[. . . ] However, with the recent increase in the number of high density buildings and use of multi air conditioner systems to ensure effective use of floor space, energy conservation and individual control, installers should ensure it is not possible to exceed density limits in the event of a refrigerant leak. In particular, where a single unit of the multi conditioner system is to be installed into a small room, select a suitable model and installation procedure so that if refrigerant leaks out, density limits are not exceeded. In a room where there is a risk of the density limit being exceeded, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The density can be calculated as shown below; Total amount of refrigerant (kg) Min. [. . . ] 50m
NOTE :
The wiring lengths from the outdoor unit to the indoor units pull box (isolator) when connected in parallel(Below figure) are stated in the above table. This assumes a voltage drop of no more than 2%. If the length exceeds 50m select wire specification in accordance with indoor wiring standards.
· Group Operation using a Remote Controller Switch
Group operation of multiple indoor units (8 units) using a single remote controller
Indoor unit No. 1
AB
No. 2
AB
No. 3
AB
No. 4
AB
No. 7
AB
No. 8
AB
Remote controller
(A. B)
Indoor power source single phase 220240V, 50Hz 220V, 60Hz Earth leakage breaker
Switch Pull box
Indoor unit
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
CAUTION
(1) Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems together. (2) When running power supplies and control wires parallel to each other, run them through separate conduits, or maintain a suitable distance between them. (Current capacity of power wires: 10A or less for 300mm, 50A or less for 500mm)
100
System wiring diagram
Power source at outdoor side 3-phase 380415V, 50Hz 380V, 60Hz Earth leakage breaker Switch
Control Communication line
Pull box
Switch Earth leakage breaker Power source at indoor side Single phase 220240V, 50Hz 220V, 60Hz
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Remote control
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
Remote controller
Connection summary for indoor unit/outdoor unit
Power source at outdoor side 3-phase 380-415V, 50Hz 380V, 60Hz
L1 L2 L3 N
Power source at outdoor side 3-phase 380-415V, 50Hz 380V, 60Hz
L1 L2 L3 N
Power source at outdoor side 3-phase 380-415V, 50Hz 380V, 60Hz
L1 L2 L3 N
Power source at outdoor side 3-phase 380-415V, 50Hz 380V, 60Hz
L1 L2 L3 N
Earth
U1 U2 U5 U6
Earth
U1 U2
U5 U6
Earth
U1 U2
U5 U6
Earth
U1 U2
U5 U6
Pull box Power source at indoor side Single phase 220-240V, 50Hz 220V, 60Hz
Control transmission line
Connection of shield wire to close end
Earth
Earth
U1 U2
LN
LN
U1 U2
LN
U1 U2
Earth
AB
Earth
AB
Earth
AB
Indoor unit
Indoor unit
Indoor unit
Remote controller
Remote controller
Remote controller
101
Connection of Power Supply Cable with Control Wire
Insert power supply cable and control wire after removing knockout of the piping/wiring panel at the front side of the outdoor unit.
Knockout for power supply cable Knockout for control wire Piping/wiring panel
When inserting power supply cable and control wire, protect from the edge where the knockout has been removed.
Power supply cable
1. Connect the power supply cables and earthing wire to the power supply terminal block. Ensure the cabling passes through the notched section on the side of the electrical parts box and is secured with a clamp.
Control wire
1. Connect the control wiring between the indoor and outdoor units (U1, U2, U5, U6). On the outdoor unit ensure wiring is passed through opening at the side of the electrical parts box and secured with a clamp. Use a 2 core shielded wire for control wiring (1. 25mm² or more) in order to prevent noise issues. (Non-polarity)
NOTE :
1) Separate the power supply cables and each control cable. Insulate the pipe and the connector on the indoor unit as well. 3) Ensure that all pipe connections are attached securely. (When using polyvinyl chloride pipe, do not forget to apply the adhesive for hard polyvinyl chloride. )
10-2. Connections to a horizontal main pipe should be dropped in from above. Furthermore, use pipe with a nominal diameter of at least VP20 (VP30) for the collective drain pipe. Limit as much as possible the number of VP25 (Outer dia. : Ø32mm) units that drain into a collective pipe in order to keep the length of the horizontal main pipe to a minimum. Do not connect models with a built-in Extended drain pump and models that use gravity bent stack drains to the same horizontal pipe.
Use as long a pipe as possible (10cm) VP30 (Outer dia. : Ø38mm) Downward slope of at least 1/100
10-3. Selecting the Diameter for the Collective Pipe
Calculate the amount of drain water based on the number of indoor units that will be connected to the collective drain pipe, then select the pipe diameter accordingly. Assume 2 liters/hour per horsepower for the amount of drain water produced by an indoor unit. [. . . ] · Short plug position (CN112, CN111, CN110 from the left) · Selection can be made by the changing of the short plugs.
Short plug position
Set data
Short Open
External static pressure
CN112 CN111 CN110
0000
CN112 CN111 CN110
10 Pa (At shipment)
0001
CN112 CN111 CN110
20 Pa
0003
CN112 CN111 CN110
35 Pa
0006
50Pa
195
Appendix High Wall Type (2 series)
Installation space
Ensure that there is sufficient space for the installation and service work. Keep a minimum of 100mm for clearance between the top plate of the indoor unit and the ceiling surface.
Installation diagram of Indoor and outdoor units
100 mm or more
Before installing the wireless remote controller
· With the remote controller cover removed install the batteries supplied correctly, observeing their polarity. 2 Wireless remote controller Cover
170 or mmm ore
For the rear left and left piping
Hook
Wall
1
Installation plate
Hook
170 or mmm ore
Insert the cushion between the indoor unit and wall, and tilt the indoor unit for better operation.
3 Batteries
Shield pipe
Do not allow the drain hose to slacken
Air
filte
r
Cut the piping hole sloped slightly
(Att
ach
to t
he
6
fron
Pan head wood screw
t pa
nel)
Make sure to run the drain hose sloped downwards.
2
Wireless remote controller
4
Remote control holder
The auxiliary piping can be connected at the left, rear left, rear right, right, bottom right or bottom left.
· Wired remote controller
RBC-AMT21E RBC-AMT31E
Right
· Simple wired remote controller
RBC-AS21E RBC-AS21E2
Rear right
Rear left Bottom right
Left Bottom left
· Weekly timer application
RBC-AMT31E and RBC-EXW21E2 When installing the Flow Selector Unit (FS Unit), Maintain a minimum space of 300mm for wiring work.
Installation position
· · · · A position which provides the sufficient space around the indoor unit as shown in the above diagram. A position where there is no obstacle near the air inlet and outlet. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE LG AS110I
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.