POWER VENT GAS WATER HEATER USER'S GUIDE
FOR POTABLE WATER HEATING ONLY NOT SUITABLE FOR SPACE HEATING NOT FOR USE IN MANUFACTURED (MOBILE) HOMES
Model Numbers
HRN11240P HRN31240P HRP11240P HRP31240P HRN11250P HRN31250P HRP11250P HRP31250P HRN11275P HRN31275P HRP11275P HRP31275P
For Your Safety
AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER.
PRINTED IN THE U. S. A. 0505
www. maytagwaterheaters. com 1
PART NO. 66001897 184683-001
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. [. . . ] One 90o elbow equals 5 feet of equivalent vent length.
CEMENTING PVC, ABS OR CPVC PIPE AND FITTINGS Read and observe all safety information printed on primer, cleaner and cement containers. 90o F TO 150o F 50o F TO 90o F 0o F TO 50o F
CUTTING OPENING THROUGH AN OUTSIDE WALL AND COLLAR INSTALLATION After reading the manual and you have determined the location of the opening in the wall, (using the drawing below), cut a 2 1/2" hole for 2" vent piping, 3 1/2" hole for 3" vent piping or a 4 1/2" hole for 4" vent piping through an exterior wall. NOTE: When determining location of the opening in the outside wall allow for the 1/8" rise per five feet that has taken place in the horizontal run.
23
FIGURE 44.
· If there is to be a vertical run of vent from blower, the 3" PVC, ABS or CPVC pipe must be attached to the blower using 3 sheet metal screws.
FIGURE 42.
The 3" )or optional 2" or 4") PVC, ABS or CPVC Schedule 40 vent pipe can be run from the water heater through the wall or from the wall to the water heater, whichever is most convenient. The vent pipe must extend a minimum of 1 1/2" through the exterior wall. Extending the vent cap as far as possible from the surface of the exterior wall will help minimize discoloration of the wall in this area which may be caused by the flue gases. NOTE: that the inside collar must be slipped over the vent piping before locating the pipe through the wall. Before securing the inside and outside collars to the wall, use a silicone sealer between pipe and opening to insure a water and air tight seal.
INSTALLATION SHOWING USE OF PVC, ABS OR CPVC PIPE
FIGURE 45.
· If the optional 2" vent piping is to be used (40, 000 BTU/HR. models only), the 2" street elbow, 3" to 2" reducer and 3" (minimum) section of 3" PVC, ABS or CPVC pipe must be supplied locally. The 3" (minimum) section of 3" PVC, ABS or CPVC pipe must be attached to the blower using 3 sheet metal screws, · If the optional 4" vent piping is to be used (70, 000 BTU/HR. and higher models only), the 4" street elbow, 4" to 3" reducer and 3" minimum section of 3" PVC, ABS or CPVC pipe must be supplied locally. The 3" (minimum) section of 3" PVC, ABS or CPVC pipe must be attached to the blower using 3 sheet metal screws. VENTING THROUGH A ROOF - ALL MODELS 3" PVC, ABS or CPVC Schedule 40 vent piping: · A 3" PVC Schedule 40 - 45o vent cap with wire screen is supplied with the water heater. · 3" PVC, ABS or CPVC Schedule 40 piping and fittings are acceptable materials for the vent system on all models and must be supplied locally. 75 GALLON 70, 000 AND 75, 000 BTU/HR MODELS ONLY OPTIONAL 4" VENT PIPING · A wiring screen to fit a 4" PVC, ABS or CPVC Schedule 40 - 45o vent cap is supplied with the water heater. · A 3" PVC, ABS or CPVC Schedule 40 pipe, minimum length of 3" (must be supplied locally), to make vent connection at the blower outlet. · A 4" to 3" PVC, ABS or CPVC Schedule 40 reducer (must be supplied locally).
24
FIGURE 43.
CONNECTING PVC, ABS OR CPVC PIPE VENT TO BLOWER · If making an immediate horizontal run of vent off the blower, a 3" PVC, ABS or CPVC Schedule 40 (supplied locally) elbow is required. Place the elbow in the required direction on the blower and using 3 sheet metal screws, attach the elbow.
· 4" and 3" PVC, ABS or CPVC Schedule 40 piping and fittings are acceptable materials for vent system on all 75 gallon 70, 000 and 75, 000 BTU/HR models and must be supplied locally.
FIGURE 46.
ALL 40 AND 50 GALLON 40, 000 BTU/HR MODELS OPTIONAL 2" VENT PIPING 2" PVC, ABS or CPVC Schedule 40 vent piping: · A wire screen to fit 2" PVC, ABS or CPVC Schedule 40 - 45o vent cap is supplied with the water heater. · A 3" PVC, ABS or CPVC Schedule 40 pipe, minimum length of 3" (must be supplied locally), to make vent connection at the blower outlet. · A 3" to 2" PVC, ABS or CPVC Schedule 40 reducer (must be supplied locally). · 2" and 3" PVC, ABS or CPVC Schedule 40 piping and fittings are acceptable materials for the vent system on all 40 and 50 gallon 40, 000 BTU/HR models and must be supplied locally.
FIGURE 48.
· The total vertical and horizontal vent runs cannot exceed the maximum length with the number of 90o elbows as specified in the tables to follow. If more elbows are required, the venting distance must be reduced 5 feet for every 90o elbow. 75 GALLON 70, 000 AND 75, 000 BTU/HR MODELS ONLY 3" DIA. [. . . ] Now that you have purchased this gas water heater, should a need ever exist for repair parts or service, simply call Maytag Customer Service at 1-800-788-8899 for an authorized servicer. Be sure to provide all pertinent facts when you call or visit. THIS IS A REPAIR PARTS LIST, NOT A PACKING LIST. The model number of this gas water heater will be found on the model rating plate located near the gas control valve.
42
When ordering repair parts, always give the following information: · · · · Model number Serial Number Part Description Part Number
REPAIR PARTS LIST
MAYTAG GAS WATER HEATERS
MODEL NO'S
HRN11275P HRN31275P HRP11275P HRP31275P 75 75 75 75 Gallon Natural Gas Gallon Natural Gas Gallon Propane Gas (L. P. ) Gallon Propane Gas (L. P. )
PCV, ABS OR CPVC ITEMS FOR ALL MODELS SUPPLIED LOCALLY
Key
No. [. . . ]