Detailed instructions for use are in the User's Guide.
[. . . ] 2 1. 2 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1. 3 SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1. 4 INSULATION RESISTANCE TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1. 5 LOCATIONS OF CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] Discharge the refrigerant by using a refrigerant recovery system. Remove 2 screws which fasten the condenser. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections. Re-install by referring to the procedures above.
Figure19
2. 4. 2 EVAPORATOR
1. Discharge the refrigerant by using a refrigerant recovery system. After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections. Re-install by referring to the procedures above.
--10--
2. 4. 3 CAPILLARY TUBE
1. Discharge the refrigerant by using a refrigerant recovery system. After discharging the refrigerant completely, unbraze the interconnecting tube of the capillary tube. Re-install by referring to the procedures above. NOTES Replacement of the refrigeration cycle. If more charge is required, the high-side will not take it. With the unit running, open valve B and add the balance of the charge. Do not add the liquid refrigerant to the lowside. Watch the low-side gauge, allow pressure to rise to 30 lbs. Turn off valve B and allow the pressure to drop. Repeat steps B and C until the balance of the charge is in the system. When the unit is operating correctly, use the pinch-off tool with the unit still running and the clamp on the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder the pinch-off tube closed. Turn off the unit, allow setting for a while and then test the leakage of the pinch-off connection.
--11--
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment, pinch-off tool capable of making a vapor proof seal, leak detector, tubing cutter, hand tools to remove components and service valve.
COMPOUND GAUGE MANIFOLD GAUGE
B
A
CONDENSER (HIGH PRESSURE SIDE)
SEE INSETS BELOW
COMPRESSOR
EVAPORATOR (LOW PRESSURE SIDE) CAPILLARY TUBE
LO
HI
CHARGING CYLINDER
A B
EXTERNAL VACUUM PUMP
B
A
C
Figure 20A-Pulling Vacuum
Figure 20B-Charging
--12--
3. INSTALLATION
This air conditioner is designed with a button-down chassis so it can be easily installed in a window.
3. 1 SELECT THE BEST LOCATION
1. [. . . ] Replace the thermistor if the circuit is open.
Blower
Loose set screw Worn bearings
Compressor will not run, fan motor runs.
Voltage
Wiring
Thermistor
Capacitor (discharge capacitor before servicing. ) Compressor
Check the capacitor. Replace if not within ±10% of manufacturer's rating, replace if shorted, open, or damaged. Check the compressor for open circuit or ground. If open or grounded, replace the compressor. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE LG ACM0860AC
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.