[. . . ] Digital Controller
(Programmable Type)
User's Manual
Cat. H085-E1-03
Preface
Thank you for your purchase of your E5EK, intelligent digital controller. The E5EK allows the user to carry out the following: · Select from many types of temperature and analog input (multiple input) · Support position-proportional control (position-proportional type controllers only). · Select output functions such as control output or alarm (output assignment) · Use the HBA (heater burnout alarm) function (standard type controllers only). [. . . ] · The "MV change rate limit" parameter sets the maximum permissible change width per second of the manipulated variable (On the position-proportional control, valve, opening). If a change in the manipulated variable (On the position-proportional control, valve, opening) causes this parameter setting to be exceeded, the calculated value is reached while changing the value by the per-second value set in this parameter. This function is disabled when the set value is "0. 0". · MV upper limit The setting ranges during standard control and heating and cooling control are different. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value.
Control Method Standard Heating and cooling Setting Range MV lower limit +0. 1 to 105. 0 0. 0 to 105. 0 Unit % % Default 105. 0 105. 0
Comment
· MV lower limit The setting ranges during standard control and heating and cooling control are different. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value.
Control Method Standard Heating and cooling Setting Range -5. 0 to MV upper limit -0. 1 -105. 0 to 0. 0 Unit % % Default -5. 0 -105. 0
· MV change rate limit
Setting Range 0. 0 to 100. 0 Unit % Default 0. 0
F Related article 4. 2 Operating Condition Restrictions/Manipulated variable restrictions (page 4-5)
See
5--22
Level 2 Mode
Input digital filter
· Sets the time constant of the input digital filter. The following figures shows the effect on data after passing through the digital filter.
Function PV before passing through filter
A
PV after passing through filter
0. 63A
Time constant
Time
Input digital filter
Setting Range 0 to 9999
Comment
Unit Second
Default 0
Open/close hysteresis
Conditions of Use Control must be position-proportional control.
· Provides hysteresis at ON/OFF switching of open or close output in position-proportional control.
Function
Setting Range 0. 1 to 20. 0
Comment
Unit %
Default 0. 8
F Related article 4. 1 Selecting the Control Method/Position-proportional Control (page 4-3)
See
E5EK-PRR2 AC100-240 E5EK-PRR2 AC/DC24
Model
5--23
CHAPTER 5 PARAMETERS
Level 2 Mode
Alarm 1 hysteresis Alarm 2 hysteresis Alarm 3 hysteresis
Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the "alarm 3 hysteresis" parameter cannot be used.
· This parameter is for checking the hysteresis of alarm outputs 1 to 3.
Function
Setting Range 0. 01 to 99. 99
Comment
Unit %FS
Default 0. 02
F Related article 3. 4 Setting Alarm Type (page 3-9)
See
F Related parameters "Alarm 1 type" "Alarm 2 type" "Alarm 3 type" "Alarm 1 open in alarm" "Alarm 2 open in alarm" "Alarm 3 open in alarm" (setup mode) "Alarm value 1" "Alarm value 2" "Alarm value 3" (level 1 mode)
Input shift upper limit Input shift lower limit
Conditions of Use The input type must be set to temperature input (thermocouple or platinum resistance thermometer).
· Sets each of the shift amounts for the input shift upper and lower limit values.
Function
Setting Range -199. 9 to 999. 9
Comment
Unit _C or _F
Default 0. 0
F Related article 3. 2 Setting Input Specifications (page 3-4)
See
F Related parameter "Input type" (setup mode)
5--24
Setup Mode
· The parameters in this mode can be used only when the "security" parameter (protect mode) is set to "0" and "1". · This mode contains the parameters for setting the basic specifications of the E5EK controller. These parameters include parameters for specifying the input type, scaling, output assignments, and direct/reverse operation. · To select this mode when in the levels 0 to 2, expansion, option and calibration key for 1 second minimum. The display changes to the menu modes, press the ] using the key then press the key for 1 display. If you select [ second minimum, the controller enters the setup mode. · To select parameters in this mode, press the or keys. To change parameter set-
· The following table shows the parameters supported in this mode and the page where the parameter is described.
