If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual MGE PULSAR EVOLUTION 3000 XL. We hope that this MGE PULSAR EVOLUTION 3000 XL user guide will be useful to you.
Lastmanuals help download the user guide MGE PULSAR EVOLUTION 3000 XL.
Manual abstract: user guide MGE PULSAR EVOLUTION 3000 XL
Detailed instructions for use are in the User's Guide.
[. . . ] www. mgeups. com
Pulsar Evolution
2200/3000/3000 XL
Installation and user manual
MGE UPS Systems
1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636 For service call 1-800-438-7373 www. mgeups. com
IMPORTANT SAFETY INSTRUCTIONS
Read before installing product
SAVE THESE INSTRUCTIONS. This manual contains important instructions for 89347, 89348, and 89349 that should be followed during installation and maintenance of the UPS and batteries. Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment. The Pulsar Evolution range has been designed with the utmost care. [. . . ] If the UPS is connected to a computer running MGE communications software, it is possible to program the interruption of power to the programmable receptacles 9 during operation on battery power, thus reserving backup power for the priority loads. 3 - Lock the connections using the securing system 29 . As soon as the UPS is energized, the battery begins charging. Eight hours are required to charge to the full rated backup time.
25 10
3400723100/AD
- Page 13
2. Installation
2. 5 Connection to the RS232 or USB communications port (optional)
CAUTION: The RS232 and USB communications ports cannot operate simultaneously. 26 1 - Connect the RS232 26 or USB 27 communications cable to the serial port or the USB port on the computer. 27
RS232
2
344-50297-00
1
2 - Connect the other end of the communications cable 26 or 27 to the RS232 2 or USB 1 communications port on the UPS. The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software.
2. 6 Connection to the data-line protection port (optional)
The data-line protection function on the UPS eliminates overvoltage flowing on the computer-network lines. Simply connect the line to be protected to the UPS using the data-line protection connectors (IN and OUT) as indicated opposite (RJ45 cables not supplied).
Data line protection
RS232 TO BATTERY CABINET
TO BATTERY CABINET
SITE WIRING FAULT
Data line protection
Pb
WARNING
3 battery cabinets max for 3000 12 battery cabinets max for 3000XL
Only for 3000
72Vdc, 9Ah
OUT
IN
344-50297-00
SITE WIRING FAULT
Pb
WARNING
3 battery cabinets max for 3000 12 battery cabinets max for 3000XL
Only for 3000
72Vdc, 9Ah
OUT
IN
U. S. 6, 094, 363
BATTERY CONNECTOR Volt: 72Vdc 40A
Page 14 -
3400723100/AD
2. Installation
2. 7 Installation of the communications-card option
1 - Remove the slot cover 5 secured by two screws. 2 - Insert the card in the slot.
RS232
TO BATTERY CABINET
5
344-50297-00
3 - Secure the cover with the two screws. It is not necessary to shut down the UPS to install the communications card.
Slot for the communications-card option.
Data line protection
SITE WIRING FAULT
Pb
WARNING
3 battery cabinets max for 3000 12 battery cabinets max for 3000XL
Only for 3000
72Vdc, 9Ah
OUT
IN
3400723100/AD
- Page 15
3. Operation
3. 1 Start-up
Press the ON / OFF button 15 . The buzzer beeps and all the LEDs come ON. The buzzer beeps twice during the self-test, then button 15 remains ON, indicating that the receptacles are supplied with power. - AC power is present: Only button 15 is ON. The protected equipment is supplied by the AC-power source. - AC power is absent: Button 15 and LED 16 are ON. The protected equipment is supplied by the UPS, operating on battery power. All the connected equipment is supplied with power.
15 16 17
1 2
%
%
1
2
%
%
Page 16 -
3400723100/AD
3. Operation
3. 3 Operation on battery power (following failure of AC-input power)
Transfer to battery power
The AC-input power is out of tolerances, LED 16 goes ON. [. . . ] Appendices
Technical characteristics
Pulsar Evolution 2200 Output rating AC-input power Voltage Frequency Output power (operation on battery power) Voltage Frequency Battery 1920 VA / 1540 W (1) Pulsar Evolution 3000 2880 VA / 2000 W Pulsar Evolution 3000 XL 2568 VA / 2000 W
Single phase, 80 V to 153 V (1) 47 Hz to 70 Hz (50 Hz system) or 56. 5 Hz to 70 Hz (2) (60 Hz system)
Single-phase, 120 V (3) (+ 6% / - 10%) 50/60 Hz +/- 1 Hz 6 x 12 V, 7 Ah, sealed leadacid, maintenance free 6 x 12 V, 9 Ah, sealed lead-acid, maintenance free external
Environment Noise level (operation on AC-input power) Operating temperature Relative humidity
<40 dBA 0 to 40° C 20 to 90% (without condensation)
(1) The upper and lower thresholds may be set using the UPS Driver software. (2) Or 40 Hz in low-sensitivity mode (may be set using the UPS Driver software). (3) Adjustable from 100 to 127 V using the UPS Driver software.
3400723100/AD
- Page 25
6. Appendices
Examples of battery backup times
Pulsar Evolution 2200
1 data server + 1 hard disk 2 distributed servers + 1 hub 8 rack-mounted servers
0
5
10
15
20
25
30 t (min)
Pulsar Evolution 3000
1 data server + 1 hard disk 4 distributed servers + 1 hub + 1 router 12 rack-mounted servers
0
5
10
15
20
25
30
35
t (min)
Pulsar Evolution 3000 XL + 3 EXB
1 telecom device 1 set of telecom devices 1 large set of telecom devices 0 Page 26 3400723100/AD
100
200
300
400
500
t (min)
6. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE MGE PULSAR EVOLUTION 3000 XL
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.