User manual OMRON E5EK

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Lastmanuals provides you a fast and easy access to the user manual OMRON E5EK. We hope that this OMRON E5EK user guide will be useful to you.

Lastmanuals help download the user guide OMRON E5EK.


Mode d'emploi OMRON E5EK
Download

You may also download the following manuals related to this product:

   OMRON E5EK MANUAL 2 (1442 ko)
   OMRON E5EK DATASHEET (954 ko)

Manual abstract: user guide OMRON E5EK

Detailed instructions for use are in the User's Guide.

[. . . ] Digital Controller (Programmable Type) User's Manual Cat. H085-E1-03 Preface Thank you for your purchase of your E5EK, intelligent digital controller. The E5EK allows the user to carry out the following: · Select from many types of temperature and analog input (multiple input) · Support position-proportional control (position-proportional type controllers only). · Select output functions such as control output or alarm (output assignment) · Use the HBA (heater burnout alarm) function (standard type controllers only). [. . . ] · The "MV change rate limit" parameter sets the maximum permissible change width per second of the manipulated variable (On the position-proportional control, valve, opening). If a change in the manipulated variable (On the position-proportional control, valve, opening) causes this parameter setting to be exceeded, the calculated value is reached while changing the value by the per-second value set in this parameter. This function is disabled when the set value is "0. 0". · MV upper limit The setting ranges during standard control and heating and cooling control are different. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value. Control Method Standard Heating and cooling Setting Range MV lower limit +0. 1 to 105. 0 0. 0 to 105. 0 Unit % % Default 105. 0 105. 0 Comment · MV lower limit The setting ranges during standard control and heating and cooling control are different. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value. Control Method Standard Heating and cooling Setting Range -5. 0 to MV upper limit -0. 1 -105. 0 to 0. 0 Unit % % Default -5. 0 -105. 0 · MV change rate limit Setting Range 0. 0 to 100. 0 Unit % Default 0. 0 F Related article 4. 2 Operating Condition Restrictions/Manipulated variable restrictions (page 4-5) See 5--22 Level 2 Mode Input digital filter · Sets the time constant of the input digital filter. The following figures shows the effect on data after passing through the digital filter. Function PV before passing through filter A PV after passing through filter 0. 63A Time constant Time Input digital filter Setting Range 0 to 9999 Comment Unit Second Default 0 Open/close hysteresis Conditions of Use Control must be position-proportional control. · Provides hysteresis at ON/OFF switching of open or close output in position-proportional control. Function Setting Range 0. 1 to 20. 0 Comment Unit % Default 0. 8 F Related article 4. 1 Selecting the Control Method/Position-proportional Control (page 4-3) See E5EK-PRR2 AC100-240 E5EK-PRR2 AC/DC24 Model 5--23 CHAPTER 5 PARAMETERS Level 2 Mode Alarm 1 hysteresis Alarm 2 hysteresis Alarm 3 hysteresis Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the "alarm 3 hysteresis" parameter cannot be used. · This parameter is for checking the hysteresis of alarm outputs 1 to 3. Function Setting Range 0. 01 to 99. 99 Comment Unit %FS Default 0. 02 F Related article 3. 4 Setting Alarm Type (page 3-9) See F Related parameters "Alarm 1 type" "Alarm 2 type" "Alarm 3 type" "Alarm 1 open in alarm" "Alarm 2 open in alarm" "Alarm 3 open in alarm" (setup mode) "Alarm value 1" "Alarm value 2" "Alarm value 3" (level 1 mode) Input shift upper limit Input shift lower limit Conditions of Use The input type must be set to temperature input (thermocouple or platinum resistance thermometer). · Sets each of the shift amounts for the input shift upper and lower limit values. Function Setting Range -199. 9 to 999. 9 Comment Unit _C or _F Default 0. 0 F Related article 3. 