Symbol Input type Scaling upper limit Scaling lower limit Decimal point _C/_F selection Parameter initialize Control output 1 assignment Control output 2 assignment Auxiliary output 1 assignment Auxiliary output 2 assignment Alarm 1 type Alarm 1 open in alarm Alarm 2 type Alarm 2 open in alarm Alarm 3 type Alarm 3 open in alarm Direct/Reverse operation Parameter Name Page 5-26 5-27 5-27 5-27 5-28 5-27 5-28 5-28 5-29 5-29 5-30 5-31 5-30 5-31 5-30 5-31 5-31
5--25
CHAPTER 5 PARAMETERS
Setup Mode
Input type
· Sets the sensor type by the code.
Function
· Set the code according to the following table. Default is "2: K1 thermocouple".
Set value Comment 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 JPt -199. 9 to 650. 0 (_C) Pt -199. 9 to 650. 0 (_C) K1 -200 to 1300 (_C) K2 0. 0 to 500. 0 (_C) J1 -100 to 850 (_C) J2 0. 0 to 400. 0 (_C) T -199. 9 to 400. 0 (_C) E 0 to 600 (_C) L1 -100 to 850 (_C) L2 0. 0 to 400. 0 (_C) U -199. 9 to 400. 0 (_C) N -200 to 1300 (_C) R 0 to 1700 (_C) S 0 to 1700 (_C) B 100 to 1800 (_C) W 0 to 2300 (_C) PLII 0 to 1300 (_C) 4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V Input Type /-199. 9 to 999. 9 (_F) /-199. 9 to 999. 9 (_F) /-300 to 2300 (_F) /0. 0 to 900. 0 (_F) /-100 to 1500 (_F) /0. 0 to 750. 0 (_F) /-199. 9 to 700. 0 (_F) /0 to 1100 (_F) /-100 to 1500 (_F) /0. 0 to 750. 0 (_F) /-199. 9 to 700. 0 (_F) /-300 to 2300 (_F) /0 to 3000 (_F) /0 to 3000 (_F) /300 to 3200 (_F) /0 to 4100 (_F) /0 to 2300 (_F) Platinum resistance thermometer
Thermocouple
Current input Voltage input
F Related article 3. 2 Setting Input Specifications (page 3-4)
See
F Related parameters When input type is set to temperature input: "_C/_F selection" (setup mode) When input type is set to voltage input or current input: "Scaling upper limit" "Scaling lower limit" "Decimal point" (setup mode)
5--26
Setup Mode
Scaling upper limit Scaling lower limit Decimal point
Conditions of Use The input type must be set to analog input (voltage or current input).
Function
· This parameter can be used only when voltage input or current input is selected as the input type. · When voltage input or current input is selected as the input type, scaling is carried out. Set the scaling upper limit in the "scaling upper limit" parameter and the scaling lower limit in the "scaling lower limit" parameter. · The "decimal point" parameter specifies the decimal point position of parameters (set point, etc. ) whose unit is set to EU (Engineering Unit). · Scaling upper limit, Scaling lower limit
Comment
Parameter Scaling upper limit Scaling lower limit
Setting Range Scaling lower limit +1 to 9999 -1999 to scaling upper limit -1
Unit EU EU
Default 100 0
· Decimal point : default : 0
Set Value 0 1 2 3 Setting 0 digits past decimal point 1 digit past decimal point 2 digits past decimal point 3 digits past decimal point Example 1234 123. 4 12. 34 1. 234
See
F Related article 3. 2 Setting Input Specifications (page 3-4) F Related parameter "Input type" (setup mode)
Parameter initialize
Function
· Returns parameter settings to their defaults. However, note that the following parameters are not affected by execution of this parameter: "input type", "scaling upper limit", "scaling lower limit", "decimal point" and "_C/_F selection". · When this parameter is selected, [ ] ("no") is first displayed. [. . . ] Modified the diagram in "RS-232C". Modified the diagram in "Preparations". Modified the diagram in "Preparation". Modified the diagram in "Preparation". [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON E5EK
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.