Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual HONEYWELL W7754Q. We hope that this HONEYWELL W7754Q user guide will be useful to you.
Lastmanuals help download the user guide HONEYWELL W7754Q.
You may also download the following manuals related to this product:
HONEYWELL W7754Q DATASHEET (306 ko)
Manual abstract: user guide HONEYWELL W7754Q
Detailed instructions for use are in the User's Guide.
[. . . ] W7754K, P, Q FAN COIL UNIT CONTROLLERS
HONEYWELL EXCEL 5000 OPEN SYSTEM
INSTALLATION INSTRUCTIONS
Excel 10
GENERAL INFORMATION
LonWorks service LED LonWorks service button left DIP switch (USED = wall module connected) terminal assignment label right DIP switch (USED = terminal 11 enabled)
W7754K1001 · 230 Vac power supply · one triac output · one digital output, for the low-voltage Pulse-Width Modulated (PWM) control of a solid-state relay employed in high-current electrical reheat applications · three relays W7754P1000 · 230 Vac power supply · four triac outputs · four relays W7754Q1008 · 24 Vac power supply · four triac outputs · four relays See also Table 1 on page 3 for a complete overview of terminals and their functions.
UNUSED WALL MOD. USED
ON
UNUSED DI2 USED
0345
FAN DI2
W7754Kxxxx
230 Vac, 50/60 Hz max. 5 VA unloaded
10A 2A
GND
LED
D-71101 Schönaich Made in Germany
triac 0. 5 A
+-
8 9 10 11 12 34567
DI1 SENS GND SET
12
RS1A 23D25
131415 16 17 18
III II fan I L N
1920 2122 2324
close open close open com com
2526
NL 230 V
2A/M
LON
5342 1
T7460 / T7560
230 V
OUT1 OUT2
230 Vac
relays terminals for hardwiring to wall module and/or sensor(s) removable LonWorks terminal plug digital output for low-voltage PWM control of solid-state relay
triacs
fuse
removable power supply terminal plug
BEFORE INSTALLATION
IMPORTANT It is recommended that the controller be kept at room temperature for at least 24 hours before applying power; this is to allow the evaporation of any condensation resulting from low shipping / storage temperatures. US requirement, only: This device must be installed in a UL-listed enclosure offering adequate space to maintain the segregation of line voltage field wiring and Class 2 field wiring.
Fig. [. . . ] NOTE: The intended use of the wall module's buttons must be configured using Honeywell's LNS plug-in. Supported wall module functions
Excel 10 W7754K, P
Excel 10 W7754Q
T7560 button T7460C T7460D T7460E T7460F T7560A left middle right left middle right
override ·
unit ON/OFF
fan speed ·
230 Vac 25
230 Vac 26
24 Vac 25
24 Vac 26
· ·
· · ·
230 Vac 25
230 Vac 26
24 Vac 25
24 Vac 26
24 Vac (+/-20%)
· · · ·
230 Vac 25
230 Vac 26
T7560B
N
L
N
L
230 Vac (15% / +10%) 50 / 60 Hz
230 Vac (15% / +10%) 50 / 60 Hz
Fig. Connection to power supply NOTE: Do not reverse the polarity of the power connection cables, and avoid ground loops (i. e. avoid connecting one field device to several controllers) as this may result in short circuits damaging your device.
Example: The T7560A has a left button which can be configured to act as a fan speed button, a middle button which can be configured to act as a unit ON/OFF button, and a right button for override. If the wall module's LED flashes twice per second, a network command has placed the controller into either the "standby" or the "occupied" mode. If the wall module's LED flashes four times per second, the controller is responding to a network management "wink" command. Different network configurations (daisy-chain, loop, and star configurations, or any combination thereof) are possible (see also Excel 50/500 LONWORKS Mechanisms Interface Description, EN0B-0270GE51).
Connecting to the LONWORKS Network
IMPORTANT Do not bundle wires carrying field device signals or LONWORKS communications together with highvoltage power supply or relay cables. separation of 3 inches (76 mm) between such cables. Local wiring codes may take precedence over this recommendation. IMPORTANT Try to avoid installing in areas of high electromagnetic noise (EMI). The unit must be wired to the LONWORKS network using level IV 22 AWG (Belden part number 9D220150) or plenum-rated level IV 22 AWG (Belden part number 9H2201504) nonshielded, twisted-pair, solid-conductor wire. When possible, use Honeywell AK3781, AK3782, AK3791, or AK3792 cable (US part numbers). See Excel 50/5000 LONWORKS Mechanisms, EN0B-0270GE51, for details, including maximum lengths. Use wire with a minimum size of 20 AWG (0. 5 mm2) and a maximum size of 14 AWG (2. 5 mm2).
·
· ·
Configuration of the LED to Display Info on Occupancy Mode The wall module's LED can also be configured to indicate the Excel 10 W7754 FCU Controller's effective occupancy mode. Specifically: · If the wall module's LED is OFF, the controller is in the "unoccupied" mode. · If the wall module's LED is ON, the controller is in the "occupied" mode. · If the wall module's LED flashes once per second, the controller is in the "standby" mode. · If the wall module's LED flashes four times per second, the controller is responding to a network management "wink" command. Configuration of the LCD to Display Info on Occupancy Mode The T7560 Wall Module's LCD can be configured to display various symbols to indicate the Excel 10 W7754 FCU Controller's effective occupancy mode. Specifically: · If is displayed continuously, the controller is in the "occupied" or "override" mode; if it flashes, the given mode has been overridden. · If is displayed continuously, the controller is in the "standby" mode; if it flashes, the "standby" mode has been overridden. · If is displayed continuously, the controller is in the "unoccupied" mode; if it flashes, the "unoccupied" mode has been overridden. [. . . ] Hardware Limits for Excel 10 W7754K, P (230 Vac Power Supply) · Low signal: 0 V; high signal: 230 Vac · Maximum allowable continuous current for each individual triac output: 500 mA · Maximum allowable peak current (for 10 seconds) for each individual triac output: 1 A · Maximum allowable continuous current for all of the triac outputs together: 1 A. · cos > 0. 8
Possible Problems and Recommended Actions
Check if the LONWORKS service LED's behavior is changed if you switch the power OFF/ON. Please contact Honeywell if this does not solve the problem.
EN1B-0304GE51 R0506C
6
EXCEL 10 W7754K, P, Q FAN COIL UNIT CONTROLLERS
Accessories
Table 5. LONWORKS Service LED Behaviors and Meanings LED blinking pattern meaning
Defective device hardware. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL W7754Q
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual HONEYWELL W7754Q will begin.