If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual MITSUBISHI PAC-YG31CDA. We hope that this MITSUBISHI PAC-YG31CDA user guide will be useful to you.
Lastmanuals help download the user guide MITSUBISHI PAC-YG31CDA.
Manual abstract: user guide MITSUBISHI PAC-YG31CDACONNECTION SPECIFICATIONS
Detailed instructions for use are in the User's Guide.
[. . . ] BACnet Connection Specifications
BACnet Interface ( PAC-YG31CDA)
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC CORPORATION
AIR-CONDITIONING & REFRIGERATION SYSTEM WORKS
WSN04-2507
1. [. . . ] It is always used as operation for 24 hours.
OS Other
1/8 WSN04-2507
3. Communication Protocol Specification 3. 1 Protocol Outline
BACnet/IP which applied to ANSI/ASHRAE 135-1995, 135a, 135b correspondingly on UDP/IP of Ethernet is used.
Ether Header
IP Header
UDP Header BVLL Header NPCIof BACnetNETWORK APDU of BACnet
3. 2 Ether Header
A physical layer sets a transmission medium to 10 BASET by Ethernet.
3. 3 IP Header
The private address of Class C is recommended (*1). Subnet mask 255. 255. 255. 0 *1: Recommendation value (range) [192. 168. 1. 1][192. 168. 254. 254] [192. 168. 0. 0] and [192. 168. 255. 255] do not use it.
3. 4 UDP Header
The default UDP port of a unicast and broadcasting is set to 47808 (OxBAC0).
3. 5 BVLL Header
BVLC type (one octet) BVLC function (one octet) 0x81 fixation (BVLL to BACnet/IP) 0x0A At the time of a unicast 0x0B At the time of broadcasting BVLC length (two octets) Arbitrary (wording-of-a-telegram length setup: a big endian specification)
3. 6 NPCI of BACnetNETWORK Version (one octet) Control (one octet)
0x01 Fixation 0x04 Those with a response message 0x00 With no response message
3. 7 APDU of BACnet
It has arbitrary lengths of 1024 or less octets. Contents details are ANSI/ASHRAE135-1995, 135a, 135b references.
3. 8 Application of BACnet
The instance number of a Device object 3(Setting change of a instance number is possible) Segmentation APDU which can be received APDU timeout Vender ID Process ID Transmission and reception are un-supported. 1024 octet 3sec(Setting change of a instance number is possible) 99 blank (Setting change of a process ID is possible)
2/8 WSN04-2507
4 Object Type and Service 4. 1 Object List
The list of the objects to be used is shown below.
Object type
Support ¡: Support ×: Un-supporting
Note
Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Loop Multi-state Input Multi-state Output Multi-state Value Notification Class Program Schedule Averaging Trend Log
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 19 15 16 17 18 20
¡ × ¡ ¡ ¡ ¡ × × ¡ × × × × ¡ ¡ × ¡ × × × ×
3/8 WSN04-2507
4. 2 Object and Management Item
Object ID consists of object type + instance number. An instance number consists of G-50A number + air-conditioner equipment group number + member number.
31 22 21 0(bit)
BACnet object type
Instance number
Instance number (decimal and 6 figures):
X X XX XX Member number (01 ~ 99) Group number (01 ~ 50) G-50A number (01 ~ 10)
Note: G-50A number: Specify the IP address of G-50A corresponding to G-50A number 1-10, and determine G-50A number.
Object
Object type
Instance number
Management item
Note
On/Off (setup) On/Off (state) Alarm signal Error Code
Binary Output Binary Input Binary Input Multi-State Input
xxxx01 xxxx02 xxxx03 xxxx04
Inactive: Off Active: On Inactive: Off Active: On Inactive: Normal Active: Abnormal 01: normal 02: other 03: refrigerator abnormal 04: water system abnormal 05: air system abnormal 06: electric system abnormal 07: sensor trouble 08: communication error 09: system abnormal 01: Cool 02: Heat 03: Fan 04: Auto 05: Dry *1) 01: Cool 02: Heat 03: Fan 05: Dry *1) 01: Low 02: High 03: Mid2 *2) 04: Mid1 *2) 01: Low 02: High 03: Mid2 *2) 04: Mid1 *2) °F / °C °F / °C Inactive: OFF Active: ON Inactive: RESET ACTIVE: Void Inactive: Permit Active: Prohibit If it read, the same state, as a Filter Signal will return.
