[. . . ] Safety Relay Unit
Ultra Slim Safety Relay Unit
s Models of width 17. 5 mm (smallest Unit in the
G9SB
world as of January 2001) available with 2 or 3 poles. Models of width 22. 5 mm with 3 poles also available.
s EN standards (TÜV approval) pending. s DIN track mounting possible.
Ordering Information
Main contacts DPST-NO Auxiliary contact None Number of input channels 2 channels 1 channel or 2 channels 2 channels 1 channel or 2 channels 3PST-NO SPST-NC None (direct breaking) 2 channels 1 channel or 2 channels 2 channels 1 channel or 2 channels Manual-reset Auto-reset Manual-reset Reset mode Auto-reset Input type Inverse + common Inverse + common --Inverse + common Inverse + common 24 VDC 24 VAC/VDC Rated voltage 24 VAC/VDC Model G9SB-2002-A G9SB-200-B G9SB-2002-C G9SB-200-D G9SB-3010 G9SB-3012-A G9SB-301-B G9SB-3012-C G9SB-301-D 3 4 4 Category
Model Number Legend:
1. [. . . ] 1, 800 operations/hr) 5 VDC, 1 mA -25 to 55°C (with no icing or condensation) 35% to 85% RH 0. 5 N·m Approx. 115 g EMI: EN55011 group 1 class A EMS: EN50082-2 Approx. 120 g EN954-1, EN60204-1, UL508, CSA C22. 2 No. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method. The bounce time is not included in the figure for operating time. The response time is the time it takes for the main contact to open after the input is turned OFF. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
2
G9SB
G9SB
Application Examples
G9SB-2002-A (24 VAC/VDC) or G9SB-3012-A (24 VAC/VDC) with 2-channel Limit Switch Input/Auto-reset
23
Timing Chart
Limit switches S1 and S2
S2 24 S1
11 12 KM1 KM2
K1 and K2 (NC) K1 and K2 (NO) KM1 and KM2 (NC) KM1 and KM2 (NO)
Open
Feedback loop
A1 A2 T11
+-
T12
T31
T32
13
23
33
41
S1:
TH SA
K1
K2
K1
K1
S2: M:
Safety limit switch with positive opening mechanism (D4D or D4B) Limit switch 3-phase motor
K2 K1 a
K2
a
Control circuit
K2
KM1 and KM2: Magnetic Contactor (LC1D)
KM1
T21
T22
14
24
34
42
KM2
Note
Only the G9SB-3012-A model has terminals 33-34 and 41-42.
KM1 KM2
M
Note External connections and timing charts for G9SB-200-B/301-B models are the same as those for G9SB-2002-A/3012-A models.
G9SB-2002-C (24 VAC/VDC) or G9SB-3012-C (24 VAC/VDC) with 2-channel Emergency Stop Switch Input/Manual-reset
S1
Timing Chart
21 11
Emergency stop switch S1
22 12
KM1 KM2
Reset switch S2 K1 and K2 (NC)
S2
Feedback loop
K1 and K2 (NO) KM1 and KM2 (NC)
A1 A2 T11
+-
T12
T31
T32
13
23
33
41
KM1 and KM2 (NO)
TH SA
K1
K2
K1
K1 K2
Note
K2 K1 a
K2
a
Control circuit
KM1
Output turns ON with the rising edge of reset switch S2, but will not operate if there is a short breakdown in S2.
Emergency stop switch with positive opening mechanism (A165E, A22E) Reset switch 3-phase motor
S1:
KM2
T21 T22 14 24 34 42
S2: M:
KM1 and KM2: Magnetic Contactor (LC1D)
KM1 KM2
M
Note
Only the G9SB-3012-C model has terminals 33-34 and 4142.
Note
External connections and timing charts for G9SB-200-D/301-D models are the same as those for G9SB-2002-C/3012-D models.
3
G9SB
G9SB-200-D (24 VAC/VDC) or G9SB-301-D (24 VAC/VDC) with 2-channel Safety Area Sensor/Manual-reset
Emitter Receiver
G9SB
Timing Chart
F3S-A: Incident Interrupted Reset switch S1 K1 and K2 (NC) K1 and K2 (NO)
F3S-A
Shield Red Red/black Gray/black Gray/black Gray Blue Brown Black Purple Brown White Gray Pink Blue
KM1 KM2
KM1 and KM2 (NC) Shield Feedback loop
KM1 and KM2 (NO)
Note
Output turns ON with the rising edge of reset switch S1, but will not operate if there is a short breakdown in S1.
