Detailed instructions for use are in the User's Guide.
[. . . ] 0. 9 W 0. 9 to 1. 1 VA (60 Hz) Must operate voltage 80% max. voltage Power consumption (approx. ) 1. 0 to 1. 2 VA (60 Hz) 50 Hz AC 6 V* 12 V 24 V 48/50 V* 110/120 V 220/240 V DC 6 V* 12 V 24 V 48 V* 100/110 V 214. 1 mA 106. 5 mA 53. 8 mA 24. 7/ 25. 7 mA 9. 9/10. 8 mA 4. 8/5. 3 mA 151 mA 75 mA 37. 7 mA 18. 8 mA 9. 0/9. 9 mA 60 Hz 183 mA 91 mA 46 mA 21. 1/ 22. 0 mA 8. 4/9. 2 mA 4. 2/4. 6 mA % of rated voltage 110%
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for rated currents and ±15% for DC coil resistance. Performance characteristic data are measured at a coil temperature of 23°C. [. . . ] of poles 2 4 Coil ratings 6, 12, 24, 48/50, 100/110 110/120, 200/220, 220/240 VAC 6, 12, 24, 48, 100/110, 125 VDC Contact ratings 10 A, 250 VAC (cos=1) 10 A, 30 VDC (L/R=0 ms) 5 A, 250 VAC (cos=1) 5 A, 30 VDC (L/R=0 ms) 10 x 10
3
Operations
100 x 103 MY4Z AC; 50 x 103
UL508 Recognitions (File No. of poles 2 4 Coil ratings 6 to 240 VAC 6 to 125 VDC Contact ratings 10 A, 30 VDC (General purpose) 10 A, 250 VAC (General purpose) 5 A, 250 VAC (General purpose) 5 A, 30 VDC (General purpose) 6 x 10
3
Operations
CSA C22. 2 No. of poles 2 4 Coil ratings 6 to 240 VAC 6 to 125 VDC 10 A, 30 VDC 10 A, 250 VAC 5 A, 250 VAC (Same polarity) 5 A, 30 VDC (Same polarity) Contact ratings 6 x 103 Operations
IMQ (File No. of poles 2 4 Coil ratings 6, 12, 24, 48/50, 100/110 110/120, 200/220, 220/240 VAC 6, 12, 24, 48, 100/110, 125 VDC 10 A, 30 VDC 10 A, 250 VAC 5 A, 250 VAC 5 A, 30 VDC Contact ratings 10 x 103 100 x 103 MY4Z AC; 50 x 103 Operations
LR Recognitions (File No. of poles 2 Coil ratings 6 to 240 VAC 6 to 125 VDC Contact ratings 10 A, 250 VAC (Resistive) 2 A, 250 VAC (PF0. 4) 10 A, 30 VDC (Resistive) 2 A, 30 VDC (L/R=7 ms) 5 A, 250 VAC (Resistive) 0. 8 A, 250 VAC (PF0. 4) 5 A, 30 VDC (Resistive) 1. 5 A, 30 VDC (L/R=7 ms) 50 x 103 Operations
4
50 x 103
SEV Listings (File No. of poles 2 4 Coil ratings 6 to 240 VAC 6 to 125 VDC 10 A, 250 VAC 10 A, 30 VDC 5 A, 250 VAC 5 A, 30 VDC Contact ratings 10 x 10
3
Operations
100 x 103 MY4Z AC; 50 x 103
4
General-purpose Relay MY
New model
Engineering Data
Maximum Switching Power
MY2
Switching current (A)
MY4, MY4Z
Switching current (A)
AC resistive load AC inductive load (cos=0. 4)
AC resistive load AC inductive load (cos=0. 4)
DC resistive load
DC resistive load
DC inductive load (L/R=7 ms)
DC inductive load (L/R=7 ms)
Switching voltage (V)
Switching voltage (V)
Endurance
MY2 (Resistive Loads)
Endurance (x10 3 operations)
10000 5000 3000 1000 500 300 30 VDC 30 VDC 250 VAC
MY2 (Inductive Loads)
Endurance (x10 3operations)
10000 5000 3000 1000 500 300 250 VAC 30 VDC
30 VDC 250 VAC
100 50 30 10
250 VAC
100 50 30 10
Switching current (A)
Switching current (A)
MY4 (Resistive Loads)
Endurance (x10 3 operations)
10000 5000 3000 1000 500 300
MY4 (Inductive Loads)
Endurance (x10 3 operations)
10000 5000 3000
250 VAC
30 VDC
1000 500 300
30 VDC 30 VDC
30 VDC 250 VAC
100
100 50 30 10
250 VAC
50 30 10
250 VAC
Switching current (A)
Switching current (A)
General-purpose Relay
MY New model
5
MY4Z (Resistive Loads)
Endurance (x10 3 operations)
10000 5000 3000 1000 500 300 30 VDC 100 50 30 10 30 VDC 250 VAC
MY4Z (Inductive Loads)
Endurance (x10 3operations)
10000 5000 3000 1000 500 300 30 VDC 30 VDC 100 50 30 10 250 VAC
250 VAC
250 VAC
Switching Current (A)
Switching Current (A)
