[. . . ] XL 800 Series
FOR SMOKE CONTROL
HONEYWELL EXCEL 5000 OPEN SYSTEM
INSTALLATION AND COMMISSIONING INSTRUCTIONS CONTENTS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Before Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] Smoke control must be initiated by a listed fire alarm control unit or in zone automatic alarm devices and not devices located outside of the smoke control zone. Interconnecting wiring must be within 20 ft. Verify that the AC voltage source connected to the inside of the main line voltage terminal block is from a UL-1481 listed uninterruptible power supply. The main line voltage terminal block maximum current draw is 0. 5 A. For 220/240 VAC (60 Hz) applications, verify that no potential between any conductor and the earth ground exceeds 150 VAC. All external LONWORKS bus field wiring must be limited to 4000 ft. (1200 meters) and be terminated to 14506944-001 transient protector (35 V, 290 mA max. ) except C-Bus field wiring communicating at 1 MHZ, which uses 14502412-014 transient protector (19 V, 500 mA). Panel Bus wiring must be in the same enclosure or less than 20 ft. No protection is required.
CAUTION
Risk of electric equipment damage!
Failure to use listed/approved replacement parts can
damage product, degrade operation and result in loss of safety function. This product must be installed and operated within its environmental, mechanical, and electrical specifications as contained in this document. When servicing, use only listed/approved replacement parts ordered directly from the manufacturer.
9
10
Typical Power Limited Circuit for XL800
POWER LIMITED POWER LIMITED
2
NON-POWER LIMITED CPU ANALOG INPUT MODULE ANALOG OUTPUT MODULE DIGITAL INPUT MODULE DIGITAL OUTPUT MODULE
POWER LIMITED 24VAC CONTROL 24VAC ACCESSORY 24VAC
NON-POWER LIMITED
11
2 1
NON-POWER LIMITED
3
2 1
NON-POWER LIMITED
12
Fig. Typical power-limited circuit for XL800
1
Data File Set-Up
Generate the engineering data file for the XL800 Series Controllers. This data file has a mix of hardware points for the necessary inputs and outputs to control fans, dampers, and other equipment. In addition to the inputs and outputs, a custom control program is written to control the outputs per the sequence. The XL800 controllers can reset the program once the data from the operator interface indicates a normal condition for the dedicated smoke control equipment. Wire conditions must be programmed to provide annunciation of trouble conditions. Also required for a dedicated application for the XL800, is a weekly time program to test control points, fans, and dampers by exercising the equipment and verifying feedback automatically during low building activity periods.
14507287-001 through -003 power module accessory 24 VAC output (rated 2A) must be wired in accordance with NFPA 70, Article 725 when routed within the cabinet or adjacent cabinets and also for external field wiring. 14507287-001, -002, -003, and -007 control power module 24 VAC output is inherently power-limited. Thus, all sourced power from the XL800 controller is power-limited. All field wiring from these controllers meet NFPA 70, Article 725 power limited Class II requirements. If a separate auxiliary power-limited 24 VAC power source is required, use a control power module (14507287-001 or -007 control supply). Devices must be installed in areas as shown. [. . . ] XF824AU connection example
M
71 COM A 72 73 74
COM B 24 V~ 24 V~0
COM A COM B 24 V~ 24 V~0
75 76 77 78
72 COM B 73 74
24 V~ 24 V~0
71 COM A
NO NC COM CON
11 12 13 14
NO 21 NC 22 COM 23 CON 24
NO NC COM CON
31 32 33 34
NO NC COM CON
41 42 43 44
NO NC COM CON
51 52 53 54
NO NC COM CON
61 62 63 64
25
3
2 M
1
14507287 SERIES POWER MODULE
Fig. XFR825AU connection example
EN1B-0410GE51 R0908A
30
Excel 800
Troubleshooting
Troubleshooting
Testing Wiring Connections
The push-in terminals feature small holes (1 mm in diameter) which can be used to measure the signals.
Insert a probe (1) as shown on the right.
Fig. Testing wiring connections
Troubleshooting on the XCL8010AU Controller
The following LEDs of the XCL8010AU Controller can be used for troubleshooting purposes: · Power LED (green) · Alarm LED (red) · LONWORKS service LED · C-Bus Tx and Rx LEDs · HMI Tx and Rx LEDs
Power LED (green)
Table 37. XCL8010AU power LED case 1 2 ON Flashing power LED Normal operation One or more of the internal voltage supplies are outside of the permissible ranges. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE HONEYWELL XL800
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.