Detailed instructions for use are in the User's Guide.
[. . . ] Example: H3CR-F 24 VAC/DC Supply voltage H3CR-FN H3CR-F8N H3CR-FN-300 H3CR-F8N-300 H3CR-F 11-pin models 8-pin models H3CR-F8
Model Number Legend: H3CR 1 23
1. Configuration None: 11-pin socket 8: 8-pin socket
4
3. Twin Timer Mode None: Flicker OFF start N: Flicker ON start 4. Specified Type 300: Long time range (1. 2 s to 300 h) type
2
H3CR-F Accessories (Order Separately)
Name/specifications Flush Mounting Adapter Y92F-30 Y92F-73 Y92F-74 Mounting Track 50 cm (l) x 7. 3 mm (t) 1 m (l) x 7. 3 mm (t) 1 m (l) x 16 mm (t) End Plate Spacer Protective Cover Track Mounting/ Front Connecting Socket Back Connecting Socket Hold-down Clip 8-pin 11-pin 8-pin 11-pin For PL08 and PL11 Sockets For PF085A Socket PFP-50N PFP-100N PFP-100N2 PFP-M PFP-S Y92A-48B P2CF-08 P2CF-11 P3G-08 P3GA-11 Y92H-7 Y92H-8 Models
H3CR-F
Specifications
General
Item Operating mode Pin type Operating/Reset method Output type Mounting method EMC 11-pin Relay output (DPDT) DIN track mounting, surface mounting, and flush mounting EN55011 Group 1 class A EN55011 Group 1 class A IEC801-2: 4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference: ENV50140: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Conducted Disturbance: ENV50141: 10 V (0. 15 to 80 MHz) (level 3) Immunity Burst: IEC801-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4) UL508, CSA C22. 2 No. 14, LR/NK Conforms to VDE0435/2021, VDE0110 Conforms to EN50081-2, prEN50082-2 Emission Enclosure: Emission AC Mains: Immunity ESD: H3CR-F Flicker OFF start 8-pin Time-limit operation/Time-limit reset or self-reset H3CR-F8 11-pin H3CR-FN Flicker ON start 8-pin H3CR-F8N
Approved standards
Time Ranges
0. 05 s to 30 h Models Time unit Setting 1. 2 3 12 30 0. 3 to 3 1. 2 to 12 3 to 30 s (sec) 0. 05 to 1. 2 x10 s (10 s) 1. 2 to 12 3 to 30 12 to 120 30 to 300 0. 12 to 1. 2 0. 3 to 3 1. 2 to 12 3 to 30 min h (hrs)
Note: Instantaneous output is available at any time range. [. . . ] Configuration None: 11-pin socket 8: 8-pin socket
16
H3CR-H Accessories (Order Separately)
Name/specifications Flush Mounting Adapter Y92F-30 Y92F-70 Y92F-71 Mounting Track 50 cm (l) x 7. 3 mm (t) 1 m (l) x 7. 3 mm (t) 1 m (l) x 16 mm (t) End Plate Spacer Protective Cover Track Mounting/ Front Connecting Socket Back Connecting Socket Hold-down Clip 8-pin 11-pin 8-pin 11-pin For PL08 and PL11 Sockets For PF085A Socket PFP-50N PFP-100N PFP-100N2 PFP-M PFP-S Y92A-48B P2CF-08 P2CF-11 P3G-08 P3GA-11 Y92H-1 Y92H-2 Models
H3CR-H
Specifications
General
Item Operating/Reset method Pin type Input type Output type Mounting method EMC H3CR-H8L Instantaneous operation/Time-limit reset 8-pin --Relay output (DPDT) Emission Enclosure: Emission AC Mains: Immunity ESD: No-voltage Relay output (SPDT) Relay output (DPDT) H3CR-H8RL H3CR-HRL Instantaneous operation/Time-limit reset/Forced reset 11-pin
DIN track mounting, surface mounting, and flush mounting EN55011 Group 1 class A EN55011 Group 1 class A IEC801-2: 4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference: ENV50140: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Conducted Disturbance: ENV50141: 10 V (0. 15 to 80 MHz) (level 3) Immunity Burst: IEC801-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4) UL508, CSA C22. 2 No. 14, LR/NK Conforms to VDE0435/2021, VDE0110 Conforms to EN50081-2, prEN50082-2
Approved standards
Time Ranges
Time unit Setting 0. 6 1. 2 6 12 Min. power ON time Note: 0. 05 to 0. 6 0. 1 to 1. 2 0. 5 to 6 1 to 12 0. 1 sec min. S-series s (sec) M-series min
If the above minimum power ON time is not secured, the H3CR may not operate. Be sure to secure the above minimum power ON time.
