[. . . ] W450-E1-06
SYSMAC CP Series CP1H-X40D_-_ CP1H-XA40D_-_ CP1H-Y20DT-D
CP1H CPU Unit
OPERATION MANUAL
CP1H-X40D@-@ CP1H-XA40D@-@ CP1H-Y20DT-D
CP1H CPU Unit
Operation Manual
Revised March 2009
iv
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!DANGER Indicates an imminently hazardous situation which, if not avoided, will result in
death or serious injury. [. . . ] The cable is provided with the Unit and cannot be removed. Note Do not touch the cables during operation. Static electricity may cause operating errors. Expansion Connector Connected to the next Expansion Unit or Expansion I/O Unit.
Main Analog Output Unit Specifications
Analog Output Units are connected to a CP1H CPU Unit. A maximum of seven Units can be connected, including other Expansion Units and Expansion I/O Units.
399
Analog Output Units
Section 7-3
A maximum of 7 Expansion Units or Expansion I/O Units can be connected.
CP1H CPU Unit
CPM1A-20EDR1 Expansion I/O Unit
CPM1A-8ED Expansion I/O Unit
CPM1A-DA041 Analog Output Unit
C OM 01 0 3 05 07 09 11 00 02 04 06 08 10 NC IN CH C H 00 01 02 03 04 05 06 07 08 09 10 11
C OM 00 IN
01 02
0 3
C H 00 01 02 03 08 09 10 11
20EDR1
OUT 00 01 02 03 04 05 06 07 CH 07 00 01 02 04 05 NC N C C OM 06 C M C OM O 0 3 CO M CH
8ED
EXP
04 C OM 0 5 06 07
EXP
OUT
CH
I OUT1 VOUT2 COM2 I OUT3 VOUT4 COM4 AG VOUT1 COM1 I OUT2 VOUT3 COM3 I OUT4 NC
Item Analog Number of outputs output sec- Output signal range tion External output allowable load resistance External output impedance Resolution Overall 25°C accuracy 0 to 55°C D/A conversion data
Voltage Output 4 outputs (4 words allocated) 1 to 5 VDC, 0 to 10 VDC, or 10 to 10 VDC 2 k min. 1/6000 (full scale) 0. 4% full scale 0. 8% full scale 16-bit binary (4-digit hexadecimal) Full scale for 10 to 10 V: F448 to 0BB8 Hex Full scale for other ranges: 0000 to 1770 Hex
Current Output 0 to 20 mA or 4 to 20 mA 350 max. ---
Conversion time Isolation method Current consumption
2 ms/point (8 ms/all points) Photocoupler isolation between analog I/O terminals and internal circuits. No isolation between analog I/O signals. 5 VDC: 80 mA max. ; 24 VDC: 124 mA max.
Analog Output Signal Ranges
Note
The analog values depend on the output signal ranges, as shown in the following diagrams. When the output exceeds the specified range, the output signal will be fixed at either the lower limit or upper limit.
400
4 analog outputs
Analog Output Units
Analog Output Signal Ranges -10 to 10 V
Section 7-3
The hexadecimal values F448 to 0BB8 (3000 to 3000) correspond to an analog voltage range of 10 to 10 V. The entire output range is 11 to 11 V. Specify a negative voltage as a two's complement.
11 V 10 V
8000
F31C (3300)
F448 (3000)
0000 (0)
0V
0BB8 0CE4 (3000) (3300)
7FFF
Conversion Data Hexadecimal (Decimal)
-10 V -11 V
0 to 10 V The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 0 to 10 V. The entire output range is 0. 5 to 10. 5 V. Specify a negative voltage as a two's complement.
10. 5 V 10 V
8000
FED4 (-300)
0000 (0)
0V -0. 5 V
1770 (6000)
189C (6300)
7FFF
Conversion Data Hexadecimal (Decimal)
1 to 5 V The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog voltage range of 1 to 5 V. The entire output range is 0. 8 to 5. 2 V.
5. 2 V 5V
1V 0. 8 V
8000 FED4 (-300)
Conversion Data Hexadecimal (Decimal)
0V
1770 (6000)
189C (6300)
7FFF
401
Analog Output Units
0 to 20 mA
Section 7-3
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 0 to 20 mA. The entire output range is 0 to 21 mA.
21 mA 20 mA
8000
0000 (0) 0 mA
1770 (6000) 189C (6300) 7FFF
Conversion Data Hexadecimal (Decimal)
4 to 20 mA The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 4 to 20 mA. The entire output range is 3. 2 to 20. 8 mA.
20. 8 mA 20 mA
4 mA 3. 2 mA
8000 FED4 (-300)
Conversion Data Hexadecimal (Decimal)
0 mA
1770 (6000)
189C (6300)
7FFF
Procedure
Connect and wire Units.
· Connect Analog Output Units. · Write range code to output words (n+1, n+2). · Select output signals using range codes. · Write D/A conversion values to output words
(n+1 to n+4).
Create a ladder program
Writing D/A Conversion Data
CPU Unit Ladder program
MOV (n+1) CH (n+2) CH
Analog Output Unit
(n+1) C H (n+2) CH
Range code (outputs 1, 2) Range code (outputs 3, 4) Analog output 1 conversion value Analog output 2 conversion value Analog output 3 conversion value Analog output 4 conversion value Analog devices Adjustment equipment Servo Controller Variable speed device Recorder Other
Writes the range code. Writes the converted values.
(n+3) CH (n+4) CH
Where "n" is the last output word allocated to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit.
402
Analog Output Units
Section 7-3
1. Connecting the Analog Output Unit
Connect the Analog Output Unit to the CPU Unit.
CPU Unit CPM1A-DA041 Analog Output Unit
OUT
CH
I OUT1 VOUT2 COM2 I OUT3 VOUT4 COM4 AG VOUT1 COM1 I OUT2 VOUT3 COM3 I OUT4 NC
2. [. . . ] Page 176: Information added on power OFF interrupts. Page 219: Information added on high-speed counter frequency measurements. Page 221: Information added on controlling pulse outputs. Page 222: Information added on output frequency. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON CP1H CPU
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual OMRON CP1H CPU will begin.