Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual LG GL-302QMASWQOM. We hope that this LG GL-302QMASWQOM user guide will be useful to you.
Lastmanuals help download the user guide LG GL-302QMASWQOM.
Detailed instructions for use are in the User's Guide.
[. . . ] If an above action is executed during the fan operation, the protective control works to stop the unit operation, and the check code "P12" may be issued. When the desired operation has finished, be sure to reset the system to clear "P12" error code using the leak breaker of the indoor unit. Then push the operation stop button of the remote controller to return to the usual operation.
CONTENTS
SAFETY CAUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] NO Are characteristics of TD sensor resistance value normal?YES NO * Refer to Characteristics-4.
Check and correct the charged refrigerant amount.
Improve and delete the cause
Replace TD sensor.
Check CDB. Defect Replace * For RAV-SM562AT-E, replace control P. C. board.
®
[H01 error]
Is power voltage normal?YES
NO
Improve power line.
YES Is not abnormal overload?NO Is the circuit detected by current sensor normal?YES NO
Improve and delete the cause.
Check and correct circuit cables.
Check IPDU. Defect Replace * For RAV-SM562AT-E, replace control P. C. board.
®
96
[P04 error]
Is high-voltage protective operation by TE sensor normal?YES
NO
Is connection of cabling connector normal?YES
NO
Correct connection of cabling connector.
Check TE sensor. If [E03] occurs during an operation, the air conditioner stops. [F29 error] / [12 error] [F29 error] or [12 error] indicates detection of trouble which occurred on IC10 non-volatile memory (EEPROM) on the indoor unit P board during operation of the air conditioner. . C.
* If EEPROM has not been inserted when the power was turned on or if EEPROM data never be read/written, the automatic address mode is repeated. In this time, the central controller displays [97 error].
(Power ON) (Approx. 3 minutes) [SET] is displayed on main remote controller. (Repetition) LED (D02) on indoor unit P. C. 10 seconds.
Reboot (Reset)
[P31 error] (Sub indoor unit) When the master unit of a group operation has detected [E03], [L03], [L07], or [L08] error, the sub unit of the group operation detects [P31 error] and then it stops. There is no display of the check code or alarm history of the main remote controller. (In this model, the mode enters in automatic address set mode when the master unit has detected [E03], [L03], [L07], or [L08] error. )
99
10-4-2. Relational Graph of Temperature Sensor Resistance Value and Temperature
20
40
TA sensor
30
TC, TCJ sensor Caracteristics-2
Resistance (k9)
10
Caracteristics-1 Resistance (k9)
20
10
0
10
20
30
40
50
0 10
0
10
20
30
40
50
60
70
Temperature [°C]
Temperature [°C]
200
20
TE, TO, TS sensor
Caracteristics-3
Resistance (k9) (10°C or lower)
100
Resistance (k9) (10°C or higher)
10
0 -10 0 10 20 30 40 50 60 70
0
Temperature [°C]
TD sensor
200
Caracteristics-4
20
Resistance (k9) (50°C or lower)
100
Resistance (k9) (50°C or higher)
10
0 50 100
0
Temperature [°C]
100
11. BOARD
[Requirement when replacing the service indoor P. C. [. . . ] When the power cord size does not match with Pshape clamp, procure the most appropriate one at the local site.
190
No. Assembly 3
Photo / Explanatory diagram
Procedure
Return a set of the refrigeration cycle assembly into the outdoor unit base plate and reassemble sound insulation board, partition plate assembly, fan motor assembly, and side cabinet (R/L) as original. Fix the thermostat fixing plate to the side cabinet (R), built in the inverter assembly, and then connect various cables. After then, incorporate front cabinet, upper cabinet, wiring cover, and valve cover as before. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE LG GL-302QMASWQOM
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual LG GL-302QMASWQOM will begin.