17
H3CR-H Ratings
Rated supply voltage (see note) Operating voltage range No-voltage input
H3CR-H
100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC, 100 to 125 VDC 85% to 110% of rated supply voltage ON-impedance: 1 k max. 100 to 120 VAC: 200 to 240 VAC: 24 VAC/DC: 48 VDC: 100 to 125 VDC: 0. 18 VA (100 VAC applied) 0. 25 VA (200 VAC applied) 0. 24 VA (24 VAC applied)/140 mW (24 VDC applied) 130 mW (48 VDC applied) 330 mW (125 VDC applied)
Power consumption
Control outputs Note:
Contact output: 5 A at 250 VAC, resistive load (cos = 1)
A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
Characteristics
Accuracy of operating time Setting error Influence of voltage Influence of temperature Insulation resistance Dielectric strength ±0. 3% FS max. (±0. 3% FS ±10 ms in ranges of 0. 6 and 1. 2 s) ±5% FS ±0. 05 s max. (±0. 5% FS ±10 ms in ranges of 0. 6 and 1. 2 s) ±2% FS max. (±2% FS ±10 ms in ranges of 0. 6 and 1. 2 s) 100 MW min. (at 500 VDC) 2, 000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts) 2, 000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit) 1, 000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) 3 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC; 1 kV for 24 VAC/DC, 48 VDC 4. 5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC; 1. 5 kV for 24 VAC/DC, 48 VDC ±1. 5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 ms, 1-ns rise); ±1 kV (between power terminals) for 48 VDC Malfunction: 8 kV Destruction: 15 kV Destruction:10 to 55 Hz with 0. 75-mm single amplitude each in three directions Malfunction:10 to 55 Hz with 0. 5-mm single amplitude each in three directions Destruction: 980 m/s2 (100G) each in three directions Malfunction: 98 m/s2 (10G) each in three directions Operating:10%C to 55%C (with no icing) Storage: 25%C to 65%C (with no icing) Operating: 35% to 85% Mechanical:10 million operations min. (under no load at 1, 200 operations/h) Electrical: 100, 000 operations min. (5 A at 250 VAC, resistive load at 1, 200 operations/h) Light Gray (Munsell 5Y7/1) IEC: IP40 Approx. 120 g
Impulse withstand voltage
Noise immunity
Static immunity Vibration resistance Shock resistance Ambient temperature Ambient humidity Life expectancy Case color Enclosure ratings Weight
18
H3CR-H
H3CR-H
Engineering Data
10, 000
Switching operations (x 10 3 )
5, 000
1, 000 30 VDC L/R = 7 ms 500 250 VAC/30 VDC (cosf = 1)
Reference: A maximum current of 0. 15 A can be switched at 125 VDC (cosf = 1) and a maximum current of 0. 1 A can be switched if L/R is 7 ms. In both cases, a life of 100, 000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P).
100 250 VAC (cosf = 0. 4)
Load current (A)
Nomenclature
Output indicator (red) Scale range display windows
Time setting knob (for setting power OFF-delay time)
Time range selector (select one from 0. 6, 1. 2, 6, 12)
Time unit display S-series: sec M-series: min
19
H3CR-H
H3CR-H
Operation
Block Diagrams
Without Reset Input (H3CR-H8L)
Time range selector
AC (DC) input
Power supply circuit
Oscillation circuit
Counting circuit
Output circuit
Power failure detection circuit
Indicator circuit
Output indicator
With Reset Input (H3CR-H8RL/-HRL)
Time range selector
AC (DC) input
Power supply circuit
Oscillation circuit
Counting circuit
Output circuit
Power failure detection circuit
Indicator circuit
LCD LCD
Output indicator
Reset input
Input circuit
I/O Functions
Inputs Outputs Reset Control output Turns off the control output and resets the elapsed time. Operates instantaneously when the power is turned on and time-limit resets when the set time is up after the power is turned off.
