[. . . ] Output 1: SPDT 2: DPST-NO
Ordering Information
List of Models
Supply voltage 24 VAC; 12, 24 VDC
Note: Specify both the model number and supply voltage when ordering. Example: H3RN-1 24 VAC Supply voltage
Accessories (Order Separately)
Connecting Socket
Timer H3RN-1/-11 H3RN-2/-21 Track mounting/Front connecting socket P2RF-05-E P2RF-08-E P2R-057P P2R-087P Back connecting socket
Solid-state timer
H3RN
B-97
Specifications
Ratings
Item Time ranges Rated supply voltage Pin type Operating mode Operating voltage range Reset voltage Power consumption H3RN-1/H3RN-2 0. 1 s to 10 min (1 s, 10 s, 1 min, or 10 min max. selectable) 24 VAC (50/60 Hz); 12, 24 VDC Plug-in ON-delay, interval, flicker OFF-start, or flicker-ON start selectable by DIP switch 85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage) (see note) 10% max. [. . . ] (including halfway reset) ±2% FS max. (at 500 VDC) 2, 000 VAC, 50/60 Hz for 1 min (between operating circuit and control output, or contacts of different poles) 1, 000 VAC, 50/60 Hz for 1 min (between non-continuous contacts) Destruction: 10 to 55 Hz, 0. 75-mm single amplitude for 1 h each in 3 directions Malfunction: 10 to 55 Hz, 0. 5-mm single amplitude for 10 min each in 3 directions Destruction: 300 m/s2 Malfunction: 100 m/s2 Operating: Storage: Operating: -10°C to 55°C (with no icing) -25°C to 65°C (with no icing) 35% to 85% H3RN-11/H3RN-21
Vibration resistance Shock resistance Ambient temperature Ambient humidity Life expectancy Impulse withstand voltage Noise immunity Static immunity Degree of protection Weight
Mechanical: 10, 000, 000 operations min. (under no load at 1, 800 operations/h) Electrical: 100, 000 operations min. (3 A at 250 VAC, resistive load at 1, 800 operations/h) Between power terminals: 1 kV ±1. 5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) Destruction: 8 kV Malfunction: 4 kV IP40 (Terminal screw sections are excluded. ) Approx. 18 g
B-98
Solid-state timer H3RN
Item EMC
H3RN-1/H3RN-2 (EMI) Emission Enclosure: Emission AC Mains: (EMS) Immunity ESD:
H3RN-11/H3RN-21
EN61812-1 EN55011 Group 1 class A EN55011 Group 1 class A EN61812-1 EN61000-4-2: 6 kV contact discharge (level 3) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: IEC61000-4-3:10 V/m (80 MHz to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4) Immunity Surge: IEC51000-4-5: 1 kV line to line (level 3) 2 kV line to ground (level 3) UL508, CSA C22. 2 No. 14 Conforms to EN61812-1, IEC60664-1 4 kV/2. Output category according to IEC60947-5-1.
Approved standards
Connections
Connection
H3RN-1/H3RN-11 H3RN-2/H3RN-21
DIN Indication DIN Indication
Timer circuit
OUT PW
Timer circuit
OUT PW
Bottom View
Bottom View
Pulse Operation
A pulse output for a certain period can be obtained with a random external input signal. Use the H3RN in interval mode as shown in the following timing charts.
H3RN-2/H3RN-21
Power (3-8) External short circuit (1-4) External input (1-3)
Timer circuit
50 ms min.