F3S-A: S1: M: E1 and E2: Safety Area Sensor Reset switch 3-phase motor 24-VDC power supply (S82K)
S1
Open
Open
Open
Open
KM1 and KM2: Magnetic Contactor (LC1D)
2
A1 A2
T21
T11
T12
T22
T31
T32
13
23
33
41
+-
Note:
K1
TH SA
K2
K1
1. Connect E1 to model other than the F3S-A. Only the G9SB301-D model has terminals 33-34 and 4142.
K2 K1 a
K1
a
Control circuit
K2
KM1
K2
KM2
14 24 34 42
KM1 KM2
M
G9SB-3010 (24 VDC) with 2-channel Limit Switch Input/Auto-reset
Timing Chart
Limit switches S1 and S2
23
K1 and K2 (NC)
S2
24
KM1 11 12 KM2
K1 and K2 (NO) KM1 and KM2 (NC) KM1 and KM2 (NO)
S1
Feedback loop
Open
A1 A2 T31 T32
13
23
33 41
+ TH
-
S1:
Safety limit switch with positive opening mechanism (D4D or D4B) Limit switch 3-phase motor
K1
K2
K1
K2
SA
K1 K2
S2: M:
a
KM1 and KM2: Magnetic Contactor (LC1D)
K1
Control circuit
a
K2
KM1
14
24
34 42
KM2
KM1 KM2
M
4
G9SB
G9SB
Dimensions
G9SB-200@-@ G9SB-3010
Terminal Arrangement G9SB-200@-@
83
G9SB-3010
13 23 33 41 T31 A1
(green) (orange) (orange)
13 23 T31 T11 T12 A1
(green) (orange) (orange)
18
PWR K1 K2
PWR K1 K2
2. 5 2 5 10
T21 T22 A2 14 24 T32
42 T32 A2 14 24 34
112 max.
2. 6
100 max. (Average: 17. 5)
G9SB-301-@
83
Terminal Arrangement
18
G9SB-200@-@
2. 5 3 5 15
13 23 33 41
112 max.
T11 T12 T31 A1
2. 6
PWR (green) K1 (orange) K2 (orange)
T21 T22 T32 A2
100 max. (Average: 22. 5)
5
G9SB
G9SB
Installation
s
Internal connections
G9SB-2002-A/C (24 VAC/VDC) G9SB-3012-A/C (24 VAC/VDC)
A1 A2 T11
+-
T12
T31
T32
13
23
33
41
TH SA
K1
K2
K1
K1 K2
K2 K1 a
K2
a
Control circuit
T21
T22
14
24
34
42
G9SB-200-B/D (24 VAC/VDC) G9SB-301-B/D (24 VAC/VDC)
A1 A2 T21 T11 T12 T22 T31 T32 13 23 33 41
+-
TH SA
K1
K2
K1
K2 K1 a
K1
a
Control circuit
K2
K2
14
24
34
42
G9SB-3010 (24 VDC)
A1 A2 T31 T32
13
23
33 41
+ TH
-
K1
K2
K1
K2
SA
K1 K2
a
K1
Control circuit
a
K2
14
24
34 42
Note:
1. @-B/D models, short terminals T12 and T22. Only G9SB-301@-@ models have terminals 33-34 and 41-42.
6
G9SB
G9SB
Precautions
Wiring
Turn OFF the G9SB before wiring. Do not touch the terminals of the G9SB while the power is turned ON, because the terminals are charged and may cause an electric shock. Stranded wire: 0. 2 to 2. 5 mm2 Solid wire: 0. 2 to 2. 5 mm2 Tighten each screw to a torque of 0. 5 to 0. 6 N·m, or the G9SB may malfunction or generate heat. External inputs connected to T11 and T12 or T21 and T22 of the G9SB must be no-voltage contact inputs.
T11 T12
T11 T12
G9SB
G9SB
Earth Short
A positive thermistor is built into the G9SB circuits, so you can detect earth short breakdowns and breakdown shorts between channel 1 and channel 2. [. . . ] To convert grams into ounces, multiply by 0. 03527.
Cat. J130-E1-1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company Industrial Devices and Components Division H. Q. Industrial Control Components Department Shiokoji Horikawa, Shimogyo-ku Kyoto, 600-8530 Japan Tel: (81)75-344-7119/Fax: (81)75-344-7149
Printed in Japan 0301-2M (0301) (A)
8 [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON G9SB
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual OMRON G9SB will begin.