20
H3CR-H Timing Chart
Model H3CR-H8L
Power ON OFF Rt
H3CR-H
Timing chart
t Rt t
Output (1 3)
Output (1 4)
Output (8 6)
Output (8 5)
Output indicator
Lit Not lit
H3CR-H8RL
Power ON OFF 0. 05 s min. ON (Short-circuited) Reset input OFF (Open) 0. 05 s min. Rt t Rt t
Output (8 6)
Output (8 5) Output indicator
Lit Not lit
H3CR-HRL
Power ON OFF
Rt t
Rt t 0. 05 s min.
Reset input
0. 05 s min.
Output (1 3)
Output (1 4)
Output (11 9)
Output (11 8)
Output indicator
Lit Not lit
Note:
t: Set time Rt: Minimum power ON time (S-series: 0. 1 s min. ; M-series: 2 s min. )
21
H3CR-H
H3CR-H
Dimensions
Note: All units are in millimeters unless otherwise indicated.
15 48 6 78. 0 63. 7 0. 7
H3CR-H8L H3CR-H8RL
48
39 dia
44. 8 x 44. 8
15
78. 0 6 63. 7 0. 7
H3CR-HRL
48
48
39 dia
44. 8 x 44. 8
22
H3CR-H
H3CR-H
Installation
Terminal Arrangement
8-pin Models
Without Reset Input (H3CR-H8L) With Reset Input (H3CR-H8RL)
Reset input
() (~)
(+) (~)
() (~)
(+) (~)
Power supply Note:
Power supply Leave terminal 3 open. Do not use them as relay terminals.
11-pin Model
With Reset Input (H3CR-HRL)
Reset input
()(~)
(+)(~) Note: Power supply Leave terminal 6 open. Do not use them as relay terminals.
23
H3CR-F/G/H
H3CR-F/G/H
Operation
Note: The undermentioned is common for all H3CR-F/G/H models.
Basic Setting
Setting of Selectors
The selectors can be turned clockwise and counterclockwise to select the desired time unit, time range, or operating mode. Each selector has a snap mechanism that secures the selector at a given position. Set the selector at a position at which it is secured. [. . . ] For the H3CR-H, the inrush current is also given for 100/110/120-VAC and 200/220/240-VAC models because these models have higher inrush currents than other series.
30
H3CR-F/G/H Input/Output (H3CR-H)
An appropriate input is applied to the input signal terminal of the Timer when the input terminal for the input signal is short-circuited. Do not attempt to connect any input terminal to any terminal other than the input terminal or to apply voltage across other than the specified input terminals or the internal circuits of the Timer may be damaged.
H3CR-F/G/H Others
If the Timer is mounted on a control board, dismount the timer from the control board or short-circuit the circuitry of the power board before carrying out a voltage withstand test between the electric circuitry and non current-carrying metal part of the Timer, in order to prevent the internal circuitry of the Timer from damage.
Power supply AC or DC
Input contact H3CR Input terminal
*
L
*Do not connect a relay or any other load between these two points, otherwise the internal circuit of the Timer may be damaged due to the high-tension voltage applied to the input terminals. When connecting a relay or a transistor as an external signal input device, pay attention to the following points to prevent short-circuiting due to a sneak current to the transformerless power supply. If a relay or transistor is connected to two or more Timers, the input terminals of those Timers must be wired properly so that they will not be different in phase or the terminals will be short-circuited to one another (refer to the figures below).
Contact or transistor for external input signal H3CR series timer
Input terminal
Power supply
Incorrect
Short-circuit current Input terminal
Input terminal
Power supply
Correct
Input terminal
Environment
When using the Timer in an area with excess electronic noise, separate the Timer, wiring, and the equipment which generates the input signals as far as possible from the noise sources. [. . . ]