Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual LG LRV410TT. We hope that this LG LRV410TT user guide will be useful to you.
Lastmanuals help download the user guide LG LRV410TT.
Detailed instructions for use are in the User's Guide.
[. . . ] The reference piping consists of 5 m of main piping and 2. 5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. [. . . ] Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
2
4-way Air Discharge Cassette Type
Engineering Data Book
60Hz
Model name
Cooling/Heating capacity (Note 1) Power supply Running current Electical characteristics Power consumption Starting current Main unit Appearance Ceiling panel Model Panel color Hight Main unit Outer dimention Ceiling panel Main unit Ceiling panel Width Depth Hight Width Depth Total weight Heat exchanger Soundproof / Heat-insulating material Fan Fan unit Standard air flow High (Mid/Low) Motor Air filter Controller Gas pipe Connecting pipe Liquid pipe Drain port Sound pressure level (Note 2) (High/Med. /Low) (mm) (mm) (Nominal dia. mm) (dB(A)) 30/29/27 9. 5 6. 4 25 (Polyvinyl chloride tube) 31/29/27 32/29/27 35/31/28 38/33/30 43/38/32 46/38/33 46/40/33 12. 7 (m³/h) (W) 800 (730/680) 930 1050 (830/790) (920/800) 14 (mm) (mm) (mm) (mm) (mm) (mm) (kg) (kg) 18 20 4. 0 Fined tube Non-flammable insulation Turbo fan 1290 (920/800) 20 Standard filter (Long life filter) Remote controller 15. 9 9. 5 1320 1970 2130 2130 (1100/850) (1430/1070) (1430/1130) (1520/1230) 68 72 256 840 840 30 950 950 25 (A) (kW) (A)
MMU- AP0092H AP0122H AP0152H AP0182H AP0242H AP0272H AP0302H AP0362H AP0482H AP0562H
(kW) 2. 8/3. 2 3. 6/4. 0 4. 5/5. 0 5. 6/6. 3 7. 1/8. 0 8. 0/9. 0 9. 0/10. 0 11. 2/12. 5 14. 0/16. 0 16. 0/18. 0 1 phase 50Hz 230V (220-240V) / 1 phase 60Hz 220V (Sepatate power supply for indoor units is required. ) 0. 24 0. 021 0. 30 0. 28 0. 023 0. 33 0. 30 0. 026 0. 36 0. 39 0. 036 0. 42 0. 45 0. 043 0. 59 0. 76 0. 088 0. 87 1. 23 0. 92 0. 112 1. 26
Heat-insulating material attached Zinc hot dipping steel plate RBC-U31PG(W)-E White (2. 5GY9. 0/0. 5) 319
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2. 5 m of branch piping connected with 0 meter height. Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616. Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound. Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
3
4-way Air Discharge Cassette Type
Engineering Data Book
2. Dimensions
MMU-AP0092H, AP0122H
15 or more
860 to 910 Ceiling open dimension
1000 or more
860 to 910 Ceiling open dimension
1000 or more
An obstacle 1000 or more
The space that is necessary for equipping and service
Standing 661 or less
15 or more
300 or less
112
44
30
172
129
77 74 105
189
Refrigerant pipe connecting port Ø6. 4 (Liquid side) Refrigerant pipe connecting port Ø9. 5 (Gas side) Bottom face of ceiling 129 77 10 5 74
Indoor unit
Bottom face of ceiling
397. 5 263 157 106. 5 72 241. 5
105
337. 5
Drain pipe connecting port (Material: PP)
Drain upstanding size
For branch duct knockout square hole Ø150 Hanging bolt M10 or Ø3/8(procured by locally)
256 132
Ø162
Electric parts box 950 Panel external dimension 780 Hanging bolt pitch 323
287. 5
416. 5 690 ± 20 Hanging bolt pitch
950 Panel external dimension
74
840 Unit external dimension
408
351
129 For branch duct 105 77
knockout square hole Ø150
80
135 105
240
105
105
384
16. 5
105 Ø162 For branch duct knockout square hole Ø150 (2 positions) For branch duct knockout square hole Ø150 269 30
207. 5
Ceiling panel (sold separately)
Bottom face of ceiling
Z
362. 5
105
372. 5
32 28 61 . 5
840 Unit external dimension
57
74
Knockout for simple OA for Ø100 Bottom face of ceiling
105
Z view
129 77
Bottom face of ceiling 5 Indoor unit
12
Bottom face of ceiling
Unit : mm
4
Standing 850 or less
Take-in port of wiring
Bottom face of ceiling
45
64
5 15 7 18
4-way Air Discharge Cassette Type
Engineering Data Book
