If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual NOVA CONTROLS NEPTUNE. We hope that this NOVA CONTROLS NEPTUNE user guide will be useful to you.
Lastmanuals help download the user guide NOVA CONTROLS NEPTUNE.
Detailed instructions for use are in the User's Guide.
[. . . ] Neptune
WATER TREATMENT SYSTEM
Fourth & Fifth Pump Option (Sprite WT)
Neptune Controller
Reference Manual
CM-700 Series
Copyright 2004 Nova Controls, Inc.
P/N 20-07788-00 Rev. H
Table of Contents
1 Theory of Operation
Page
Overview . 3 Bulkhead Fitting Installation (3 Fittings) . 10
3 Description of Controls
Overview . [. . . ] A flashing display indicates that Neptune is not ready to begin operation, and may result from an interruption and resumption of power while in Manual Start mode.
Setup Mode Access
Setup Mode allows the installer to program operating parameters, including pump dispense and run times. Setup Mode access requires a password, as explained in the "Setup Mode" section. To reach the password entry screen from the Select Formula Home Screen (Fr-A), press and hold ENTER for two seconds. Normal operation stops and the Password entry screen displays. Enter the password as described in "Password Entry" on page 19. Normal operation resumes after all setup programming is complete and the controller is put back into Run Mode.
16
P/N 20-07788-00 Rev. H
5 Setup Mode
Overview
This chapter describes how to program the high level functions of the Neptune. In this chapter, you will learn to how to set the following functions: · · · · · · · · · · Password Entry into Setup Mode Pump/Fill Prime (Pr) User Prime Enable (UPr) User Formula Select Enable (UFr) Formula Time Edit (FE) - Pump Volume vs. Time Fill Time Limit (FILL) AutoStart on Power Up (ASt. ) Solenoid Type Identification (FC) Pump Sequence Edit (S. 1-F) Change Password (PASS)
Use the menu screen illustrations (Figure 14 on page 18) as a guide when learning to program the Neptune. Use the Next key to move to each main Setup screen. The main Setup screens are in a circular loop so you can always return to any screen within the loop by pressing the Next key.
Note
Note
After 5 minutes of idle time in Setup Mode, the display returns to the Run Mode Formula Select screen.
P/N 20-07788-00 Rev. H
17
Setup Mode Menu Screens
Press NEXT to move to each menu in this circular loop. Values shown are default settings.
Input Password Prime Pump/Fill
Select 1, 2, 3, F
Selected Pump
Prime On/Off
Password Input to Setup Mode
Press & Hold 2 Seconds Select First Digit
Enable User Prime
Disable User Prime
Select Second Digit
Installer Select Formula Default Run Formula
A, b, C
NOTE: To allow User to select formula, set UFr. Y )
Select Third Digit Enter Setup Mode
Enable User Formula Select Disable User Formula Select
Edit Formula Time
A1, 2, 3 B1, 2, 3 C1, 2, 3
Formula A, Pump 1
2 sec.
Pump Run Time 0=off, 1-299. 9 Seconds
Start-Press & hold > 2 sec. Stop-Press & release .
Fill Time Limit
0-5999 Seconds
Default = 15 min. (0900 seconds)
Auto Start on Power-up
Manual Start
Fill Solenoid Type - 24 VAC
For Identification Only Not Programmable
Set Value Screens
Edit Pump/Fill Sequence Set Run Sequence (default)
Enter Screen Moves Blinking Digit (when applicable) Set Value/Exit Screen Changes Digit Value
Pump 1
Pump 3 Fill Pump 2
Edit Password
Change Password
Guide To Icons & Display
Next key--Moves Grey digit--Blinking Multi-colored digit--Circling Solid digit--Constant On
End Menu
Exit to Run Mode
Scroll key--Changes Enter key--Action
Figure 14
Setup Mode Programming Menus
18
P/N 20-07788-00 Rev. H
Password Entry
You must enter the correct password to program any of the Setup Mode menus. To enter the password, the Run Mode Select Formula / Home Screen (Fr-A) screen is displayed. The default password is 123. From the Run Mode Fr-A screen, press and hold ENTER for two seconds. At the blinking digit, press SCROLL until you reach the desired number (increments by 1). Press NEXT to move to the next digit and repeat with next digits. Press ENTER to complete the process and enter Setup menus. Prime Pump/Fill (Pr) will be the first menu displayed.
Select Third Digit Enter Setup Mode
Password Input to Setup Mode
Press & Hold 2 Seconds Select First Digit
Select Second Digit
Figure 15 Password Access to Setup Mode
Prime Pump/Fill (Pr)
Note A Prime Pump display of Pr - 0 indicates that a formula is currently operating and/or the tank is filling. [. . . ] · Loosen the pump front captive screw and remove the pump front. · Remove the old tube with barbed connectors and compression nuts. · Install the new tube with barbed connectors and compressions nuts oriented with flat sides facing towards the front. · Insert new tube from the left side of the pump, with pump spinner oriented in an 11/1 o'clock position. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE NOVA CONTROLS NEPTUNE
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.