Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual LG GR-L207TUJA. We hope that this LG GR-L207TUJA user guide will be useful to you.
Lastmanuals help download the user guide LG GR-L207TUJA.
Detailed instructions for use are in the User's Guide.
[. . . ] Store the operation and installation manual in a safe location and remember to hand it over to the new owner if the air This manual explains how to install an indoor unit with a split system with two LG units. The use of other types of
units with different control systems may damage the units and invalidate the warranty. The manufacturer shall not be responsible for damages arising from the use of non compliant units. The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper connection of electric and requirements set forth in the "Operating limits" table, included in the manual, shall immediately invalidate the warranty. [. . . ] Replace the terminal board cover, carefully tightening the screw. Connect the power cable to the auxiliary circuit breaker. The designs and shape are subject to change according to the model.
3 4 5 6
MH040FXA2B/MH050FXA2B/MH18VF1X/MH19VF1X A-unit
1(L) 2(N) F1 F2
Indoor unit
1(L)
B-unit
2(N) F1 F2
1
2
F1 F2
Assembly cable
1
2
F1 F2
Earth terminal
B 1 2 C
F1 F2
Earth terminal
B 1 2 C
F1 F2
Earth terminal
Earth terminal
Outdoor unit
1(L) 2(N) 1(L) 2(N)
L
N
Power cable to indoor units
Cable Type: A Cable Type: B Cable Type: C
A
Main Power supply cable Earth terminal
F1 F2 F1 F2
1
2
Communication cable to indoor units
The specification for cables :
Model MH040FX*A2B MH050FX*A2B MH18VF1X MH19VF1X MH060FX*A3B MH070FX*A4B MH080FX*A4B Main Power Supply Cable Indoor Power Supply Cable Type Specication Type Specication 3G, 2. 5mm2 or more, H07RN-F 3G, 1. 0mm2 or more, H07RN-F Communication Cable Specication Type 2G, 0. 75mm2 or more, H07RN-F FUSE 20A
MCCB Frame : 30A Trip : 20A Frame : 30A Trip : 25A Frame : 30A Trip : 30A
Type GL
20A 25A 30A
20A 30A
Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be incorporated in a wire with a contact opening of 3mm.
E-15
INSTALLING THE OUTDOOR UNIT
Connecting the Cables to the Outdoor Unit(Continued)
MH060FXA3B A-unit
1(L) 2(N) F1 F2
B-unit
1(L) 2(N) F1 F2
Indoor unit
C-unit
1(L) 2(N) F1 F2
1
B
2
F1 F2
1
2
F1 F2
Assembly cable
1
2
F1 F2
Earth terminal
2
C
F1 F2
B 1 2
Earth terminal
C
F1 F2
B 1 2
Earth terminal
C
F1 F2
1
Earth terminal
Earth terminal
Earth terminal
Outdoor unit
1(L) 2(N) 1(L) 2(N) 1(L) 2(N)
L
N
Main Power supply cable
F1 F2
F1 F2 F1 F2
A
B
C
Power cable to indoor units
A
1
2
A
Earth terminal
B
C
Communication cable to indoor units
Cable Type: A Cable Type: B Cable Type: C
The specification for cables :
Model MH040FX*A2B MH050FX*A2B MH18VF1X MH19VF1X MH060FX*A3B MH070FX*A4B MH080FX*A4B Main Power Supply Cable Indoor Power Supply Cable Type Specication Type Specication 3G, 2. 5mm2 or more, H07RN-F 3G, 1. 0mm2 or more, H07RN-F Communication Cable Specication Type 2G, 0. 75mm2 or more, H07RN-F FUSE 20A
MCCB Frame : 30A Trip : 20A Frame : 30A Trip : 25A Frame : 30A Trip : 30A
Type GL
20A 25A 30A
20A 30A
Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be incorporated in a wire with a contact opening of 3mm.
E-16
INSTALLING THE OUTDOOR UNIT
MH070FXA4B / MH080FXA4B A-unit
1(L) 2(N) F1 F2
B-unit
1(L) 2(N) F1 F2
Indoor unit
C-unit
1(L) 2(N) F1 F2
D-unit
1(L) 2(N) F1 F2
1
2
F1 F2
1
2
Assembly cable
F1 F2
1
2
F1 F2
1
2
F1 F2
B
Earth terminal
2
Earth terminal
C
F1 F2
B 1 2
C
F1 F2
B 1 2
Earth terminal
C
F1 F2
B 1 2
Earth terminal
C
F1 F2
1
Earth terminal
Earth terminal
Earth terminal
Earth terminal
Outdoor unit
1(L) 2(N) 1(L) 2(N) 1(L) 2(N) 1(L) 2(N)
L
N
Main Power supply cable
F1 F2 F1 F2
F1 F2 F1 F2
A
B
C
D
A
1 A 2
B
C
D
Power cable to indoor units
Earth terminal
Communication cable to indoor units
Cable Type: A Cable Type: B Cable Type: C
The specification for cables :
Model MH040FX*A2B MH050FX*A2B MH18VF1X MH19VF1X MH060FX*A3B MH070FX*A4B MH080FX*A4B Main Power Supply Cable Indoor Power Supply Cable Type Specication Type Specication 3G, 2. 5mm2 or more, H07RN-F 3G, 1. 0mm2 or more, H07RN-F Communication Cable Specication Type 2G, 0. 75mm2 or more, H07RN-F FUSE 20A
MCCB Frame : 30A Trip : 20A Frame : 30A Trip : 25A Frame : 30A Trip : 30A
Type GL
20A 25A 30A
20A 30A
Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be incorporated in a wire with a contact opening of 3mm.
