Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual INTERMATIC PG2000. We hope that this INTERMATIC PG2000 user guide will be useful to you.
Lastmanuals help download the user guide INTERMATIC PG2000.
Detailed instructions for use are in the User's Guide.
[. . . ] Refer to the wiring configurations and voltages on page 2 and 3 for additional information. Remove the knockout from the power bus, load center or equipment panel that will position the SPD for the shortest wire lead distance. Note that the shorter the lead length between the SPD and the connection point, the better the protection. [. . . ] Connect each phase wire, BLACK or RED, to the power bus. Select a method of connection that complies with local electric code and the National Electric Code. Make sure that the phase wires have the correct voltage level between them. Note that for the 240 volt High Leg Delta, the wire lead for the High Leg is colored RED, and must be connected to the phase that measures approximately 208 volts to neutral and to ground. Failure to comply with this instruction will result in failure of the SPD and void the warranty. If remote monitoring is used, remove the ½" knockout and connect wire leads to the terminal strip located in the monitoring section of the PanelGuard cabinet. Be sure to comply with local and national wiring codes for the voltage of the monitoring circuit. Check all connections for proper tightness or torque. Observe the suggested torque values published by the manufacturer when circuit breakers or separate disconnect devices are used. Close and secure the hinged cover using the locking bolts provided with the cover. Make sure that each Protection Status indicator on the PanelGuard is ON. If not, turn power off and recheck each installation step listed above. Make sure that the Alarm Warning indicator on the PanelGuard is OFF. If not, turn power off and recheck each installation step listed above. For troubleshooting assistance, call Intermatic at 800-391-4555.
4. 18.
19.
WIRING CONFIGURATIONS
120 VAC Single Phase
Transformer Secondary Load Center or equipment L1 Black
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
PanelGuard
Line to Neutral Line to Ground
120 120
N G
White
Green
Use of Circuit Breakers is optional
120/240 VAC Single (Split) Phase
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 L2 N G Black Black White Green
PanelGuard
Line to Line Line to Neutral Line to Ground
240 120 120
Use of Circuit Breakers is optional
120/208 VAC Three Phase WYE
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 Black L2 Black L3 Black N G White Green
PanelGuard
Line to Line Line to Neutral Line to Ground
208 120 120
Use of Circuit Breakers is optional
120/240 VAC Three Phase Delta High Leg Delta
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 Black L2 Red L3 Black N White G Green
PanelGuard
Line to Line Line to Neutral High Leg to Neutral Line to Ground High Leg to Ground
240 120 208 120 208
Use of Circuit Breakers is optional
277/480 VAC Three Phase WYE
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 Black L2 Black L3 Black N G White Green
PanelGuard
Line to Line Line to Neutral Line to Ground
480 277 277
Use of Circuit Breakers is optional
480 VAC Three Phase DELTA
Transformer Secondary
VOLTAGE CONFIGURATION CONFIRMATION MODE VOLTAGE
Load Center or equipment
L1 L2 L3 Black Black Black Green
PanelGuard
Line to Line Line to Ground
480 480
G
Use of Circuit Breakers is optional
Alarm relay for remote monitoring
Violet n/c Brown - c
PanelGuard
Common - Brown Normally Open - orange Normally Closed - Violet
Orange n/o
Normal operating condition relay energized
Violet n/c Brown - c Orange n/o
AC lead connections
Alarm relay connections
Alarm condition relay not energized
Contact your Intermatic Representative or Distributor for information on other hardwired panel Surge Protection Devices. [. . . ] TO THE EXTENT ALLOWED BY LAW, ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED IN DURATION TO THE DURATION OF THIS LIMITED WARRANTY.
(4) Limitation of Remedies
In no case shall Intermatic be liable for any special, incidental, or consequential damages based upon breach of warranty, breach of contract, negligence, strict tort, or any other legal theory. Such excluded damages include, but are not limited to, damage to software, loss of data, loss of profits, loss of savings or revenue, loss of use of the Product or any associated equipment, cost of capital, cost of any substitute equipment, facilities or services, downtime, the claims of third parties including customers, damage to property and personal injury. Some states do not allow limits on warranties or on remedies for breach in certain transactions. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE INTERMATIC PG2000
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual INTERMATIC PG2000 will begin.