MMU-AP0152H, AP0182H
15 or more
860 to 910 Ceiling open dimension
1000 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle 1000 or more
15 or more
The space that is necessary for equipping and service
Standing 661 or less
300 or less
Take-in port of wiring
44
Bottom face of ceiling 30
129
172
112
77 74 105
189
Indoor unit
Bottom face of ceiling
Refrigerant pipe connecting port Ø6. 4 (Liquid side) Refrigerant pipe connecting port Ø12. 7 (Gas side) Bottom face of ceiling 129 77 10 5 74
Drain upstanding size
397. 5 263 157 106. 5 72 241. 5 Electric parts box
105
337. 5
Drain pipe connecting port (Material: PP)
For branch duct knockout square hole Ø150 Hanging bolt M10 or Ø3/8 (procured locally)
256 132
Ø162
950 Panel external dimension 780 Hanging bolt pitch 323
287. 5
416. 5 690 ± 20 Hanging bolt pitch
950 Panel external dimension
74
351
840 Unit external dimension
408
129 For branch duct 105 77
knockout square hole Ø150
80
135 105
240
105
105
384
16. 5
105 Ø162 For branch duct knockout square hole Ø150 (2 positions) For branch duct knockout square hole Ø150 269 30
207. 5
Ceiling panel (sold separately)
Bottom face of ceiling
Z
57
74
28
362. 5
105
372. 5
. 5
32 61
840 Unit external dimension
105
Knockout for simple OA for Ø100
5 15 7 18
Bottom face of ceiling
129
77
Bottom face of ceiling
5
Z view
Indoor unit
12
Bottom face of ceiling
Unit : mm
5
Standing 850 or less
45
64
4-way Air Discharge Cassette Type
Engineering Data Book
MMU-AP0242H, AP0272H, AP0302H
15 or more
860 to 910 Ceiling open dimension
1000 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle 1000 or more
15 or more
The space that is necessary for equipping and service
Standing 661 or less
300 or less
Take-in port of wiring
44
Bottom face of ceiling 30
129
172
112
77 74 105
189
Indoor unit
Bottom face of ceiling
Refrigerant pipe connecting port Ø9. 5 (Liquid side) Refrigerant pipe connecting port Ø15. 9 (Gas side) Bottom face of ceiling 129 4 77 10 5 74
Drain upstanding size
397. 5 263 157 106. 5 72 241. 5 Electric parts box
105
337. 5
Drain pipe connecting port (Material: PP)
For branch duct knockout square hole Ø150 Hanging bolt M10 or Ø3/8 (procured locally)
256 132
Ø162 162
950 Panel external dimension 780 Hanging bolt pitch 323
287. 5
416. 5 690 ± 20 Hanging bolt pitch
950 Panel external dimension
74
351
840 Unit external dimension
408
129 For branch duct 105 77
knockout square hole Ø150
80
135 105
240
105
105
384
16. 5
105 Ø162 For branch duct knockout square hole Ø150 (2 positions) For branch duct knockout square hole Ø150 269 30
207. 5
Ceiling panel (sold separately)
Bottom face of ceiling
Z
57
362. 5
105
372. 5
74
32 28 61 . 5
840 Unit external dimension
105
Knockout for simple OA for Ø100
5 15 7 18
Bottom face of ceiling
129
77
Bottom face of ceiling
5
Z view
Indoor unit
12
Bottom face of ceiling
Unit : mm
6
Standing 850 or less
45
64
4-way Air Discharge Cassette Type
Engineering Data Book
MMU-AP0362H, AP0482H, AP0562H
15 or more
860 to 910 Ceiling open dimension
1000 or more
1000 or more
860 to 910 Ceiling open dimension
An obstacle 1000 or more
15 or more
The space that is necessary for equipping and service
Standing 661 or less
300 or less
Take-in port of wiring
44
30
Bottom face of ceiling
112
77 105
129 189
172
Refrigerant pipe connecting port Ø15. 9 (Gas side)
137
Refrigerant pipe connecting port Ø9. 5 (Liquid side) 157 106. 5 72 Electric parts box
Indoor unit
Bottom face of ceiling
397. 5 263 241. 5
105
337. 5
Drain pipe connecting port (Material: PP)
Drain upstanding size
For branch duct knockout square hole Ø150 Hanging bolt M10 or Ø3/8 (procured locally)
319 132
Bottom face of ceiling 129 77 10 5 137
950 Panel external dimension 780 Hanging bolt pitch 323 Ø162
240 207. 5 105 135 105 287. 5 840 Unit external dimension 408
416. 5 690 ± 20 Hanging bolt pitch
137
950 Panel external dimension
351
80
105
129 For branch duct 77 knockout square