E-17
ENGLISH
INSTALLING THE OUTDOOR UNIT
Connecting the Cables to the Outdoor Unit (Continued)
Preparation of cables for outdoor unit terminal block
1 2 E
Main power supply cable: L(mm) Cable of indoor unit Main Power
L(mm)
1
2
E
20
20
90
Power cable to indoor units: L(mm) Cable of indoor unit A B C D
1 2 E
Remark
60 60 70 90
60 60 70 90
80 80 110 90 For 060/070/080 only For 070/080 only
Communication cable to indoor units : L(mm) Cable of indoor unit A The designs and shape are subject to change according to the model. B 15 C D 15 For 060/070/080 only For 070/080 only
1 2
Remark
E-18
INSTALLING THE OUTDOOR UNIT
Transmitter Installation (Optional)
ENGLISH
MH040FXA2B/MH18VF1X/MH19VF1X Accessories (Transmitter: MIM-B13)
Transmitter Transmitter power cable Transmitter communication cable Installation Manual Case Cable-tie
1
Fix the case at with bolts on the side of the control box in the outdoor unit. (See the picture) Attach the transmitter PCB to the case in the control box in the outdoor unit, then connect the power and the communication cable between the transmitter and the outdoor unit; refer to the figure of page 19. If you install a transmitter to an outdoor unit, every indoor unit which is connected to an outdoor unit can be controlled simultaneously. Each outdoor unit connected to the same centralized controller has its own transmitter.
Bolts spec. LED Display side
2
Terminal side
Transmitter
3
4
Fix the case with hinges (Control Box in the outdoor unit)
E-19
INSTALLING THE OUTDOOR UNIT
Transmitter Installation (Optional) (Continued)
MH050FXA2B/MH060FXA3B/MH070FXA4B / MH080FXA4B Accessories(Transmitter: MIM-B13)
Transmitter Transmitter power cable Transmitter communication cable Installation Manual Case Cable-tie
MH050FXA2B
Terminal side Transmitter 7seg. Refrigerant for air purging is not charged in the outdoor unit. MH040FXA2B / MH052FXA2B / MH18VF1X/MH19VF1X
ENGLISH
Indoor A-unit Indoor B-unit
1 Check the piping connections. 2 Connect the charging hose of low pressure side of manifold gauge to the
packed valve having a service port (MH040FXA2B:3/8" service valve 2EA; MH052FXA2B:3/8" service valve 1EA+1/2" service valve 1EA) as shown at the figure. WARNING: Make the electrical connection and leave the system into "stand by mode". This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve - EEV -).
Vacuum Pump
3 Open the valve of the low pressure side of manifold gauge counter-clockwise. 4 Purge the air from the system using vacuum pump for about 10 minutes.
- Close the valve of the low pressure side of manifold gauge clockwise. - Make sure that pressure gauge show -0. 1MPa(-76cmHg) after about 10 minutes. This procedure is very important in order to avoid gas leak. - Turn off the vacuum pump - Remove the hose of the low pressure side of manifold gauge.
Valve stem Stem cap
Service port
5 Set valve cork of both liquid side and gas side of packed valve to the open position. 6 Mount the valve stem nuts and the service port cap to the valve, 7 Check for gas leakage.
and tighten them at the torque of 183kgf·cm with a torque wrench. - At this time, especially check for gas leakage from the 3-way valve's stem nuts, and from the service port cap. .
E-23
COMPLETING THE INSTALLATION
Connecting Up and Purging the Circuit(Cont. )
MH060FXA3B/MH070FXA4B / MH080FXA4B
1 Check the piping connections.
2 Connect the charging hose of low pressure side of manifold gauge to the
packed valve having a service port (5/8" Packed valve) as shown at the figure (Value stem: 1/2" - 20UNF).
A B C
WARNING: Make the electrical connection and leave the system into "stand by mode". [. . . ] Cool mode try-run : Push the [K2] button three times. Heat mode try-run : Push the [K2] button once. After 12 minutes of stationary condition check each indoor unit air treatment: Cooling mode (indoor unit check) --> Inlet air temp. - Outlet air temp: From 10°K to 12°K ( indicative delta T) Heating mode (indoor unit check) --> Outlet air temp. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE LG GR-L207TUJA
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual LG GR-L207TUJA will begin.