Detailed instructions for use are in the User's Guide.
[. . . ] · High switching power (1-pole: 10 A). · Environment-friendly (Cd, Pb free). · Wide range of Sockets also available.
Model Number Structure
Model Number Legend
G2R
1
LR
2 3 4
5 6
5. Classification Blank: General-purpose N: LED indicator D: Diode ND: LED indicator and diode NI: LED indicator with test button NDI: LED indicator and diode with test button 7. [. . . ] operating frequency Insulation resistance Dielectric strength 100 m max. (w/built-in diode: 20 ms max. ) Mechanical: Electrical: AC: 15 ms max. ; DC: 10 ms max. (w/built-in diode: 20 ms max. ) 1 pole 2 poles
18, 000 operations/hr 1, 800 operations/hr (under rated load)
1, 000 M min. (at 500 VDC) 5, 000 VAC, 50/60 Hz for 1 min between coil and 5, 000 VAC, 50/60 Hz for 1 min between coil and contacts*; contacts*; 3, 000 VAC, 50/60 Hz for 1 min between contacts of different polarity 1, 000 VAC, 50/60 Hz for 1 min between contacts of 1, 000 VAC, 50/60 Hz for 1 min between contacts of same polarity same polarity
Electromechanical relays
Vibration resistance Shock resistance Endurance
Destruction: Malfunction: Destruction: Malfunction: Mechanical: Electrical:
10 to 55 to 10 Hz, 0. 75 mm single amplitude (1. 5 mm double amplitude) 10 to 55 to 10 Hz, 0. 75 mm single amplitude (1. 5 mm double amplitude) 1, 000 m/s2 200 m/s2 when energized; 100 m/s2 when not energized AC coil: 10, 000, 000 operations min. ; DC coil: 20, 000, 000 operations min. (at 18, 000 operations/hr) 100, 000 operations min. (at 1, 800 operations/hr under rated load) (DC coil type) 40°C to 70°C (with no icing or condensation) 5% to 85%
Ambient temperature Ambient humidity Weight
Operating: Operating: Approx. 21 g
Note: Values in the above table are the initial values. *4, 000 VAC, 50/60 Hz for 1 minute when the P2R-05A or P2R-08A Socket is mounted.
Approved Standards
UL 508 (File No. E41643)
Model Contact form Coil ratings 5 to 110 VDC 5 to 240 VAC Contact ratings 10 A, 30 VDC (resistive) 10 A, 250 VAC (general use) TV-3 (NO contact only) 5 A, 30 VDC (resistive) 5 A, 250 VAC (general use) TV-3 (NO contact only) Operations 6 x 103 G2R-1-S SPDT
IEC/VDE (EN61810)
Contact form 1 pole Coil ratings 6, 12, 24, 48 VDC 24, 110, 120, 230, 240 VAC 6, 12, 24, 48 VDC 24, 110, 120, 230, 240 VAC Contact ratings 5 A, 440 VAC (cos = 1. 0) 10 A, 250 VAC (cos = 1. 0) 10 A, 30 VDC (0 ms) 5 A, 250 VAC (cos =1. 0) 5 A, 30 VDC (0 ms) Operations 100 x 103
G2R-2-S DPDT
6 x 103
2 poles
100 x 103
CSA 22. 2 No. 0, No. 14 (File No. LR31928)
Model Contact form Coil ratings 5 to 110 VDC 5 to 240 VAC Contact ratings 10 A, 30 VDC (resistive) 10 A, 250 VAC (general use) TV-3 (NO contact only) 5 A, 30 VDC (resistive) 5 A, 250 VAC (general use) TV-3 (NO contact only) Operations 6 x 103 G2R-1-S SPDT
LR
Number of poles 1 pole Coil ratings 5 to 110 VDC 5 to 240 VDC Contact ratings 10 A, 250 VAC (general use) 7. 5 A, 250 VAC (PF0. 4) 10 A, 30 VDC (resistive) 5A, 30VDC (L/R=7ms) 5 A, 250 VAC (general use) 2 A, 250 VAC (PF0. 4) 5 A, 30 VDC (resistive) 3A, 30VDC (L/R=7ms) Operations 100 x 103
2 poles 6 x 103
G2R-2-S DPDT
5 to 110 VDC 5 to 240 VDC
100 x 103
General-purpose Relay
G2RS
G-7
Engineering Data
Maximum Switching Power
Plug-in Relays
G2R-1-S
100
G2R-2-S
100
Switching current (A)
Switching current (A)
AC inductive load (cos = 0. 4)
AC resistive load
10
DC resistive load DC inductive load (L/R = 7 ms)
10
AC inductive load (cos = 0. 4)
AC resistive load
DC resistive load
1
1
DC inductive load (L/R = 7 ms)
0. 1
1
10
100
1000
0. 1
1
10
100
1000
Switching voltage (V)
Switching voltage (V)
Endurance
Plug-in Relays
G2R-1-S Endurance (x103 operations)
5, 000
G2R-2-S
10, 000
Endurance (x103 operations)
5, 000
1, 000 500
250-VAC/30-VDC resistive load 250-VAC inductive load (cos = 0. 4)
1, 000 500
30-VDC inductive load (L/R = 7ms) 250-VAC/30-VDC resistive load
100 50
30-VDC inductive load (L/R = 7ms)
100
250-VAC 50 inductive load (cos = 0. 4)
Switching current (A)
Switching current (A)
Ambient Temperature vs Maximum Coil Voltage
Maximum voltage (%)
DC coil
AC coil
Note: The maximum voltage refers to the maximum value in a varying range of operating power voltage, not a continuous voltage. Ambient temperature (°C)
G-8
General-purpose Relay G2RS
Technical and Environmental Properties
Properties DIN-railing Resistance Environmental Protection Flammability Class Base 250 RT 1 Base, Insulator, Spool Case, Indicator, Pushbutton 2 8 mm 8 mm AgSnIn UL 94V-0 UL 94V-2 1-Pole and 2 Pole Model
Pollution degree Creepage Distance Clearance Distance Contact Material
Two-way action test button
Relay in normal operation For momentary operation For lock operation
1
2
Pull down the test button to the first position, then press the yellow button with an insulated tool to operate the contact.
