[. . . ] Indoor Unit Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Purging the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Refrigerant Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cutting/Flaring the Pipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] Where the air filter can be removed and cleaned easily.
Space requirements for installation & service
Construction Standard for Inspection Hole. 1) In case, the ceiling is textile, Inspection hole dose not need. 2) In case, the ceiling is plaster board, Inspection hole depends on Inside height of the ceiling. Height is more than 1m : Only "B" [Inspection for PBA] is applied. Height is less than 1m : Both "A" & "B" are applied. "A" & "B" are inspection holes.
Unit Depth(D)+50mm
20mm or more
Unit Width(W) "A"=W+100mm "B"=500mm
20mm or more
You must have 20mm or more space between the ceiling and the bottom of indoor unit. Otherwise, the noise from the vibration of indoor unit may bother the user. When the ceiling is under construction, the hole for check-up must be made to take service, clean and repair the unit. It is possible to install the unit at an height of between 2. 2~2. 5m from the ground, if the unit has a duct with a well defined lenght (300mm or more), to avoid fan motor blower contact.
Insulation Guide
D
B Back
Front
Thickness: more than 10mm Indoor unit 20. 0~28. 0kW (1240x470x1040) A 1240x1040 B 1240x1040 C 470x1040 D
A
C
Front/Back
Insulate the front and back side in proper size at the same time when insulating the suction duct and discharge duct.
470x1040
Insulate the end of the pipe and some curved area by using separate insulator. Insulate the discharge and suction part at the same time when you insulate connection duct.
E-7
Selecting the Installation Location (Continued)
Drawing of the indoor unit
1306 Suspension position 1188 Air inlet duct flange 140X8=1120
Unit : mm
914 Suspension position
1040
140X8=1120 1188 Air outlet duct flange 1240
34 660 647 598 100X2=200 93 22 209 236 Suction side
OD 32 35
470
Discharge side
No.
Name
Liquid pipe connection Gas pipe connection Drain pipe connection Drain pipe connection (Option drain pump) Power supply/Communication connection Air discharge grille flange Air suction flange Hook
Description
ø9. 52 (3/8") ND200/220 : ø19. 05(3/4") ND280 : ø22. 22(7/8") VP25 (OD ø32, ID ø25) VP25 (OD ø32, ID ø25)
3/8" or M10
E-8
29
385
Indoor Unit Installation
It is recommended to install theY-joint before installing the indoor unit. 1 Place the pattern sheet on the ceiling at the spot where you want to install the
indoor unit. Note Fix the flexible hose to the indoor unit with the supplied cable clamp securely. (Use the screwdriver to fix the flexible hose securely. )
Cable Clamp
Indoor Unit
Cable-tie Clamp hose
3
Install the drain hose so that its length can be as short as possible. Internal diameter of the drain hose should be the same or slightly bigger than the external diameter of the drain hose port. Inner diameter of the drain hose 32mm(Inner diameter) Note Give a slightly slant to the drain hose for proper drainage of condensate. Fix the flexible hose to the PVC with the supplied cable tie securely.
Insulation
Flexible hose
Must fit tightly against body without any gap.
No gap
4
Wrap the drain hose with the insulation drain as shown in figure and secure it.
E-14
Drain pipe Connection
Without the drain pump 1
Install horizontal drain pipe with a slope of 1/100 or more and fix it by hanger space of 1. 0~1. 5m. Install U-trap at the end of the drain pipe to prevent a nasty smell to reach the indoor unit. Do not install the drain pipe to upward position. It may cause water flow back to the unit.
2
3
1~1. 5m
Hanger H50mm
1H 2
Drain pipe cleaning hole Ceiling
Horizontal drain pipe more than 1/100 slope
With the drain pump 1 2 3
The drain pipe should be installed within 330mm from the flexible hose and then lift down 20mm or more. Install horizontal drain pipe with a slope of 1/100 or more and fix it by hanger space of 1. 0~1. 5m. Install the air vent in the horizontal drain pipe to prevent water flow back to the indoor unit. Note You may not need to install it if there were proper slope in the horizontal drain pipe.
4
The flexible hose should not be installed upward position, it may cause water flow back to the indoor unit.
Air vent
300mm or less 200mm or more 20mm or more Within 330mm
1~1. 5m Hanger
Flexible hose
Ceiling
Horizontal drain pipe more than 1/100 slope
E-15
Drain pipe and Drain hose Installation (Continued)
Centralized Drainage
Without the drain pump 1
Install horizontal drain pipe with a slope of 1/100 or more and fix it by hanger space of 1. 0~1. 5m.
2
Install U-trap at the end of the drain pipe to prevent a nasty smell to reach the indoor unit.
100mm or more
Ceiling
Horizontal drain pipe more than 1/100 slope
With the drain pump 1
Install main air vent at the front of the farthest indoor unit from the main drain when installed indoor units are more than 3.
2
You may need to install individual air vent to prevent water flow back at the top of each indoor unit drain pipe.
Hanger Individual air vent
1~1. 5m
Main air vent
330mm or less Centralized horizontal drain pipe (more than 1/100 slope)
Main drain pipe
E-16
Testing the drainage
Prepare a little water about 2 liters.
1
Pour water into the drain pan in the indoor unit as shown in figure.
2 3
Confirm that the water flows out through the drain hose.
When the drain pump is installed, operate the unit as cooling mode and check a drain pump pumping.
Drain pan
4
Check drain water drops at the end of the drain pipe.
Drain pipe
Drain water drops
5
Make sure there is no water leak at the drainage.
The designs and shape are subject to change
according to the model.
6
Reassemble the cover of water supply intake.
E-17
Wiring Work
Power and communication cable connection
1 2
Before wiring work, you must turn off all power source. [. . . ] When MAIN address is set as "12".
Note
For Example
Setting RMC Address
The SW03 and SW04 RMC switch is the address setting switch for controlling the indoor unit with the centralized controller. You must set the SW03, SW04 and K2 switch when using the centralized controller. You don't have to set the SW03 and SW04 RMC switch when not using the centralized controller. When RMC address is set as "12".
For Example
SW03
SW04
E-22
Additional Functions
No.
K1
Function
External room sensor Centralized controller Drain Pump
ON
Not use Not use Not use
OFF
Use Use Use
K1 K2 K3 K4
SW05
K2 K3 K4
g K1 OFF
Heating mode : Setting temperature compensation value = 0°C Thermo OFF Fan OFF
No.
K5
Function
Heating Current Temperature Compensation Filter Time Hot Water Heater -
ON
2°C 1, 000 hours Not Use -
OFF
5°C 2, 000 hours Use -
SW06
K6 K7 K8
K5K6K7K8
No.
K9
Function
Indoor Expansion Valve For Heating Stop Wired Remocon Group Master External control Operation output
ON
Fix 160 step Not Use Not Use Thermal ON
OFF
0 or 160 step Use Use Operation ON
K9K10K11K12
SW07
K10 K11 K12
E-23
Final Checks and User Tips
To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly.
1
Check the followings. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE LG GR-191SV
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.