User manual LIFT-MASTER LM90 MODEL B2

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual LIFT-MASTER LM90 MODEL B2. We hope that this LIFT-MASTER LM90 MODEL B2 user guide will be useful to you.

Lastmanuals help download the user guide LIFT-MASTER LM90 MODEL B2.


Mode d'emploi LIFT-MASTER LM90 MODEL B2
Download
Manual abstract: user guide LIFT-MASTER LM90 MODEL B2

Detailed instructions for use are in the User's Guide.

[. . . ] LISTED GENERAL DESCRIPTION CANADIAN LISTED CSFM: 7300-1418:100 S/N:________________ The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and center parting level and inclined track doors. All models are normally energized Fail-Safe Releasing Devices incorporating an internal 72 hour battery pack and state of the art electronic control circuitry. The Release Devices respond to emergency conditions generated by manual or automatic normally closed initiating devices and shall be used in conjunction with a temperature fuse link system. The Release Device features include separate adjustable time delays for alarm and power loss, up to 72 hours battery support for release and smoke detectors, motor voltage sensing, form-C relay outputs, proximity/down limit detection, annunciator outputs with voice module options and trouble diagnostic capabilities. [. . . ] Connect wiring from N/O electrical loop (switch open when door is up) to TB1 screws 1 & 16 or N/O electrical loop (switch closed with door up) to TB1-1 & 18. * Note: Electrical loop must be provided as dry contacts and may not be used in conjunction with the simultaneous switching of a motor control or any other voltage through the same contacts. Connections of this type will result in immediate damage to the release device. Annunciator - (+12VDC output) connect annunciator (option) observing polarity to TB1-6 (-) & 7 (+). If voice option is included see LM21-VAS, Installation Manual. Do Not connect a speaker to this output. Relay outputs - Two separate SPDT dry contact relay outputs are provided for switching of devices external to the release device. A non-delayed output (relay toggles on alarm- beginning of time delay) is provided on TB110, 11 &12 and a delayed relay output (relay toggles after time delay) is provided on TB1-14, 15 &17. See Figure 2 for contact status and ratings. Note: Battery should "not" be connected until testing of unit is being performed! TESTING OF RELEASE DEVICE/CONTROL PANEL SHALL BE PERFORMED AND WITNESSED FOR NORMAL OPERATION AFTER INSTALLATION. REFER TO TEST PROCEDURES CONTAINED HEREIN, AS WELL AS ANY OTHER TESTING PROGRAMS RECOMMENDED BY DOOR MANUFACTURER. "LM90"SERIES MODEL B2 RELEASE DEVICE ELECTRICAL & MECHANICAL SPECIFICATIONS OPERATING VOLTAGES MODEL LM90-B2-24DC . . . . . . . . . . . . . 24VAC +/- 10% LM90-B2-120AC . . . . . . . . . . . . . 120VAC +/- 10% CURRENT REQUIREMENTS MODEL LM90-B2-24DC . . . . . . SUPERVISORY (non-alarm) . 100A / ALARM . 500A MAX LM90-B2-24AC . . . . . . SUPERVISORY (non-alarm) . 100A / ALARM . 500A MAX LM90-B2-120AC . . . . . . SUPERVISORY (non-alarm) . 100A / ALARM . 500A MAX * NOTE: Initial power up inrush current shall not exceed 3 times rated current on any model. MOTOR CONTROL SENSE - ALL MODELS Input Voltage: 24V AC/dc typical +15% / -10% Input Current: Not to exceed . 004A INITIATING/DOOR INPUTS CAUTION: All initiating devices shall be dry contact type only Maximum loop resistance: 100 Ohms Maximum current: Not to exceed . 002A Maximum voltage: 15VDC FORM C OUTPUT (MAXIMUM CONTACT RATING) 2A/30VDC 60 Watt DC Resistive Load Only AUXILIARY POWER: 12VDC @ . 250A FUSES All fuses 1A @250V, 2AG Fast Acting Type MECHANICAL SPECIFICATIONS LOAD RATING Support and Release : 40 LB. MAXIMUM PHYSICAL DIMENSIONS 9. 125" x 9. 125" x 4. 750" (H x W x D) 5 LM90-B2 ELECTRICAL CONNECTIONS NOTE: WHEN INSTALLING LM90-B2 MASTER AND REMOTE DEVICES, REFER TO FIGURE 3A ON PAGE 8, FOR WIRING INSTRUCTIONS. (2) End of Line Relay As per U. L. 864 (+) (-) CONTROL BOARD TB1 (+) (-) Do Not loop wires under terminals. Break wire run to provide system supervision. 1 2 3 Smoke detector 4 (2) (4) (5) 5 6 7 8 9 10 11 12 13 14 15 Use TB1-1 DOWN LIMIT N/O 16 for or 17 common DOWN LIMIT N/C 18 (1) FIGURE 2 (4) (+)12VDC (1) Trouble relay non-delayed 2A @ 30VDC Delayed relay 1A @ 30VDC { TB2- AUX. [. . . ] Service and/or installation by unauthorized personnel shall void warranty. Review the following guide prior to requesting technical support. If technical support is required, unit serial number (found on front of manual and inside unit), as well as distributor who supplied unit must be supplied. SYMPTOM 1. Red Power LED does not light. POSSIBLE TROUBLE A) Primary power source turned off. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE LIFT-MASTER LM90 MODEL B2

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets...
In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.

Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual LIFT-MASTER LM90 MODEL B2 will begin.

Search for a user manual

 

Copyright © 2015 - LastManuals - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.

flag