Time limit contact NO (6-5) Run/Power indicator (PW) Output indicator (OUT) External input
Note: t: Set time Rt: Reset time
!Caution
Be careful when connecting wires. Mode Pulse operation Power supply between 3 and 8 Short-circuit between 4 and 1 Input signal between 3 and 1 Terminals
Operating mode; interval and all other Power supply between 1 and 8 modes
Solid-state timer
H3RN
B-99
Timers
Operation
Timing Chart
Operating mode H3RN-1/H3RN-11 Timing chart H3RN-2/H3RN-21
ON-delay
Power (1-5) Power Output Time limit contact NC (4-2) Time limit contact NO (4-3) Run/Power indicator (PW) Output indicator (OUT) Power (1-8) Time limit contact NO (4-3, 5-6) Run/Power indicator (PW) Output indicator (OUT)
Interval
Power (1-5) Power Time limit contact NC (4-2) Time limit contact NO (4-3) Run/Power indicator (PW) Output indicator (OUT) Power (1-8) Time limit contact NO (4-3, 5-6) Run/Power indicator (PW) Output indicator (OUT)
Output
Flicker OFF-start
Power (1-5) Power Output Power (1-8) Time limit contact NC (4-2) Time limit contact NO (4-3) Run/Power indicator (PW) Output indicator (OUT) Time limit contact NO (4-3, 5-6) Run/Power indicator (PW) Output indicator (OUT)
Flicker ON-start
Power (1-5) Power Output Time limit contact NC (4-2) Time limit contact NO (4-3) Run/Power indicator (PW) Output indicator (OUT) Power (1-8) Time limit contact NO (4-3, 5-6) Run/Power indicator (PW) Output indicator (OUT)
Note: t: Set time Rt: Reset time
B-100
Solid-state timer H3RN
DIP Switch Settings
The 1-s range and ON-delay mode for H3RN-1/-2, 1-min range and ON-delay mode for H3RN-11/-21 are factory-set before shipping. Timers
Time Ranges
Model H3RN-1, H3RN-2 Time range 1s 10 s 1 min 10 min H3RN-11, H3RN-21 1 min 10 min 1h 10 h Time setting range 0. 1 to 1 s 1 to 10 s 0. 1 to 1 min 1 to 10 min 0. 1 to 1 min 1 to 10 min 0. 1 to 1 h 1 to 10 h Setting Factory-set Yes No No No Yes No No No
Note: The left two DIP switch pins are used to select the time ranges.
Operating Modes
Operating mode ON-delay Interval Flicker OFF-start Flicker ON-start Setting Factory-set Yes No No No
Note: The right two DIP switch pins are used to select the operating modes.
Nomenclature
Run/Power Indicator (Green) (Lit: Power ON) Main Dial Set the desired time according to time range selectable by DIP switch.
Output Indicator (Orange) (Lit: Output ON)
Solid-state timer
H3RN
B-101
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Timers
H3RN-1/H3RN-11 Front Mounting
H3RN-2/H3RN-21 Front Mounting
Mounting Height
Use the P2RF-@-E or P2R-@7P to mount the H3RN. When ordering any one of these sockets, replace "@" with "05" for SPDT or "08" for DPST-NO. The P2RF-@ cannot be used because the hook is a different shape.
P2RF-@-E
P2R-@7P
H3RN Series
H3RN Series 80. 9 (see note 1) (84. 9) (see note 2) 79. 5 (see note 1) (83. 5) (see note 2)
P2RF-@-E Socket
P2R-@7P Socket
Note: 1. The value shown indicates the dimension for the P2RF-05-E with the PFP-@N Mounting Rail. The value is 71. 5 mm when using the PFP-N@2. The value shown in parentheses indicates the dimension for the P2RF-08-E with the PFP-@N Mounting Rail. The value is 75. 5 mm when using the PFP-N@2.
B-102
Solid-state timer H3RN
Precautions
When using the H3RN in any place where the ambient temperature is more than 50°C, supply 90% to 110% of the rated voltages (at 12 VDC: 95% to 110%). [. . . ] Position the H3RN to provide the necessary clearance for the voltage used. When using the P2RF-@-E or P2R-057P Socket, basic insulation is ensured in the mounted condition for a voltage of 250 VAC max.
Solid-state timer
H3RN
B-103
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0. 03937. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON H3RN
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.