Pull down the test button to the second position. (The contact is now in the locked position).
Typical information for reference only
The following data is provided as experimental and/or calculated data for reference only. These fall under the category of typical behaviour and the operation of individual relays will vary according to the exact operating conditions Typical Operate / Release times AC Type (operate / release time) DC Type (operate / release time) 6 / 8 ms 12 / 4 ms 1 pole model 6 / 10 ms 11 / 15 ms 2 pole model
Multiple Contact DC Switching Capacity
Load Reduction Factor
1 10 0. 8 Switching Current (A) Switching Current (A)
Switching capacity of DC resistive load
0. 6
G2R-2-S
1
0. 4
2 contacts in series 1 0. 8 0. 6 0. 4 Cos(p. f. ) 0. 2 0. 1 20 40 60 80 100 120
G2R-1S
140
160
180
200
220
For AC inductive loads (such as solenoids, contactor coils, etc. ) the reduction factor corresponding to cos(p. f. ) (cosine of power factor) is multiplied by the rated current in order to identify the maximum allowable current. This approximation is not valid for loads with high inrush currents such as electric motors or fluorescent lamps.
Switching Voltage (Vdc)
General-purpose Relay
G2RS
G-9
Electromechanical relays
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Relays with Plug-in Terminals
SPDT Relays
G2R-1-S, G2R-1-SN, G2R-1-SNI G2R-1-SD, G2R-1-SND, G2R-1-SNDI
Terminal Arrangement/Internal Connections (Bottom View)
G2R-1-S
1
G2R-1-SD (DC)
29 max.
13 max.
1
5
35. 5 max.
2
4
3
5
2
4
3
G2R-1-SN, G2R-1-SNI (AC)
G2R-1-SN, G2R-1-SNI (DC)
20
1
1
DC 24V
1
0. 5
4. 75
5
5
2
4
3
5
2
4
3
7. 5
G2R-1-SND, G2R-1-SNDI (DC)
5. 2 5. 2 17. 5
1
5
2
4
3
DPDT Relays
G2R-2-S, G2R-2-SN, G2R-2-SNI G2R-2-SD, G2R-2-SND, G2R-2-SNDI
Terminal Arrangement/Internal Connections (Bottom View)
G2R-2-S
1 2 3 4
G2R-2-SD (DC)
1 2 3 4
29 max.
13 max.
8
7
6
5
8
7
6
5
35. 5 max.
G2R-2-SN, G2R-2-SNI (AC)
1 2 3 4
G2R-2-SN, G2R-2-SNI (DC)
1 2 3 4
6. 2
0. 5
2. 5 2. 4
20
8
7
6
5
8
7
6
5
7. 4
8. 9
G2R-2-SND, G2R-2-SNDI (DC)
5 5 19. 4
1
2
3
4
8
7
6
5
G-10
General-purpose Relay G2RS
DIN-rail/Surface Mounting Sockets
P2RF-05-S
38. 2 max. Terminal Arrangement (Top View)
11 32. 6 27. 6 22. 6 12 14
92. 0 max.
35. 4
24. 5
A1 A2
Standard model
Option (with ejector and label attached)
28. 5 18. 0 max. 36. 5 max.
Terminal Arrangement (Top View)
21 11 32. 6 27. 6 22. 6 (3. 4) 24 14 22 12
92. 0 max.
35. 4
A1 A2
Standard model
Option (with ejector and label attached)
28. 6 18. 0 max. 32. 6
(5. 3)
Accessories for P2RF-@-S
Socket Bridge
Insulating coating
Clip and Release Lever
9 L 1. 2 dia. conductor (See note 1. )
14
16. 8
40. 35
General-purpose Relay
G2RS
36
G-11
Electromechanical relays
24. 5
P2RF-05-E
Five, M3. 5×7 48 max. [. . . ] Doing so may cause damage to internal components (e. g. , deformation of the clamp spring or cracks in the housing) or cause deterioration of insulation. · Do not insert the screwdriver at an angle. Doing so may break the side of the socket and result in a short-circuit.
General-purpose Relay
G2RS
G-15
Electromechanical relays
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0. 03937. [. . . ]