Operation mode (setup)
Multi-State Output
xxxx05
*4)
Operation mode (state)
Multi-State Input
xxxx06
*4)
Fan Speed (setup)
Multi-State Output
xxxx07
Low<Mid2<Mid1<High
Fan Speed (state)
Multi-State Input
xxxx08
Low<Mid2<Mid1<High
Room Temp. Filter Signal Filter Signal Reset Prohibition of local operation (On/Off) Prohibition of local operation (Mode) Prohibition of local operation (filter reset)
Analog Input Analog Value Binary Input Binary Value Binary Value
xxxx09 xxxx10 xxxx11 xxxx12 xxxx13
*3) *3)
Binary Value
xxxx14
Inactive: Permit Active: Prohibit
*3)
Binary Value
xxxx15
Inactive: Permit Active: Prohibit
4/8 WSN04-2507
Object
Object type
Instance number
Management item
Note
Prohibition of local operation (Set Temp. ) Communication State System Forced Off Air direction (setup)
Binary Value
xxxx16
Inactive: Permit Active: Prohibit
*3)
Binary Input Binary Value Multi-State Output
xxxx20 xx9921 xxxx22
Inactive: Normal Active: Abnormal Inactive: Released Active: Effective 01: Horizontal 02: Down 60% 03: Down 80% 04: Down100% 05: Swing 01: Horizontal 02: Down 60% 03: Down 80% 04: Down100% 05: Swing *3)
Air direction (state)
Multi-State Input
xxxx23
*3)
Notification Class Device
Notification Class Device
000003 000003
Setting change of an instance number is possible. Setting change of an instance number is possible.
*1) It can use, if dry operation use is set up. [. . . ] EXEC : BACnet IF receives.
Multi-State Output
Notification Class
Multi-State Value
Multi-State Input
Analog Output
Binary Output
Analog Value
Analog Input
Binary Value
Binary Input
Device
Note
Time Synchronization I-Am
INIT EXEC INIT EXEC
¡ ¡
Who-Is
INIT EXEC
¡ ¡
I-Have
INIT EXEC
Who-Has Confirmed COV Notification Confirmed Event Notification Unconfirmed COV Notification Unconfirmed Event Notification Read Property Read Property Multiple Write Property Write Property Multiple Add List Element Remove List Element
INIT EXEC INIT EXEC INIT EXEC INIT EXEC INIT EXEC INIT EXEC INIT EXEC INIT EXEC INIT EXEC INIT EXEC INIT EXEC
¡
¡ ¡
¡ ¡ ¡ ¡
¡ ¡
¡ ¡ ¡ ¡
¡ ¡ ¡ ¡
¡ ¡
¡ ¡ ¡ ¡ ¡ ¡
¡ : Standard support : Setting change is possible.
7/8 WSN04-2507
4. 5 The property list for every object
46 off off normal refrigerator 9 abnormal 5 4 4 4 Low High Mid2 Mid1 Low High Mid2 Mid1 Cool Heat Fan Dry Cool Heat Fan Auto Dry abnormal abnormal abnormal trouble error normal other abnormal water system air system electric system sensor communication abnormal normal system on normal on normal 4 84 43 42 74 110-1 110-2 110-3 110-4 110-5 110-6 110-7 110-8 110-9 110-10 17
75
77
79
-1
117
65
69
72 45 59
OnOffSetup xxxx
4 xxxx01
0
OnOffState xxxx
3 xxxx02
0
AlarmSignal xxxx
3 xxxx03
0
ErrorCode_xxxx
13 xxxx04
0
OperationModeSetup xxxx
14 xxxx05
0
OperationModeState xxxx
13 xxxx06
0
FanSpeedSetup xxxx
14 xxxx07
0
FanSpeedState xxxx
13 xxxx08
0
RoomTemp_xxxx
64 0 xxxx09 / 62
198 / 92
-144 / -98
0
SetTemp_xxxx off reset permit permit permit permit normal Released 5 5 Horizontal Down60% Horizontal Down60% Down80% Down80% Effective normal Down100% Down100% Swing Swing abnormal prohibit prohibit prohibit prohibit on normal
64 2 xxxx10 / 62
0
FilterSign xxxx
3 xxxx11
0
FilterSignReset xxxx
5 xxxx12
0
ProhibitionOnOff xxxx
5 xxxx13
0
ProhibitionMode xxxx
5 xxxx14
0
ProhibitionFilterSignReset xxxx
5 xxxx15
0
ProhibitionSetTemp xxxx
5 xxxx16
0
CommunicationState xxxx
3 xxxx20
0
SystemForcedOff xx
5 xx9921
0
AirDirectionSetup xxxx
14 xxxx22
0
AirDirectionState xxxx
13 xxxx23
0
Notification Class
15 000003
Device 10 11 12 13 14 15 16 17 18
8 000003 19 20 21 22 23 24 25 26 27
1
2
3
4
5
6
7
8
9
File Size
File Type
Polarity
Low Limit
Active Text
High Limit
State Text 1
State Text 2
State Text 3
State Text 4
State Text 5
State Text 6
State Text 7
State Text 8
State Text 9
Notify Type
Units
Inactive Text
Object Type
Object Name
Notification Class
Number of States
Min Present Value (°F / °C)
Max Present Value (°F / °C)
Instance Number
Object Identifier
8/8 WSN04-2507 [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE MITSUBISHI PAC-YG31CDA
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.