Technical and Environmental Properties
2-Pole model Tracking Resistance Environmental Protection Flammability Class Pollution Degree Creepage Distance Clearance Distance Contact Material 600 CTI (base) RT1 Base, Insulator, Spool Case, Indicator, Nameplate, Push Button 2 4. 0 mm 3. 0 mm Ag 1 3. 2 mm 3. 0 mm AgNi + Au 600 CTI (base) RT1 ul 94V-0 ul 94V-2 4-Pole model
6
General-purpose Relay MY
New model
Typical information for reference only
The following data is provided as experimental and/or calculated data for reference only. These figures fall under the category of typical behaviour and the operation of individual relays will vary according to the exact operating conditions. Typical Operate / Release Times AC Type (operate / release time) DC Type (operate / release time) Load reduction Factor
1
2-Pole model 8 ms/8 ms 14 ms/4 ms
4-Pole model 10 ms/10 ms 14 ms/6 ms
0. 8
For AC inductive loads (such as solenoids, contactors coils, etc. ) the reduction factor corresponding to cos(p. f. ) (cosine of the power factor) is multiplied by the rated current in order to identify the maximum allowable current. This approximation is not valid for loads with high inrush currents such as electric motors or fluorescent lamps.
Reduction factor
0. 6
0. 4
1
0. 8
0. 6
0. 4
0. 2
cos(p. f. )
Multiple Contact DC Switching Capacity Switching capacity of DC resistive load
100
Effect of temperature on coil voltages MY2/4 Operating range (DC and AC type) vs ambient temperature
2
1 10 1. 5
Switching Current (A)
MY4
U/Un
2 1
1. 0 4 contacts 3 contacts 2 contacts in series
MY2 1: Max coil voltage permitted. 2: Min pick-up voltage with coil at ambient temperature
0, 1 20
0. 5 40 60 80 100 120 140 160 180 200 220 0 10 20 30 40 50 60 70 80
Switching Voltage (Vdc)
Ambient temperature (°C)
This graph can be used to estimate the number of contacts that can be This graph shows the typical relationship between the maximum / miniused to switch DC resistive loads mum coil and pick-up voltage and ambient temperature
General-purpose Relay
MY New model
7
Dimensions
Note: All units are in millimeters unless otherwise indicated.
2-Pole Models
MY2N
2. 6
Eight, 1. 2 dia. × 2. 2 long holes
0. 5
28 max.
36 max.
6. 4
21. 5 max.
4-Pole Models
MY4N
2. 6
Eight, 1. 2 dia. × 2. 2 long holes
0. 5
28 max.
36 max.
6. 4 21. 5 max.
Models with Test Button
MY2IN
2. 6
6. 3
8
Eight, 1. 2 dia. × 2. 2 long holes
28 max.
80. 5
5
14. 2
36 max. 21. 5 max.
MY4IN
2. 6
6. 3
8
Fourteen, 1. 2 dia. × 2. 2 long holes
0. 5
28 max.
14. 2
80. 5
5
36 max. Dielectric withstand voltage 2, 000 VAC, 1 min Insulation resistance (see note 2) Less than 1, 000 M
10
General-purpose Relay MY
New model
s Dimensions
Note: All units are in millimeters unless otherwise indicated. Socket Dimensions Terminal arrangement/ Internal connections (top view)
38. 2 max. 36. 5 max.
Mounting holes
PYF08S
23. 2 max.
---
85 max.
(5. 3)
PYF08A-E
Two, 4. 2 x 5 mounting holes
Two, M3, M4, or 4. 5-dia. holes
Eight, M3 x 8 sems screws
72 max.
(TOP VIEW)
23 max. 31 max.
Note: Track mounting is also possible. [. . . ] holes
PY14/PY14-Y1
(See note)
Fourteen, 3 x 1. 2 elliptical holes
25. 5 max. 29. 5 max.
42 max.
20 max.
24 max.
Note: The PY14-Y1 includes sections indicated by dotted lines. PY14QN/ PY14QN-Y1
(See note) 29. 5 max.
41. 5 max.
42 max.
22 max. 24 max.
Note: The PY14QN-Y1 includes sections indicated by dotted lines.
PY14-02