[. . . ] I539-E1-02
USER'S MANUAL
DeviceNet Communications Unit
MODEL 3G3MV-PDRT2 (For SYSDRIVE 3G3MV Multi-function Compact Inverters)
DeviceNet Communications Card
MODEL 3G3RV-PDRT2 (For SYSDRIVE 3G3RV and 3G3FV High-function General-purpose Inverters)
Thank you for choosing a 3G3MV/3G3RV Series Inverter and DeviceNet Communications Unit. This manual describes the specifications and operating methods of the DeviceNet Communications Unit used for exchanging data between an Inverter and a Programmable Controller. Specifically, it describes the operation methods, communications methods, and data setting methods of the 3G3MV-PDRT2 DeviceNet Communications Unit and 3G3RV-PDRT2 DeviceNet Communications Card. Proper use and handling of the product will help ensure proper product performance, will lengthen product life, and may prevent possible accidents. [. . . ] apres '' u'a les d'etac Pour repon conde ' hment ' ' le neutre dre aux nsateurs sont d'elec ' ' decha tricite, est a la exigences ' rges. masse pour la , s'assurer ' que~ serie 400V.
Motor Output current
The motor torque (Inverter's output current) fluctuates due to deterioration of the equipment, such as loose chain or wear on the machine). A current waveform can be used to check the fluctuation.
Time
7-17
Configurator Settings
Chapter 7
Setting Method
Current Trace Tab Page in the Maintenance Information Window
Click the Current Trace Tab in the Maintenance Information Window and set each item.
Item Trigger
Setting range Forward run command, reverse run command, frequency agreement, or error 10 ms, 20 ms, 50 ms, 100 ms, or a value up to 100 s
Current Trace Sampling Cycle
Details Sets the signal for trace timing. Note: The trace is performed by combining the trigger setting with the Start Trigger, Middle Trigger, and End Trigger Buttons. Select the trace sampling cycle from the pull-down menu.
7-18
Configurator Settings
Chapter 7
Tracing Methods
Button Details Performs manual tracing. When this button is clicked, the trace starts, and when the Cancel Button is clicked, the trace stops. Note 1: When the amount of trace data exceeds 150 points, the oldest data is deleted. Note 2: The 150 points that exist in memory when the Cancel Button is clicked will be stored.
Recorded trace data Trace start (Trace Button is ON. ) Time Trace stop (Cancel Button is ON. )
Use the following button operations to perform traces.
Trace
Trace (Buffer full)
Performs manual tracing. When this button is clicked, the trace starts, and when 150 points have been sampled, the trace stops. Note: If the Cancel Button is clicked during the trace, the trace will stop.
Recorded trace data Trace start (Trace Button is ON. ) Trace stop (150 points sampled) Time
Start Trigger
Starts the trace using the signals selected in the Trigger field, and stops the trace when 150 points have been sampled. Note: The trace will also stop if the Cancel Button is clicked during the trace.
Recorded trace data Start Trigger Button ON. Trace start (trigger signal ON) Time Trace stop (150 points sampled)
Middle Trigger
When this button is clicked, the trace starts. When the signals selected in the Trigger field are turned ON, 75 points are sampled, and then the trace stops. Note 1: When the trigger signal is ON, the 75 points before the trigger and the 75 points after the trigger are recorded. Note 2: The trace also stops when the Cancel Button is clicked.
Recorded trace data Trace start (Middle Trigger Button ON) Trigger signal ON Trace stop (75 points sampled) Time
End Trigger
When this button is clicked, the trace starts. When the signals selected in the Trigger field are turned ON, the trace stops. Note 1: The 150 points from immediately before the trigger signal turns ON are recorded. Note 2: The trace also stops when the Cancel Button is clicked.
Recorded trace data Trace start (End Trigger Button ON) Time Trace stop Trigger signal ON
7-19
Configurator Settings
Chapter 7
Monitor Methods
The trace data can be checked on the History Tab Page and Graph Tab Page.
History Tab Page
Current Trace Tab Page and History Tab Page in the Maintenance Information Window
Item Time Current Status Save Button
Details Displays the time determined from the current trace sampling cycle. Displays all current levels traced in every sampling cycle. Displays whether the sampling timing is during acceleration/deceleration or frequency agreement. Converts the traced data into CSV format and saves as a file. Note: When this button is clicked, the Save File Window is displayed.
7-20
Configurator Settings
Chapter 7
Graph Tab Page
The graph shown in this tab page consists of a vertical axis representing the current level shown in the History Tab Page, and a horizontal axis representing the time. [. . . ] The default setting depends upon the type of Inverter. The value for a 200-V-class 0. 4-kW Inverter is given above.
Operator Parameters
RegisClass 64 (hex) Name ter numInAtber stance tribute (hex) 0500 01 BF Monitor selection 0501 0502 0503 0504 0505 0506 0507 0508 01 01 01 01 01 01 --01 C0 C1 C2 C3 C4 C5 --C6 Monitor selection after power-on Frequency reference setting and display units V/f pattern setting units Not used. Local/Remote Key Stop Key User constant initial values Inverter capacity selection Setting range Setting unit Default setting Write during operation Yes Yes No No --No No No No
Constant
o1-01 o1-02 o1-03 o1-04 o1-05 o2-01 o2-02 o2-03 o2-04
4 to 38 1 to 4 0 to 39999 0, 1 --0, 1 0, 1 0 to 2 0 to FF (See note. )
1 1 1 1 --1 1 1 1
6 1 0 0 0 1 1 0 0 (See note. ) 0 0 0 0 1
o2-05 o2-06 o2-07 o2-08 o2-09
0509 050A 050B 050C 050D
01 01 ----01
C7 C8 ----C9
Frequency reference setting method 0, 1 Operation selection when Digital Oper- 0, 1 ator is disconnected Cumulative operation time setting Cumulative operation time selection Factory use 0 to 65535 0, 1 ---
1 1 1 hr 1 ---
No No No No ---
Note The default setting depends upon the type of Inverter. The value for a 200-V-class 0. 4-kW Inverter is given above.
10-102
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON 3G3MV-PDRT2
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.