User manual MGE PULSAR EVOLUTION 3000 XL

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual MGE PULSAR EVOLUTION 3000 XL. We hope that this MGE PULSAR EVOLUTION 3000 XL user guide will be useful to you.

Lastmanuals help download the user guide MGE PULSAR EVOLUTION 3000 XL.


Mode d'emploi MGE PULSAR EVOLUTION 3000 XL
Download
Manual abstract: user guide MGE PULSAR EVOLUTION 3000 XL

Detailed instructions for use are in the User's Guide.

[. . . ] www. mgeups. com Pulsar Evolution 2200/3000/3000 XL Installation and user manual MGE UPS Systems 1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636 For service call 1-800-438-7373 www. mgeups. com IMPORTANT SAFETY INSTRUCTIONS Read before installing product SAVE THESE INSTRUCTIONS. This manual contains important instructions for 89347, 89348, and 89349 that should be followed during installation and maintenance of the UPS and batteries. Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment. The Pulsar Evolution range has been designed with the utmost care. [. . . ] If the UPS is connected to a computer running MGE communications software, it is possible to program the interruption of power to the programmable receptacles 9 during operation on battery power, thus reserving backup power for the priority loads. 3 - Lock the connections using the securing system 29 . As soon as the UPS is energized, the battery begins charging. Eight hours are required to charge to the full rated backup time. 25 10 3400723100/AD - Page 13 2. Installation 2. 5 Connection to the RS232 or USB communications port (optional) CAUTION: The RS232 and USB communications ports cannot operate simultaneously. 26 1 - Connect the RS232 26 or USB 27 communications cable to the serial port or the USB port on the computer. 27 RS232 2 344-50297-00 1 2 - Connect the other end of the communications cable 26 or 27 to the RS232 2 or USB 1 communications port on the UPS. The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software. 2. 6 Connection to the data-line protection port (optional) The data-line protection function on the UPS eliminates overvoltage flowing on the computer-network lines. Simply connect the line to be protected to the UPS using the data-line protection connectors (IN and OUT) as indicated opposite (RJ45 cables not supplied). Data line protection RS232 TO BATTERY CABINET TO BATTERY CABINET SITE WIRING FAULT Data line protection Pb WARNING 3 battery cabinets max for 3000 12 battery cabinets max for 3000XL Only for 3000 72Vdc, 9Ah OUT IN 344-50297-00 SITE WIRING FAULT Pb WARNING 3 battery cabinets max for 3000 12 battery cabinets max for 3000XL Only for 3000 72Vdc, 9Ah OUT IN U. S. 6, 094, 363 BATTERY CONNECTOR Volt: 72Vdc 40A Page 14 - 3400723100/AD 2. Installation 2. 7 Installation of the communications-card option 1 - Remove the slot cover 5 secured by two screws. 2 - Insert the card in the slot. RS232 TO BATTERY CABINET 5 344-50297-00 3 - Secure the cover with the two screws. It is not necessary to shut down the UPS to install the communications card. Slot for the communications-card option. Data line protection SITE WIRING FAULT Pb WARNING 3 battery cabinets max for 3000 12 battery cabinets max for 3000XL Only for 3000 72Vdc, 9Ah OUT IN 3400723100/AD - Page 15 3. Operation 3. 1 Start-up Press the ON / OFF button 15 . The buzzer beeps and all the LEDs come ON. The buzzer beeps twice during the self-test, then button 15 remains ON, indicating that the receptacles are supplied with power. - AC power is present: Only button 15 is ON. The protected equipment is supplied by the AC-power source. - AC power is absent: Button 15 and LED 16 are ON. The protected equipment is supplied by the UPS, operating on battery power. All the connected equipment is supplied with power. 15 16 17 1 2 % % 1 2 % % Page 16 - 3400723100/AD 3. Operation 3. 3 Operation on battery power (following failure of AC-input power) Transfer to battery power The AC-input power is out of tolerances, LED 16 goes ON. [. . . ] Appendices Technical characteristics Pulsar Evolution 2200 Output rating AC-input power Voltage Frequency Output power (operation on battery power) Voltage Frequency Battery 1920 VA / 1540 W (1) Pulsar Evolution 3000 2880 VA / 2000 W Pulsar Evolution 3000 XL 2568 VA / 2000 W Single phase, 80 V to 153 V (1) 47 Hz to 70 Hz (50 Hz system) or 56. 5 Hz to 70 Hz (2) (60 Hz system) Single-phase, 120 V (3) (+ 6% / - 10%) 50/60 Hz +/- 1 Hz 6 x 12 V, 7 Ah, sealed leadacid, maintenance free 6 x 12 V, 9 Ah, sealed lead-acid, maintenance free external Environment Noise level (operation on AC-input power) Operating temperature Relative humidity <40 dBA 0 to 40° C 20 to 90% (without condensation) (1) The upper and lower thresholds may be set using the UPS Driver software. (2) Or 40 Hz in low-sensitivity mode (may be set using the UPS Driver software). (3) Adjustable from 100 to 127 V using the UPS Driver software. 3400723100/AD - Page 25 6. Appendices Examples of battery backup times Pulsar Evolution 2200 1 data server + 1 hard disk 2 distributed servers + 1 hub 8 rack-mounted servers 0 5 10 15 20 25 30 t (min) Pulsar Evolution 3000 1 data server + 1 hard disk 4 distributed servers + 1 hub + 1 router 12 rack-mounted servers 0 5 10 15 20 25 30 35 t (min) Pulsar Evolution 3000 XL + 3 EXB 1 telecom device 1 set of telecom devices 1 large set of telecom devices 0 Page 26 3400723100/AD 100 200 300 400 500 t (min) 6. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE MGE PULSAR EVOLUTION 3000 XL

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets...
In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.

Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual MGE PULSAR EVOLUTION 3000 XL will begin.

Search for a user manual

 

Copyright © 2015 - LastManuals - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.

flag