[. . . ] E5CN-H E5AN-H E5EN-H
Digital Controllers
SUB1 SUB2
SUB1 SUB2 SUB3 HA
PV
HA SUB3
PV
SUB1 SUB2 SUB3 HA
SV
RSP
SV
OUT1 RSP STOP OUT2 CMW MANU
MV
OUT1 STOP OUT2 CMW MANU
MV
OUT1 STOP OUT2 CWM MANU
PF
A/M
PF
A/M
Ir
Ir
E5CN-H
E5AN-H
E5EN-H
User's Manual Advanced Type
Cat. H157-E1-02
E5CN-H E5AN-H E5EN-H Digital Controllers
User's Manual Advanced Type
Revised March 2009
iv
Preface
The E5CN-H, E5AN-H, and E5EN-H are Digital Controllers. The main functions and characteristics of these Digital Controllers are as follows: · Use the universal inputs to input from thermocouples or temperatureresistance thermometers, or to input analog voltage or analog current inputs. · Either standard or heating/cooling control can be performed. [. . . ] Select the Transfer Output Upper Limit parameter by pressing the M Key.
Transfer Output
Initial Setting Level
tr-h Upper Limit
1300. 0
C
tr-h
200. 0
5. Use the D Key to set the parameter to 200. 0. The default is 1300. 0.
Initial Setting Level
C
6. Select the Transfer Output Lower Limit parameter by pressing the M Key.
tr-l Lower Limit
-200. 0
Transfer Output
127
Using the Transfer Output
C
Section 4-14
7. Use the U Key to set the parameter to -50. 0. The default is -200. 0.
tr-l 25. 0
-50. 0
8. To return to the operation level, press the O Key for at least one second.
PV/SP
Operation Level
C
100. 0
128
Using Banks and PID Sets
Section 4-15
4-15 Using Banks and PID Sets
Banks
Up to eight banks, each of which contains the following parameters, can be created. The current bank number can be changed by using key operations, event inputs, communications (operation commands), or simple programs.
Parameter Set Point PID Set No. SP Ramp Set Value Alarm Value 1 to 3 Alarm Value Upper Limit 1 to 3 Alarm Value Lower Limit 1 to 3 Soak Time Wait Band 0 200. 0 0 OFF 240. 0 40. 0 40. 0 5 3. 0 1 500. 0 0 OFF 300. 0 30. 0 30. 0 10 5. 0 ··· 7
In the bank setting level, select the bank numbers to be edited with the Display Bank Selection parameter, and make the settings for each bank.
Parameter Bank No. Display Bank Selection Setting range 0 to 7 0 to 7 Unit ----Default 0 See note.
Note
The current bank will be displayed. If you change the bank using the U and D Keys, monitor function will be canceled.
If the following parameters are changed, the changes will be saved in the current bank: Set Point, Alarm Values 1 to 3, Alarm Value Upper Limits 1 to 3, Alarm Value Lower Limits 1 to 3, (operation level) SP Ramp Set Value, Soak Time, Wait Band (adjustment level). PID Set Number
PID Set No.
· Select a number from 1 to 8 to specify the PID set for each bank. · The bank number can be confirmed by checking the number at the beginning of the parameter.
1
0. pid
Simple Program and Bank Functions For each bank, the Soak Time and Wait Band parameters can be set, and a simple program can be created. For details on creating a simple program, refer to 4-16 Using the Simple Program Function.
PID Sets
· The PID set to be executed is selected by using the PID Set No. If 0 (Automatic selection) is set, then the PID set will be selected automatically according to preset conditions. · Up to eight of the following parameters can be registered for each PID set.
Parameter Proportional Band Setting range Temperature: 0. 1 to 3, 240. 0 Analog: 0. 1 to 999. 9 Default 8. 0 10. 0 Unit °C or °F %FS
129
Using Banks and PID Sets
Parameter Integral Time Setting range Standard, heating/cooling, position proportional (closed): 0. 0 to 3, 240. 0 Position proportional (floating): 0. 1 to 3, 240. 0 0. 0 to 3240. 0 Standard: MV lower limit + 0. 1 to 105. 0 Heating/cooling: 0. 0 to 105. 0 Position proportional (closed): MV lower limit + 0. 1 to 105. 0 Standard: -5. 0 to MV upper limit -0. 1 Heating/cooling: -105. 0 to 0. 0 Position proportional (closed): -5. 0 to MV upper limit -0. 1 Temperature: -19, 999 to 32, 400 Analog: -5. 0 to 105. 0 0. 01 to 99. 99 0 to 9, 999 (0: LBA function disabled) Default 233. 0
Section 4-15
Unit s
Derivative Time MV Upper Limit
40. 0 105. 0
s %
MV Lower Limit
-5. 0 -105. 0 -5. 0 1320. 0 105. 0 1. 00 0
%
Automatic Selection Range Upper Limit Cooling Coefficient LBA Detection Time
EU % (See note. ) None s
Note
When the PID Automatic Selection Data parameter is set to DV, the unit will be %FS.
The settings for the PID sets are made in the PID setting level. In the PID setting level, select the PID set numbers to be edited with the Display PID Selection parameter, and make the settings for each PID set.
