[. . . ] All hardware, fusible links and chain or cable shall be furnished by door manufacturer or installing company and shall be approved or recognized as required for use with this product. MOUNTING PROCEDURE (Figures 1 & 1A) 1. The release device shall be mounted on a vertical surface with chain end link exiting side of enclosure as illustrated in figure 1 (horizontal pull) or 1A (vertical pull). Release device enclosure shall be mounted with minimum #10 size fastening screws or bolts for securing to structures other than masonry. [. . . ] 2) Connect red (+) wire from LM90-RR-12 to wiring from TB1-15 and black wire to wiring from TB2-1. Review Figure 3A for additional wiring required inside of master unit. Close cover and secure screw-on lid after all connections are made. DO NOT LEAVE COVER OPEN AFTER CONNECTIONS ARE MADE!
2
LM90-RR LM90-RRD Horizontal pull
FIGURE 1
FIGURES 1 AND 1A DEPICT MOUNTING OPTIONS FOR REMOTE RELEASE AND ARE NOT PROVIDED AS GUIDELINES FOR THE INSTALLATION OF THE DOOR OR ASSOCIATED HARDWARE. SEE DOOR MANUFACTURERS RECOMMENDATIONS AND NFPA 80 FOR USE OF THIS PRODUCT, FUSIBLE LINKS AND ASSOCIATED HARDWARE USED WITH SPECIFIC DOOR. ACTUAL CONFIGURATION MAY VARY SIGNIFICANTLY FROM ILLUSTRATIONS PROVIDED.
FIGURE 1A LM90-RR LM90-RRD Vertical pull
3
LM90-RR INSIDE VIEW (Cover removed)
FIGURE 2
Reset Knob
Power LED
Manual Test Button
FIGURE 3 - ELECTRICAL WIRING
(+) (2) Initiating Device (Smoke detector, etc. )
(1) Input power
(-) LM90-RR (REMOTE RELEASE) LM90-RRD (DELAY OPTION) (+) (-) Chassis ground
RED
BLACK
(1) Verify input voltage to model being used. (2) See NFPA 80 and NFPA 72 for proper placement.
Installation of all wiring and related connecting hardware must be performed in accordance with the latest NFPA, UL, and NEC standards and codes. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material type, wiring gauge related to power capacity requirements and circuit length and wiring methods.
4
FIGURE 3A - ELECTRICAL WIRING : TIME DELAY DAISY CHAIN CONFIGURATION
SMOKE DETECTOR OR ALARM PANEL NORMALLY CLOSED DRY CONTACT LOOP
(5) LM90-B2 Master 1 TB-1 1 2 3
(2)
(+) (-)
RED BLACK
LM90-RR #3
(+) (-) 14 15 18 1 2 TB-2 (-) (4) (+) (-)
RED BLACK
LM90-RR #2
RED BLACK
LM90-RR #1
(1)
18 (3) (+)
Refer to page 1, Section C for wiring descriptions.
Wiring of the remote releases in a Daisy Chain configuration to a master unit provides time delayed release with simultaneous closure on all doors. A maximum of three (3) units may be daisy chained from the master unit. (1) Verify model being used as LM90-RR-12. (2) See NFPA 80 and NFPA 72 for proper placement. Electrical supervision of detector shall be provided as per U. L. 864 (3) Install jumper between TB2-2 and TB1-14 of master unit. (4) Wiring between units is parallel connected. (5) Illustration does not depict entire master unit. See installation manual of master unit for additional information.
Installation of all wiring and related connecting hardware must be performed in accordance with the latest NFPA, UL, and NEC standards and codes. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material type, wiring gauge related to power capacity requirements and circuit length and wiring methods.
5
"LM90" SERIES RELEASE DEVICE ELECTRICALAND MECHANICAL CHARACTERISTICS ELECTRICALRATINGS MODEL (D- delay option) VOLTAGE LM90-RR-12 / LM90-RRD-12 12VDC LM90-RR-24 / LM90-RRD-24 24VDC MECHANICAL- LOAD RATING Support and release: 40LB. 15. 0 28. 0 CURRENT . 050A . 050A
DIMENSIONS 6" x 4 " x 3 1/8" (H x W x D)
SECTION D. TEST PROCEDURES TO BE PERFORMED BY FACTORYAUTHORIZED PERSONNELONLY!REGULAR TESTING OFALLRELEASE DEVICE EQUIPMENT IS RECOMMENDED. TESTING SHALL BE WITNESSED FOR PROPER OPERATION.
Testing does not affect normal operation of alarm system when connected to release device. Testing and normal operation can only be accomplished with power applied to unit. [. . . ] After servicing equipment as required, unit shall be tested and witnessed for proper operation as described in SECTION D- TEST PROCEDURES, contained herein.
6
LM90-RR & LM90-RRD TROUBLESHOOTING GUIDE
Verify that desired options are available on unit before troubleshooting. Refer to electrical connection information and wiring diagrams of this manual. Troubleshooting shall be performed by factory authorized personnel only. Service and/or installation by unauthorized personnel shall void warranty. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE LIFT-MASTER LM90-RR
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.