2 Setting Input Specifications (page 3-4) See F Related parameter "Input type" (setup mode) 5--24 Setup Mode · The parameters in this mode can be used only when the "security" parameter (protect mode) is set to "0" and "1". · This mode contains the parameters for setting the basic specifications of the E5EK controller. These parameters include parameters for specifying the input type, scaling, output assignments, and direct/reverse operation. · To select this mode when in the levels 0 to 2, expansion, option and calibration key for 1 second minimum. The display changes to the menu modes, press the ] using the key then press the key for 1 display. If you select [ second minimum, the controller enters the setup mode. · To select parameters in this mode, press the or keys. To change parameter set- · The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol Input type Scaling upper limit Scaling lower limit Decimal point _C/_F selection Parameter initialize Control output 1 assignment Control output 2 assignment Auxiliary output 1 assignment Auxiliary output 2 assignment Alarm 1 type Alarm 1 open in alarm Alarm 2 type Alarm 2 open in alarm Alarm 3 type Alarm 3 open in alarm Direct/Reverse operation Parameter Name Page 5-26 5-27 5-27 5-27 5-28 5-27 5-28 5-28 5-29 5-29 5-30 5-31 5-30 5-31 5-30 5-31 5-31 5--25 CHAPTER 5 PARAMETERS Setup Mode Input type · Sets the sensor type by the code. Function · Set the code according to the following table. Default is "2: K1 thermocouple". Set value Comment 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 JPt -199. 9 to 650. 0 (_C) Pt -199. 9 to 650. 0 (_C) K1 -200 to 1300 (_C) K2 0. 0 to 500. 0 (_C) J1 -100 to 850 (_C) J2 0. 0 to 400. 0 (_C) T -199. 9 to 400. 0 (_C) E 0 to 600 (_C) L1 -100 to 850 (_C) L2 0. 0 to 400. 0 (_C) U -199. 9 to 400. 0 (_C) N -200 to 1300 (_C) R 0 to 1700 (_C) S 0 to 1700 (_C) B 100 to 1800 (_C) W 0 to 2300 (_C) PLII 0 to 1300 (_C) 4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V Input Type /-199. 9 to 999. 9 (_F) /-199. 9 to 999. 9 (_F) /-300 to 2300 (_F) /0. 0 to 900. 0 (_F) /-100 to 1500 (_F) /0. 0 to 750. 0 (_F) /-199. 9 to 700. 0 (_F) /0 to 1100 (_F) /-100 to 1500 (_F) /0. 0 to 750. 0 (_F) /-199. 9 to 700. 0 (_F) /-300 to 2300 (_F) /0 to 3000 (_F) /0 to 3000 (_F) /300 to 3200 (_F) /0 to 4100 (_F) /0 to 2300 (_F) Platinum resistance thermometer Thermocouple Current input Voltage input F Related article 3. 2 Setting Input Specifications (page 3-4) See F Related parameters When input type is set to temperature input: "_C/_F selection" (setup mode) When input type is set to voltage input or current input: "Scaling upper limit" "Scaling lower limit" "Decimal point" (setup mode) 5--26 Setup Mode Scaling upper limit Scaling lower limit Decimal point Conditions of Use The input type must be set to analog input (voltage or current input). Function · This parameter can be used only when voltage input or current input is selected as the input type. · When voltage input or current input is selected as the input type, scaling is carried out. Set the scaling upper limit in the "scaling upper limit" parameter and the scaling lower limit in the "scaling lower limit" parameter. · The "decimal point" parameter specifies the decimal point position of parameters (set point, etc. ) whose unit is set to EU (Engineering Unit). · Scaling upper limit, Scaling lower limit Comment Parameter Scaling upper limit Scaling lower limit Setting Range Scaling lower limit +1 to 9999 -1999 to scaling upper limit -1 Unit EU EU Default 100 0 · Decimal point : default : 0 Set Value 0 1 2 3 Setting 0 digits past decimal point 1 digit past decimal point 2 digits past decimal point 3 digits past decimal point Example 1234 123. 4 12. 34 1. 234 See F Related article 3. 2 Setting Input Specifications (page 3-4) F Related parameter "Input type" (setup mode) Parameter initialize Function · Returns parameter settings to their defaults. However, note that the following parameters are not affected by execution of this parameter: "input type", "scaling upper limit", "scaling lower limit", "decimal point" and "_C/_F selection". · When this parameter is selected, [ ] ("no") is first displayed. [. . . ] Modified the diagram in "RS-232C". Modified the diagram in "Preparations". Modified the diagram in "Preparation". Modified the diagram in "Preparation". [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON E5EK

Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets...
In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.

Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual OMRON E5EK will begin.

Search for a user manual

 

Copyright © 2015 - LastManuals - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.

flag