hole Ø150
105
384
16. 5
Ceiling panel (sold separately)
105 Ø162 269 30
Bottom face of ceiling
Z
57
For branch duct knockout square hole Ø150
105
137
For branch duct knockout square hole Ø150 (2 positions)
6 28 1 . 5
840 Unit external dimension 362. 5 105 372. 5
32
Knockout for simple OA for Ø100
15 5 18 7
Bottom face of ceiling
129
77
Bottom face of ceiling
5
Z view
Indoor unit Bottom face of ceiling Unit : mm
7
Standing 850 or less
45
64
4-way Air Discharge Cassette Type
Engineering Data Book
3. Center of Gravity
Total weight Model name MMU-AP0092H MMU-AP0122H MMU-AP0152H MMU-AP0182H MMU-AP0242H MMU-AP0272H MMU-AP0302H MMU-AP0362H LRV410TT MMU-AP0562H 450 184 25 470 455 154 20 4. 0 X(mm) Y(mm) Z(mm) Main unit (kg) 18 Ceiling panel (kg)
8
4-way Air Discharge Cassette Type
Engineering Data Book
4. Electrical current characteristics
Type Model MMU-AP0092H MMU-AP0122H MMU-AP0152H MMU-AP0182H 4-Way Air 50Hz Discharge Cassette Type MMU-AP0242H MMU-AP0272H MMU-AP0302H MMU-AP0362H LRV410TT MMU-AP0562H MMU-AP0092H MMU-AP0122H MMU-AP0152H MMU-AP0182H 4-Way Air 60Hz Discharge Cassette Type MMU-AP0242H MMU-AP0272H MMU-AP0302H MMU-AP0362H LRV410TT MMU-AP0562H Nominal Voltage (V-Ph-Hz) 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 220-1-60 Voltage Range Min 198 198 198 198 198 198 198 198 198 198 198 198 198 198 198 198 198 198 198 198 Max 264 264 264 264 264 264 264 264 264 264 242 242 242 242 242 242 242 242 242 242 Fan Motor kW 0. 014 0. 014 0. 014 0. 014 0. 020 0. 020 0. 020 0. 068 0. 072 0. 072 0. 014 0. 014 0. 014 0. 014 0. 020 0. 020 0. 020 0. 068 0. 072 0. 072 FLA 0. 63 0. 63 0. 80 0. 80 0. 87 0. 87 0. 87 1. 15 1. 15 1. 15 0. 66 0. 66 0. 84 0. 84 0. 91 0. 91 0. 91 1. 21 1. 21 1. 21 Power Supply MCA 0. 79 0. 79 1. 00 1. 00 1. 09 1. 09 1. 09 1. 44 1. 44 1. 44 0. 83 0. 83 1. 05 1. 05 1. 14 1. 14 1. 14 1. 51 1. 51 1. 51 MOCP 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
9
4-way Air Discharge Cassette Type
Engineering Data Book
5. Fresh air intake by using the fresh air and filter chamber and fresh air inlet box.
Usage as the filter chamber
In case the optional filter is used, air volume may decrease. This can cause decrease temperature of cooling air flow and dew drop.
Caution
1. The fresh air shall be treated by heat reclaim ventilator or the like. Recommended treated air temperature is 12C to 30C. Be sure to decide the fresh air volume so that mixed suction air with fresh air keep operating temperature. Provide an air filter in fresh air way to prevent sucking dust. In order to accelate starting up in heating mode, implement pre-heating operation by cutting off fresh air intake.
245 Static Pressure (Pa) 195 145 95 45 -5 0 50 100 150 200 250 300 Fresh Air Volume (m³/h) 350 400
Booster fan P1 P
(Atmospheric)
Fresh Air Chamber
Static Pressure = P (atmospheric) - P1
Characteristics between air volume of branching duct and static pressure
Up to 20% fresh air intake ratio is available by using the booster fan. fresh air intake ratio = ( fresh air volume ) / ( total air volume ) X 100 %
Inter - lock circuit
1. [. . . ] In order to accelate starting up in heating mode, implement pre-heating operation by cutting off fresh air intake.
245 Static Pressure (Pa) 195 145 95 45 -5 0 50 100 150 200 250 300 Fresh Air Volume (m³/h) 350 400
Booster fan P1 P
(Atmospheric)
Fresh Air Chamber
Static Pressure = P (atmospheric) - P1
Characteristics between air volume of branching duct and static pressure
Up to 20% fresh air intake ratio is available by using the booster fan. fresh air intake ratio = ( fresh air volume ) / ( total air volume ) X 100 %
Inter - lock circuit
1. Connect the driving relay of the duct fan ( DC 12 V ) between 1 and 6 on the indoor P. C. board. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE LG LRV410TT
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual LG LRV410TT will begin.