[. . . ] N128-E1-01D
K3HB-S/-X/-V/-H
Digital Indicators
USER'S MANUAL
Preface
Thank you for purchasing the K3HB. This manual describes the functions, performance, and application methods needed for optimum use of the K3HB. Please observe the following items when using the K3HB.
· This product is designed for use by qualified personnel with a knowledge of electrical systems. · Read this manual carefully and make sure you understand it well to ensure that you are using the K3HB correctly. [. . . ] J Use the U [UP] and S [SHIFT] Keys to change the timing delay. · Units: ms for the K3HB-S, 100 ms for the K3HB-X/V/H K Press the M [MODE] Key to switch to the next parameter. L Press the L [LEVEL] Key for at least 1 s to return to RUN level.
L
1
on-t
0000
US
L
1
on-t
0020
M
L
1
off-t
0
S
L
1
off-t
0000
Functions and Operations
US
L
1
off-t
0010
M L
1 s min.
L
1
z-lim
off
123. 4
5-35
Section 5 Functions and Operations
5. 12 Eliminating Drift Near "0"
Input adjustment level
The zero limit function makes all measurement values "0" for inputs lower than a set value. Explanation of Functions Zero-limit
If the input value is less than the set value, the measurement value becomes "0. " This function is effective to eliminate display drift and displacement near "0. "
L1
z-lim
(Z-LIM)
Set the following parameter for zero-limit. The zero-limit value can be set only when zero-limit has been enabled. Parameter Zero-limit z-lim Zero-limit value lim-p Set value on/off 0 to 99 Meaning of set value on: Enabled off: Disabled 0 to 99 *
L1
lim-p
(LIM-P)
* The decimal point depends on the "decimal point position" setting. Parameter Setting Procedure A Press the L [LEVEL] Key for at least 3 s in RUN level to move to the initial setting level. · "L 0" is displayed on the level/bank display to indicate the initial setting level. B Press the L [LEVEL] Key again once (less than 1 s) to move to the input adjustment level. · "L 1" is displayed on the level/bank display. C Press the M [MODE] Key several times to switch the PV display to "z-lim. "
L
3 s min.
L
0
Displays "L 0. "
Functions and Operations
L
Less than 1 s
L
1
tmg-h
nomal
Displays "L 1. "
M S
L
1
z-lim
off
D Press the S [SHIFT] Key to make the SV display flash. · The setting can be changed when the SV display starts to flash. E Use the U [UP] Key to change the set value to "on. " · Change the set value to "off" to disable the setting. F Press the M [MODE] Key to switch to the next parameter "lim-p. " · The set value is registered.
L
1
z-lim
off
U
L
1
z-lim
on
M
L
1
lim-p
0
5-36
5. 12 Eliminating Drift Near "0"
G Press the S [SHIFT] Key to make the SV display flash. · The setting can be changed when the SV display starts to flash. H Use the U [UP] and S [SHIFT] Key to change the zero-limit value.
M
L
1
lim-p
00
US
L
1
lim-p
0010
I
Press the M [MODE] Key to switch to the next parameter. · The set value is registered.
M L
1 s min.
L
1
step
off
J Press the L [LEVEL] Key for at least 1 s to return to RUN level.
1234. 5
Functions and Operations
5-37
Section 5 Functions and Operations
5. 13 Averaging Inputs
Input adjustment level
X
V
S
H
The averaging function smooths the displays and outputs for input values with dramatic fluctuations, such as spike noise.
Explanation of Functions
Average processing
There are two types of averaging: "simple" and "moving. " Select one type. The number of samples ("averaging times") can also be specified for the input values to be averaged. Simple average is used when the display refresh period is to be lengthened. Moving average is used to remove periodic noise superimposed on input signals. [. . . ] The setting to be changed will flash.
To next parameter.
Appendices
A-25
Appendices
Sampling and Comparative Output Response Times
The K3HB-S sampling and comparative output response times depend on the calculations, timing hold type, and, for simple averaging, the averaging times. Refer to the following description for details.
Output Refresh Period
The K3HB-S repeats input reads, calculation, and judgement output processing. The output refresh period differs depending on whether there are one or two inputs, as outlined below.
One input 0. 5 ms Input Input A or Input B Output Input read Output refresh Output Output Output Output 0. 5 ms Input 0. 5 ms Input Input Input Input
Every 0. 5 ms Every 0. 5 ms
Two inputs 0. 5 ms Input Input A Input B Output Input read Output Output Output Output Output 0. 5 ms Input 0. 5 ms Input Input Input Input Input
Input A: every 1 ms Input B: every 1 ms
Output refresh Every 0. 5 ms
Appendices
A-26
Sampling and Comparative Output Response Times
Output Response Time
The comparative output response time is the sum of the data processing time and the output (relay or transistor) response time.
One input 0. 5 ms 0. 5 ms 0. 5 ms Data processing time
R R R R
Output response time (See note 1. )
Two inputs 0. 5 ms 0. 5 ms
0. 5 ms
0. 5 ms Data processing time
R
R
R
R
R
Output response time (See note 1. )
(Note 1. ) For transistor outputs For one input: OFF ON 1 ms and ON OFF 1. 5 ms For two inputs: OFF ON 2 ms and ON OFF 2. 5 ms For relay outputs The relay operation time of 10 ms is added to the transistor output response times.
Operation Timing Examples
Example 1 The Unit operates as shown in the diagram to the right for the settings shown in the table below. Calculation Timing hold mode Averaging times (n) A Normal Once
Output Output Output Output Output Output Comparative output response time 0. 5 ms + output response time (See note 1. )
0. 5 Input
0. 5 Input
0. 5 Input
0. 5 Input
0. 5 Input Input
Example 2 The Unit operates as shown in the diagram to the right for the settings shown in the table below. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE OMRON K3HB-H
Lastmanuals offers a socially driven service of sharing, storing and searching manuals related to use of hardware and software : user guide, owner's manual, quick start guide, technical datasheets... In any way can't Lastmanuals be held responsible if the document you are looking for is not available, incomplete, in a different language than yours, or if the model or language do not match the description. Lastmanuals, for instance, does not offer a translation service.
Click on "Download the user manual" at the end of this Contract if you accept its terms, the downloading of the manual OMRON K3HB-H will begin.