 DDF (2 to 100 K) (0 = disable) 10 to 3200 seconds (0 = disable) 10 to 3200 seconds (0 = disable) 1 to 3200 seconds (0 = disable) 1 to 3200 seconds (0 = disable) 0. 9 to 18 DDF (0. 5 to 10 K) (0 = disable)
cooling boost temperature
heating boost temperature 0. 9 to 18 DDF (0. 5 to 10 K) (0 = disable) 1. 8 DDF (1 K) Notes: 1. Prior to version 1. 0. 3, the minimum proportional gain was 7. 2 DDF (4 K) for all control algorithms.
Commissioning
Commissioning is the process of writing the LONWORKS addresses, the binding information and the configuration to the Excel 10 Controller. E-Vision is the tool used to perform these activities, as described in Appendix B. Job Commissioning The CARE database that is generated for the Excel 10 FCU Controllers and associated Zone Managers contains information concerning interrelationships and network identifications. For this reason, it is mandatory to commission (assign ID and download) all Excel 10 FCU Controllers and the Zone Managers from a single database.
®
containing its Neuron ID number. This ID number is on a removable sticker on the side of the W7752 housing or on the adhesive sticker on the top of the W7754 housing and can be typed in manually. E-Vision is used to perform both methods (see E-Vision User Guide). Configuring the Zone Manager The Q7750A Excel 10 Zone Manager sends a one-time LONWORKS message containing its 48-bit Neuron ID after any power-up WARMSTART or when the Excel 10 Zone Manager is reset by pressing the reset button. IMPORTANT Pressing the reset button on the Excel 10 Zone Manager causes all application files in the Q7750A, including the C-Bus setup, to be lost. [. . . ] Bug Fix Number: Network variables are unchanged. A change to the algorithm, network interface, or physical input/output subsystem was made that does not affect compatibility with other nodes or the equipment controlled by the node. Node type number.
X
X
X
79
EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C5. Unused Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
engineering units: English (metric) or states plus range UBYTE UBYTE 7 bits 4 bits UBYTE UBYTE 3 bits WORD Same as nvoFcuStatus Same as nvoFcuStatus 6 bits Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit SNVT_lev_percent digital state or value
user address
NvName
field name
default
nciApplVer nciApplVer nciCntrlSettings nciFcuConfig nciWallMod nciWallMod nvoFcuStatus nvoFcuStatus nvoFcuStatusP nvoFcuStatusP nvoSensor nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoStatus nvoUnitStatus
not_used1 not_used2 reserve not_used spare_field[0] spare_field[1] not_used spare_field[0] not_used spare_field[0] not_used out_of_limits open_circuit out_of_service mechanical_fault feedback_failure over_range under_range electrical_fault unable_to_measure fail_self_test self_test_in_progress locked_out manual_control in_override reserved1 reserved2 econ_output
EN0B-0377GE51 R0703
80
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C5. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL W7752D
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.