Parameter Display PID Selection Setting range 1 to 8 Unit --Default See note.
Note
The current PID set is displayed. If you use the U and D Keys to change the PID set, the monitor function will be canceled
When the following parameters are changed, the changes will be reflected in the current PID set: Proportional Band, Integral Time, Derivative Time, MV Upper Limit, MV Lower Limit, Cooling Coefficient (adjustment level) LBA Detection Time (advanced function setting level) Automatic PID Set Selection · If the PID Set No. parameter for a bank is set to 0, the PID set will be selected automatically according to preset conditions.
PID set Automatic selection range
1 2 3 4 5 6 7 8
200. 0 400. 0 500. 0 600. 0 700. 0 800. 0 1000. 0 1300. 0
PV: 240. 0 (upper limit)
In the setting example on the left (with the PID Set Automatic Selection Data parameter set to PV), the following PID parameters are used: PV 200°C: PID Set No. 1 200°C < PV 400°C: PID Set No. 2 Set the PID Set Automatic Selection Range Upper Limit so that the set value becomes larger as the PID set number increases. 8, however, the automatic selection range upper limit always equals the upper limit of the specified range. [. . . ] Bank No.
c
M al1h
Alarm Value
0. 0 Upper Limit 1
Infrared Communications Use
M c-sc Cooling Coefficient
1. 00
M bank
0
c
M al1l Alarm Value M
0. 0 Lower Limit 1
Set either of these parameters.
M spmd
lsp
SP Mode
M c-db
0. 0
Heating/cooling Dead Band
M
c
rsp
0. 0
Remote SP Monitor
c
al-2
0. 0
Alarm Value 2
M ct1 M hb1 M oc1
50. 0
M
Heater Current 1
M
Manual Reset Value Clear the offset during control.
M
Set Point During
c
of-r
sp-m
0. 0 Value Monitor
50. 0 stabilization of P or PD
0. 0 SP Ramp
al2h
Alarm Value
0. 0 Upper Limit 2
Set either of these parameters.
Adjustment Level Display Displayed only once when entering adjustment level.
c c
25. 0 M
p
8. 0
Process Value Added when Additional PV display is ON.
r-s RUN/STOP
run
Proportional Band
M
Heater Burnout
M hys
1. 0
M ct1
0. 0
Heater Current 1 Value Monitor
c
Hysteresis (Heating) Hysteresis settings Hysteresis (Cooling)
M al2l
0. 0
Press the O and M Keys for at least 1 s.
Alarm Value Lower Limit 2
Heater Overcurrent Detection 1
M chys
1. 0
ct2
0. 0
Heater Current 2 Value Monitor
c
Alarm Value 3
0. 0
M ct2 M hb2
0. 0
Heater Current 2
M soak
1
M
Soak Time
lcr1
Leakage Current 1
M al3h Alarm Value
0. 0 Value Monitor
0. 0 Monitor
0. 0 Upper Limit 3
Heater Burnout Detection 2
M wt-b
off
M
Wait Band
lcr2
Leakage Current 2
M al3l Alarm Value
0. 0
0. 0 Monitor
Lower Limit 3
M oc2
50. 0
M
Heater Overcurrent Detection 2
M
MV at Stop
M
0. 0
mv-s
0. 0
prst Program Start
rset
o MV Monitor (Heating)
M lcr1
Leakage Current 1
M mv-e
0. 0
MV at PV Error
M sktr Soak Time Remain
0
M c-o
0. 0
MV Monitor (Cooling)
0. 0 Monitor
M hs1
50. 0
M sprt
HS Alarm 1
M
SP Ramp Set Value
M v-m
0. 0
Valve Opening Monitor
off
M lcr2
0. 0
Leakage Current 2 Monitor
M ol-h
105. 0
M
MV Upper Limit
M hs2
50. 0
M ol-l
HS Alarm 2
-5. 0
MV Lower Limit
M
c
ins
0. 00
Temperature Input Shift 1-point shift Upper Limit Temperature Set either of these parameters.
M orl
0. 0
PF Key (See note 2. )
MV Change Rate Limit
Monitor/Setting Item Level
25. 0 Monitor/Setting Item Display 1
0. 0
PF
(E5AN/EN-H only)
M
c
M
db
2. 0
Position Proportional Dead Band Monitor/Setting Item Display 2
PF
insh M
Set either of these parameters.
0. 0 Detection 1
M
M al-3
0. 00 Input Shift Value
2-point shift Lower Limit Temperature
Monitor/Setting Item Display 3
PF
M oc-h
0. 8
Open/Close Hysteresis
c
insl M
0. 00 Input Shift Value
M sqrp M
Monitor/Setting Item Display 4
PF
Monitor/Setting Item Display 5
Extraction of Square Root 0. 0 Low-cut Point
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
PF Key (See note 2. )
Note: 1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/EN-H). When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/EN-H).
339
Appendix
Press the O Key for at least 1 s. Other than the Auto/Manual Switch display
Initial Setting Level
Press the O Key less than 1 s.
Press the O Key less than 1 s.
Protect Level
The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting.
Communications Setting Level
Displayed only for models with communications. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON E5AN-H
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.